126 MIRAMAR AVE

Oceanview/Merced/Ingleside · San Francisco, CA · Parcel 6983028 · Last violation Aug 26, 2024 · Last complaint Dec 28, 2024

NeighborhoodOceanview/Merced/Ingleside
More violations than 99% of nearby buildings
More violations than 99% of buildings and more complaints than 97% of buildings in Oceanview/Merced/Ingleside. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 10 violations · 13 complaints
'22'24ViolationsComplaints
Severityⓘopen violations
6 open fire-safety violations
Active Notices of Violation issued by the Department of Building Inspection.
Open fire-safety violations6
Open lead violations0
311 Housing Complaints
Total complaints since 2022
29
6 per year avg.↓ Down 13% in the last 2 years (13 vs 15 prior 2 yrs)
Reported issues
13
Heatⓘ8
Leadⓘ1
Pestsⓘ2
Dept. of Building Inspection Violations
Total violations since 2022
72
14 per year avg.↓ Down 82% in the last 2 years (10 vs 55 prior 2 yrs)
Open violations
60
Fire safetyⓘ6
Leadⓘ0

Top violation categories

5 yrsAll time
building sectionⓘ28 violations
other sectionⓘ12 violations
plumbing and electrical sectionⓘ9 violations
fire sectionⓘ6 violations
interior surfaces sectionⓘ6 violations
smoke detection sectionⓘ4 violations
sanitation sectionⓘ3 violations
security requirements sectionⓘ3 violations
Unknownⓘ1 violations

Top complaint types

5 yrsAll time
Hot Water Lack Of Hot Water5 complaints
Doors Windows Broken Defective4 complaints
Electrical Hazardous Condition3 complaints
Heat Lack Of Heat3 complaints
Plumbing Broken Leaking2 complaints
Mold And Mildew2 complaints
Infestation Rodent Insect2 complaints
Deck Stairs Handrails2 complaints
Ventilation Inadequate Or None1 complaints
Electrical Non Hazard1 complaints
General Maintenance Not In List Above1 complaints
Illegal Construction No Permit Exceeds Permit Scope1 complaints
Paint Lead Violating Safe Practices1 complaints
Paint Peeling1 complaints
Hide violations (72) ↑See complaints (29) →

Violation log

60 DBI violations · Open

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
OpenAug 26, 2024building sectionrepair/secure/replace ground floor side exit gate. (1001(b)(13)hc)repair/secure/replace ground floor exterior side exit gate. the base of the supporting members and framing has deteriorated and the framing and gate are leaning and falling over. currently this situation creates safety hazard. repair/secure/replace the framing/gate within 48 hours. **building permit and approval is required. (note: a similar notice was issued on 7/29/24, complaint #202424682 item #2), however this situation is now a safety hazard and requires new notice of violation for this issue.
See something wrong? File a complaint with SF 311
OpenAug 26, 2024building sectionthis notice includes violations for the areas noted.126 miramar ave.
OpenAug 26, 2024other sectioninspector commentsdue to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenAug 9, 2024interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.—
OpenAug 9, 2024building sectionthis notice includes violations for the areas noted.126 miramar ave.
OpenAug 9, 2024interior surfaces sectionremove or cover damaged paint in an approved manner to prevent a lead hazard, weather protection and paint the areas. see attached lead hazard warning. (703, 1001-h, 1001 b-13, 1001-d sfhc , 3426 et.seq. sfbc)remove or cover and repaint all chipping & peeling paint at all exposed surfaces of building in a lead safe manner (sfbc 3426 et.seq.) **note: ensure that the proper procedures are followed when there is the possibility of disturbing lead based paint.
OpenAug 9, 2024other sectioninspector commentsdue to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenAug 8, 2024other sectionprovide hot water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps. (505d(3))provide hot water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps(within 48 hours.) at time of inspection, the gas connection to the water heater has been disconnected and the gas valve shut off. per p g & e service report issued 8/6/24 states "found high co @ h20 heater. disconnected, capped and issued hazard notice. co reads above threshold. refer to licensed contractor for service. hazard notice states "high co @ h20 htr. ****have a licensced professional inspect the flue system and connections at the water heater and furnace and make necessary repairs to insure they are working properly and pose no hazard to the occupants and/or surrounding areas. provide written report of work performed to ensure safety.
OpenAug 8, 2024other sectioninspector commentsdue to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenAug 8, 2024building sectionthis notice includes violations for the areas noted.126 miramar ave.
OpenJun 12, 2024plumbing and electrical sectionreplace deteriorated interior base of upstairs bathroom sink cabinet.(1001f hc)replace deteriorated interior base of upstairs bathroom sink cabinet.
OpenJun 12, 2024building sectionrepair second floor rear exit door.(1001(b)(13)hc)repair second floor rear exit door to proper working order. currenly the door is difficult to close and gets stuck in the framing.
OpenJun 12, 2024building sectionrepair window to proper working order (1001(h),708 hc)replace/repair both front windows to proper working order. currently the aluminum front windows get stuck in the framing, do not seal or lock correctly and allow air infiltration. **note: if windows are replace, permit and approval required.
OpenJun 12, 2024building sectionrepair ground floor side gate and framing (1001(b)(13) hc)repair ground floor side gate and framing which is broken and deteriorated. door needs to function properly when work is completed.
OpenJun 12, 2024other sectioninspector commentsdue to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenJun 12, 2024plumbing and electrical sectionrepair electrical outlet (1001e hc)repair electrical outlet in upstairs bathroom to proper working order.
OpenJun 12, 2024building sectionrepair hand/guardrails,deck & stairs (802(c),1001(b)(13)hc)deterioration was noted on the rear exterior egress stair supports, hand/guardrail and deck. some of the guard/handrails, deck boards and supports, and stair stringers on the deck and stairs have signs of wood detioration and are in need of repair, replacement and/or securing. have a general contractor, architect, or structural engineer inspect stairs and provide a written report with recommended repairs, then make repairs or replace as necessary to ensure stability and safety. **obtain a building permit, commence repairs and have inspected and approved by the district building inspector.
OpenJun 12, 2024plumbing and electrical sectionrepair/provide/replace kithcen exhaust fan and grills (1001 hc)repair/provide/replace kithcen exhaust fan and grills. grills need to be reinstalled and ensure exhaust fan is functioning properly.
OpenJun 12, 2024building sectionthis notice includes violations for the areas noted.126 miramar ave.
OpenJun 12, 2024building sectionrepair entrance gate latch(1001(b)(13) hc)repair entrance gate latch to proper working order.
OpenFeb 9, 2024———
OpenOct 26, 2023other sectioninspector commentsdue to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenOct 26, 2023other sectionprovide heat to each occupied habitable room capable of maintaining a min. room temp. of 70 degrees f. (21 degrees c.). (701(a) hc)provide heat to the unit within 48 hours. at time of inspection the gas service was shut off to the property per pg & e service report. **have a licensced professional inspect the gas service and all gas appliances to insure they are working properly and pose no hazard to the occupants and/or surrounding areas. provide written report of work performed to ensure safety. **permit may be required if work is extensive.
OpenOct 26, 2023other sectionprovide unit with water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps. (505d(3))provide hot water to the unit within 48 hours. at time of inspection the gas service was shut off to the property per pg & e service report. **have a licensced professional inspect the gas service and all gas appliances to insure they are working properly and pose no hazard to the occupants and/or surrounding areas. provide written report of work performed to ensure safety. **permit may be required if work is extensive.
OpenOct 26, 2023building sectionthis notice includes violations for the areas noted.126 miramar ave.
OpenOct 20, 2023plumbing and electrical sectionrepair toilet (1001f hc)repair toilet in the basement to proper working order. at time of inspection the toilet was clogged.
OpenOct 20, 2023other sectioninspector commentsdue to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenOct 20, 2023building sectionthis notice includes violations for the areas noted.126 miramar ave
OpenOct 20, 2023plumbing and electrical sectionprovide working doorbell (1001 hc)repair/replace/provide working doorbell.
OpenFeb 8, 2023interior surfaces sectionmake necessary repairs to rear exterior door.—
OpenFeb 8, 2023plumbing and electrical sectionmake necessary repairs to light fixture/mechanical vent. 504 & 1001(g) sfhcat time of inspection, the light did not turn on and the fixture was helld up with duct tape. repair using approved materials.
OpenFeb 8, 2023interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.—
OpenFeb 8, 2023building sectionthis notice includes violations for the areas noted.126 miramar avenue
OpenFeb 8, 2023fire sectionrepair inoperable light fixture. 504 & 1001(b) sfhcat time of inspection, kitchen light did not work. make necessary repairs.
OpenFeb 8, 2023smoke detection sectionremove duct tape covering floor vent. 1001(i) sfhcat time of inspection, heat vent on the floor had been completely covered in duct tape. remove tape to prevent fire hazard. cover vent in an approved manner, using approved materials if no longer in use.
OpenFeb 8, 2023sanitation sectionremove unpermitted stairs/ladder to attic and replace with an approved means of access. 1001(b) sfhcat time of inspection, stairs/ladder providing access to the attic had differing rises and runs; were missing rungs/steps and appeareed to be installed without the benefit of any permits. remove and replace with an approved means of access. ***building permit required*** in order to abate this violation, a building permit application must be obtained and finalized prior to re-inspection date.
OpenFeb 8, 2023other sectioninspector commentsviolations cited herein constitute a nuisance pursuant to sections 401 and 1001(d) of the san francisco housing code. it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. repairs cited in this notice require a building, plumbing and /or electrical permit. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, plans and permits indicating that all work under building, plumbing and electrical permits is complete. prior to reinspection by housing inspector, call building, plumbing and electrical inspectors for required inspections.
OpenFeb 8, 2023building sectionprovide cover to electrical junction box. 1001(e) sfhcprovide coverplate over electrical junction box located along the wall of the ground floor storage area.
OpenFeb 8, 2023plumbing and electrical sectionmake necessary repairs to bathroom (inside the unit).—
OpenFeb 8, 2023interior surfaces sectionremove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. 1301 sfhcremove or cover damaged and peeling paint on rear exterior door in an approved manner. ***see lead hazard warning***
OpenFeb 8, 2023smoke detection sectionreplace missing crown molding. 1001(b) sfhcat time of inspection, crown molding had been removed.
OpenFeb 8, 2023fire sectionreplace missing baseboards in kitchen. 1001(b) sfhcat time of inspection, the baseboards in the kitchen had been removed. replace baseboards.
OpenFeb 8, 2023sanitation sectionmake necessary repairs in front room/foyer.—
OpenFeb 8, 2023security requirements sectionrepair light fixture. 504 & 1001(e) sfhcat time of inspection, light fixture was coming out of the ceiling. make needed repairs.
OpenFeb 8, 2023building sectionrepair electrical outlet and provide coverplate. 504 & 1001(e) sfhcat groundfloor bathroom, make necessary repairs to electrical outlet located just above the bathroom vanity and proved a cover plate. at time of inspection outlet was coming out og the wall and missing a cover plate.
OpenFeb 8, 2023fire sectioneliminate rodent infestation. 1001(b) & 1306 sfhcat time of inspection, mouse droppings were observed in the kitchen. provide pest control services to eliminate infestation.
OpenFeb 8, 2023sanitation sectionreplace missing cover plate for lightswitch. 504 sfhcprovide a coverplate for light switch.
OpenFeb 8, 2023security requirements sectionprovide weatherproofing to windows. 708 sfhcat time of inspection, windows had small gaps which allowed cold air to enter. repair so that windows are weatherproof.
OpenFeb 8, 2023building sectionrepair malfunctioning mechanical ventilation/fan. 504(c) & 1001(g) sfhcmake necessary repairs/replacements to malfunctioning fan in ground floor bathroom.
OpenFeb 8, 2023fire sectionreattach cover of heat vent. 1001(b) sfhcreattach heat vent cover. at time of inspection vent cover had been removed.
OpenAug 26, 2024
building section · repair/secure/replace ground floor side exit gate. (1001(b)(13)hc)
repair/secure/replace ground floor exterior side exit gate. the base of the supporting members and framing has deteriorated and the framing and gate are leaning and falling over. currently this situation creates safety hazard. repair/secure/replace the framing/gate within 48 hours. **building permit and approval is required. (note: a similar notice was issued on 7/29/24, complaint #202424682 item #2), however this situation is now a safety hazard and requires new notice of violation for this issue.
OpenAug 26, 2024
building section · this notice includes violations for the areas noted.
126 miramar ave.
OpenAug 26, 2024
other section · inspector comments
due to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenAug 9, 2024
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
OpenAug 9, 2024
building section · this notice includes violations for the areas noted.
126 miramar ave.
OpenAug 9, 2024
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard, weather protection and paint the areas. see attached lead hazard warning. (703, 1001-h, 1001 b-13, 1001-d sfhc , 3426 et.seq. sfbc)
remove or cover and repaint all chipping & peeling paint at all exposed surfaces of building in a lead safe manner (sfbc 3426 et.seq.) **note: ensure that the proper procedures are followed when there is the possibility of disturbing lead based paint.
OpenAug 9, 2024
other section · inspector comments
due to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenAug 8, 2024
other section · provide hot water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps. (505d(3))
provide hot water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps(within 48 hours.) at time of inspection, the gas connection to the water heater has been disconnected and the gas valve shut off. per p g & e service report issued 8/6/24 states "found high co @ h20 heater. disconnected, capped and issued hazard notice. co reads above threshold. refer to licensed contractor for service. hazard notice states "high co @ h20 htr. ****have a licensced professional inspect the flue system and connections at the water heater and furnace and make necessary repairs to insure they are working properly and pose no hazard to the occupants and/or surrounding areas. provide written report of work performed to ensure safety.
OpenAug 8, 2024
other section · inspector comments
due to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenAug 8, 2024
building section · this notice includes violations for the areas noted.
126 miramar ave.
OpenJun 12, 2024
plumbing and electrical section · replace deteriorated interior base of upstairs bathroom sink cabinet.(1001f hc)
replace deteriorated interior base of upstairs bathroom sink cabinet.
OpenJun 12, 2024
building section · repair second floor rear exit door.(1001(b)(13)hc)
repair second floor rear exit door to proper working order. currenly the door is difficult to close and gets stuck in the framing.
OpenJun 12, 2024
building section · repair window to proper working order (1001(h),708 hc)
replace/repair both front windows to proper working order. currently the aluminum front windows get stuck in the framing, do not seal or lock correctly and allow air infiltration. **note: if windows are replace, permit and approval required.
OpenJun 12, 2024
building section · repair ground floor side gate and framing (1001(b)(13) hc)
repair ground floor side gate and framing which is broken and deteriorated. door needs to function properly when work is completed.
OpenJun 12, 2024
other section · inspector comments
due to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenJun 12, 2024
plumbing and electrical section · repair electrical outlet (1001e hc)
repair electrical outlet in upstairs bathroom to proper working order.
OpenJun 12, 2024
building section · repair hand/guardrails,deck & stairs (802(c),1001(b)(13)hc)
deterioration was noted on the rear exterior egress stair supports, hand/guardrail and deck. some of the guard/handrails, deck boards and supports, and stair stringers on the deck and stairs have signs of wood detioration and are in need of repair, replacement and/or securing. have a general contractor, architect, or structural engineer inspect stairs and provide a written report with recommended repairs, then make repairs or replace as necessary to ensure stability and safety. **obtain a building permit, commence repairs and have inspected and approved by the district building inspector.
OpenJun 12, 2024
plumbing and electrical section · repair/provide/replace kithcen exhaust fan and grills (1001 hc)
repair/provide/replace kithcen exhaust fan and grills. grills need to be reinstalled and ensure exhaust fan is functioning properly.
OpenJun 12, 2024
building section · this notice includes violations for the areas noted.
126 miramar ave.
OpenJun 12, 2024
building section · repair entrance gate latch(1001(b)(13) hc)
repair entrance gate latch to proper working order.
OpenFeb 9, 2024
—
OpenOct 26, 2023
other section · inspector comments
due to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenOct 26, 2023
other section · provide heat to each occupied habitable room capable of maintaining a min. room temp. of 70 degrees f. (21 degrees c.). (701(a) hc)
provide heat to the unit within 48 hours. at time of inspection the gas service was shut off to the property per pg & e service report. **have a licensced professional inspect the gas service and all gas appliances to insure they are working properly and pose no hazard to the occupants and/or surrounding areas. provide written report of work performed to ensure safety. **permit may be required if work is extensive.
OpenOct 26, 2023
other section · provide unit with water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps. (505d(3))
provide hot water to the unit within 48 hours. at time of inspection the gas service was shut off to the property per pg & e service report. **have a licensced professional inspect the gas service and all gas appliances to insure they are working properly and pose no hazard to the occupants and/or surrounding areas. provide written report of work performed to ensure safety. **permit may be required if work is extensive.
OpenOct 26, 2023
building section · this notice includes violations for the areas noted.
126 miramar ave.
OpenOct 20, 2023
plumbing and electrical section · repair toilet (1001f hc)
repair toilet in the basement to proper working order. at time of inspection the toilet was clogged.
OpenOct 20, 2023
other section · inspector comments
due to the violations noted, this constitutes a nuisance per the san francisco housing code section 1001(d) it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
OpenOct 20, 2023
building section · this notice includes violations for the areas noted.
126 miramar ave
OpenOct 20, 2023
plumbing and electrical section · provide working doorbell (1001 hc)
repair/replace/provide working doorbell.
OpenFeb 8, 2023
interior surfaces section · make necessary repairs to rear exterior door.
OpenFeb 8, 2023
plumbing and electrical section · make necessary repairs to light fixture/mechanical vent. 504 & 1001(g) sfhc
at time of inspection, the light did not turn on and the fixture was helld up with duct tape. repair using approved materials.
OpenFeb 8, 2023
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
OpenFeb 8, 2023
building section · this notice includes violations for the areas noted.
126 miramar avenue
OpenFeb 8, 2023
fire section · repair inoperable light fixture. 504 & 1001(b) sfhc
at time of inspection, kitchen light did not work. make necessary repairs.
OpenFeb 8, 2023
smoke detection section · remove duct tape covering floor vent. 1001(i) sfhc
at time of inspection, heat vent on the floor had been completely covered in duct tape. remove tape to prevent fire hazard. cover vent in an approved manner, using approved materials if no longer in use.
OpenFeb 8, 2023
sanitation section · remove unpermitted stairs/ladder to attic and replace with an approved means of access. 1001(b) sfhc
at time of inspection, stairs/ladder providing access to the attic had differing rises and runs; were missing rungs/steps and appeareed to be installed without the benefit of any permits. remove and replace with an approved means of access. ***building permit required*** in order to abate this violation, a building permit application must be obtained and finalized prior to re-inspection date.
OpenFeb 8, 2023
other section · inspector comments
violations cited herein constitute a nuisance pursuant to sections 401 and 1001(d) of the san francisco housing code. it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. repairs cited in this notice require a building, plumbing and /or electrical permit. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, plans and permits indicating that all work under building, plumbing and electrical permits is complete. prior to reinspection by housing inspector, call building, plumbing and electrical inspectors for required inspections.
OpenFeb 8, 2023
building section · provide cover to electrical junction box. 1001(e) sfhc
provide coverplate over electrical junction box located along the wall of the ground floor storage area.
OpenFeb 8, 2023
plumbing and electrical section · make necessary repairs to bathroom (inside the unit).
OpenFeb 8, 2023
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. 1301 sfhc
remove or cover damaged and peeling paint on rear exterior door in an approved manner. ***see lead hazard warning***
OpenFeb 8, 2023
smoke detection section · replace missing crown molding. 1001(b) sfhc
at time of inspection, crown molding had been removed.
OpenFeb 8, 2023
fire section · replace missing baseboards in kitchen. 1001(b) sfhc
at time of inspection, the baseboards in the kitchen had been removed. replace baseboards.
OpenFeb 8, 2023
sanitation section · make necessary repairs in front room/foyer.
OpenFeb 8, 2023
security requirements section · repair light fixture. 504 & 1001(e) sfhc
at time of inspection, light fixture was coming out of the ceiling. make needed repairs.
OpenFeb 8, 2023
building section · repair electrical outlet and provide coverplate. 504 & 1001(e) sfhc
at groundfloor bathroom, make necessary repairs to electrical outlet located just above the bathroom vanity and proved a cover plate. at time of inspection outlet was coming out og the wall and missing a cover plate.
OpenFeb 8, 2023
fire section · eliminate rodent infestation. 1001(b) & 1306 sfhc
at time of inspection, mouse droppings were observed in the kitchen. provide pest control services to eliminate infestation.
OpenFeb 8, 2023
sanitation section · replace missing cover plate for lightswitch. 504 sfhc
provide a coverplate for light switch.
OpenFeb 8, 2023
security requirements section · provide weatherproofing to windows. 708 sfhc
at time of inspection, windows had small gaps which allowed cold air to enter. repair so that windows are weatherproof.
OpenFeb 8, 2023
building section · repair malfunctioning mechanical ventilation/fan. 504(c) & 1001(g) sfhc
make necessary repairs/replacements to malfunctioning fan in ground floor bathroom.
OpenFeb 8, 2023
fire section · reattach cover of heat vent. 1001(b) sfhc
reattach heat vent cover. at time of inspection vent cover had been removed.
Page 1 of 2