stoop
MAP
LeaderboardAbout

510 SOUTH VAN NESS AVE

Mission · San Francisco, CA · Parcel 3570002 · Last violation Jun 29, 2026 · Last complaint Jun 19, 2026

NeighborhoodMission
More violations than 93% of nearby buildings
More violations than 93% of buildings and more complaints than 89% of buildings in Mission. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 36 violations · 13 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
5 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Open fire-safety violations0
Open lead violations0
311 Housing Complaints
Total complaints since 2011
87
5 per year avg.↑ Up 44% in the last 2 years (13 vs 9 prior 2 yrs)
Reported issues
13
Heatⓘ4
Leadⓘ1
Pestsⓘ33
Dept. of Building Inspection Violations
Total violations since 1996
478
15 per year avg.↑ Up 13% in the last 2 years (36 vs 32 prior 2 yrs)
Open violations
5
Fire safetyⓘ0
Leadⓘ0

Top violation categories

5 yrsAll time
building sectionⓘ19 violations
other sectionⓘ17 violations
interior surfaces section16 violations
fire section7 violations
plumbing and electrical section6 violations
sanitation section3 violations
smoke detection sectionⓘ2 violations
Unknownⓘ1 violations

Top complaint types

5 yrsAll time
Infestation Rodent Insect6 complaints
Bathroom5 complaints
Infestation Bed Bugs3 complaints
Plumbing Broken Leaking2 complaints
Fire Hazard2 complaints
Mold And Mildew2 complaints
Hot Water Lack Of Hot Water1 complaints
Fire Alarm System1 complaints
Elevators Everthing Else1 complaints
Mail Service Delivery Problem1 complaints
Clutter Hoarder Unit Interior Storage1 complaints
General Maintenance Not In List Above1 complaints
Hide violations (478) ↑See complaints (87) →

Violation log

478 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeJul 2, 1998building sectionreplace broken glass window pane (1001(h),708 hc)in fire exit room on 2nd floor, along mission street.
See something wrong? File a complaint with SF 311
not activeJul 2, 1998fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)on 2nd floor. also, replace nozzle on existing fire extinguisher on 2nd floor.
not activeJul 2, 1998other sectionprovide non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not (701c hc)provide a key to thermostat box.
not activeJul 2, 1998sanitation sectionremove rubbish or trash (1306,1307 hc)from lightwells on 1st and 2nd floors. remove debris from floors in fire exit rooms on a regular basis.
not activeJul 2, 1998interior surfaces sectionrepair damaged walls (1001b,h,o hc)inside elevator. replace damaged panelling.
not activeMar 23, 1998interior surfaces sectionother interior violations1)repair leaky p-trap sec 1001h.c. 2) secure baseboard heater to wall sec 1001h.c. all violations in unit #347
not activeMar 23, 1998interior surfaces sectionrepair damaged walls (1001b,h,o hc)#347 remove holes
not activeNov 25, 1997fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)missing fire extinguisher in hallways on 2nd and 3rd floors.
not activeNov 25, 1997plumbing and electrical sectionprovide adequate lighting (504g hc)unit 366
not activeNov 25, 1997building sectionother building violationsremove any kitchen appliance such as hot plate and microwave oven.(a burnt spot at newspaper over microwave oven was verified in unit 257)
not activeSep 26, 1997building sectionother building violations1) repair 2nd floor bathroom ceiling. sec 1001h.c. 2) provide fire extinguishers all hallways, all floors. sec 1001h.c. 3) remove broken glass fire escapes. sec 1001h.c. 4) remove hanging wires from ceiling women's room 3rd floor. all violations to be corrected in seven (7) days.
not activeAug 12, 1997interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)room 105-bathroom, room 121, room 133, room 383, in bathroom of 392, bathroom in room 218, room 235, room 255, in bathroom of 246, room 256, rom 284.
not activeAug 12, 1997other sectioninspector commentsupon date or reinspection the following rooms will be made accessible that were not inspected per this routine; room 126, 139, 142, 292, 294, 299a, 236, 244, 247, 272, 278, 280, 286, 305, 328, 339, 342, 350, 365, 375, 377,and room 395.
not activeAug 12, 1997fire sectionother fire violationsremove hasp and/or padlock on entry door to room 117, room 114, room 292, room 290, room 299, room 299c, room 258, room 249, room 256, room 284, room 290, room 280, room 266. 1001hc repair fire sprinkler brackets supporting fire protection line in room 265, room 252. 904hc
not activeAug 12, 1997plumbing and electrical sectionprovide adequate lighting (504g hc)repair lite fixture in room 156.
not activeAug 12, 1997interior surfaces sectionreplace floor covering (1001b,j,o hc)in room 296
not activeAug 12, 1997plumbing and electrical sectionrepair lightswitch (1001e hc)install coverplate on entry lightswitch in room 263
not activeAug 12, 1997sanitation sectionremove rubbish or trash (1306,1307 hc)in room 203, room 274, room 299d
not activeAug 12, 1997security requirements sectionprovide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)correct location for room 387.
not activeAug 12, 1997interior surfaces sectionclean interior (1306 hc)clean entire room number 149and room 260, eliminate mold/mildew, paint entire room and repair/replace floor covering. 1001hc & 1301hc remove all rubbish & clean room 203. 1001hc, 1301hc
not activeAug 12, 1997plumbing and electrical sectionrepair toilet (1001f hc)toilet leaking in room 139c.
not activeAug 12, 1997sanitation sectionother sanitation violationsrepair bathroom fan in rooms 139a & room 139c. restore operation of bathroom window or install mechanical ventilation in room 319. 504hc
not activeAug 12, 1997plumbing and electrical sectionother plumbing and/or electrical violations—
not activeAug 12, 1997security requirements sectionother security violationsrepair front door stop & jamb for room 138 and door jamb and install strike for room 260. 1001hc, 706hc mark room number on door clearly for room 295, room 289, room 305. 706hc install/repair front door handle for room 287, room 299d, room 319, room 385. 1001hc, 706hc
not activeAug 12, 1997plumbing and electrical sectionrepair sink (1001f hc)leaking faucet in room 120, p-trap in room 212, eliminate basin stoppage in room 228, restore operation of basin drain in room 260
not activeAug 12, 1997interior surfaces sectionremove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)where work required.
not activeAug 12, 1997interior surfaces sectionrepair damaged walls (1001b,h,o hc)room 105-bathroom, room 143, room 361, around door in room 374, in bathroom of room 392, room 235, room 255, in bathroom of room 246, below sink in room 151, room 284.
not activeAug 12, 1997interior surfaces sectioneliminate mold/mildew on walls (1301,1001b(13),1306 hc)room 105-bathroom, in bathroom of room 392, in bathroom of 246
not activeAug 12, 1997interior surfaces sectioneliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)room 105-bathroom, in bathroom of 392, in bathroom of 246
not activeAug 12, 1997interior surfaces sectionother interior violationsrepair casing and wall around room 358 in the hallway and paint as necessary. 1001hc repair and/or replace bath lavy countertop and backsplash in room 108. patch hole at wall at sink waste penetration and paint as necessary in room 120, room 335, room 224, room 225 repair damaged walls at shower stall and around window in bathroom of room 346. 1001hc, 1301hc
not activeAug 12, 1997interior surfaces sectionrepair floor covering (1001b,j,o hc)in common hallway floor on 1st floor in corridor labeled 139a-139c and on the 2nd floor in corridor labeled 221-225.
not activeAug 12, 1997building sectionthis notice includes violations for the areas noted.this notice pertains to all common areas & individual rooms of this hotel. inspections performed on 8/6/97, 8/8/97, 8/11/97 & 8/12/97 to cover entire space.
not activeAug 12, 1997security requirements sectionprovide single cylinder deadbolt locks with a minimum 1" throw for entry doors of the following units. (706 hc)repair entry deadbolts in rooms 360, 374
not activeAug 12, 1997interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.where work required.
not activeAug 12, 1997building sectionreplace broken glass window pane (1001(h),708 hc)at 2nd floor at end of common hallway by room number 265.
not activeAug 12, 1997interior surfaces sectionpaint ceilings (1001b,1301 hc)room 105-bathroom, room 119, room 121, room 133, room 383, in bathroom of 392, in bathroom of 218, room 235, room 255, room 284.
not activeAug 12, 1997interior surfaces sectionpaint walls (1001b,1301 hc)room 105-bathroom, room 119, room 143, room 361, around door in room 374, in bathroom of 392, room 235, room 255, in bathroom of 246, interior door trim of room 268, below sink in room 151, room 284.
not activeMay 5, 1997security requirements sectionprovide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)hotel unit #387 entry door - reinstall the peephole/135-degree viewer to mounting height of 58 inches. 706 hc.
not activeMay 5, 1997fire sectionrecharge all fire extinguishers (905, 1001(m) hc)in all floors of public hallways.
not activeMay 5, 1997fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)replacement to missing fire extinguisher in all floors of public hallways.
not activeMay 5, 1997other sectionmiscellaneous violationshotel unit #387 - steam baseboard heater shut-off valve is missing. 1001 hc. provide a shut-off heating valve.
not activeApr 24, 1997interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.hotel unit #115.
not activeApr 24, 1997other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)hotel unit #115 and 355.
not activeApr 24, 1997interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)hotel unit #115 - defective ceiling. 1001 hc.
not activeApr 24, 1997interior surfaces sectionlocate source of water damage (703, 1001f hc)hotel unit #115.
not activeApr 24, 1997interior surfaces sectioneliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)men's 3rd floor - eliminate mildew and repaint. 1001/1301 hc.
not activeApr 24, 1997interior surfaces sectionrepair damaged walls (1001b,h,o hc)hotel unit #115 - peeling paint and repaint. 1001/1301 hc. men's 3rd floor - repair/seal defective wall behind the water closet. 1001 hc.; repair unsecure plastic divider in shower stall. 1001 hc.
not activeApr 24, 1997interior surfaces sectionreplace floor covering (1001b,j,o hc)hallway 2nd floor (#274 - 279) - carpet floor has been removed and expoxed nailing edges. 1001 hc. correct this deficiency.
not activeApr 24, 1997other sectionmiscellaneous violationshotel unit #115 & 355 - replace missing baseboard heater shut-off valves. 1001 hc. must be completed within 7 days.
not activeApr 24, 1997interior surfaces sectionother interior violationsmen's 1st floor - replace the missing enclosure access panel opening in the ceiling. 1001 hc.
not activeJul 2, 1998
building section · replace broken glass window pane (1001(h),708 hc)
in fire exit room on 2nd floor, along mission street.
not activeJul 2, 1998
fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)
on 2nd floor. also, replace nozzle on existing fire extinguisher on 2nd floor.
not activeJul 2, 1998
other section · provide non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not (701c hc)
provide a key to thermostat box.
not activeJul 2, 1998
sanitation section · remove rubbish or trash (1306,1307 hc)
from lightwells on 1st and 2nd floors. remove debris from floors in fire exit rooms on a regular basis.
not activeJul 2, 1998
interior surfaces section · repair damaged walls (1001b,h,o hc)
inside elevator. replace damaged panelling.
not activeMar 23, 1998
interior surfaces section · other interior violations
1)repair leaky p-trap sec 1001h.c. 2) secure baseboard heater to wall sec 1001h.c. all violations in unit #347
not activeMar 23, 1998
interior surfaces section · repair damaged walls (1001b,h,o hc)
#347 remove holes
not activeNov 25, 1997
fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)
missing fire extinguisher in hallways on 2nd and 3rd floors.
not activeNov 25, 1997
plumbing and electrical section · provide adequate lighting (504g hc)
unit 366
not activeNov 25, 1997
building section · other building violations
remove any kitchen appliance such as hot plate and microwave oven.(a burnt spot at newspaper over microwave oven was verified in unit 257)
not activeSep 26, 1997
building section · other building violations
1) repair 2nd floor bathroom ceiling. sec 1001h.c. 2) provide fire extinguishers all hallways, all floors. sec 1001h.c. 3) remove broken glass fire escapes. sec 1001h.c. 4) remove hanging wires from ceiling women's room 3rd floor. all violations to be corrected in seven (7) days.
not activeAug 12, 1997
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
room 105-bathroom, room 121, room 133, room 383, in bathroom of 392, bathroom in room 218, room 235, room 255, in bathroom of 246, room 256, rom 284.
not activeAug 12, 1997
other section · inspector comments
upon date or reinspection the following rooms will be made accessible that were not inspected per this routine; room 126, 139, 142, 292, 294, 299a, 236, 244, 247, 272, 278, 280, 286, 305, 328, 339, 342, 350, 365, 375, 377,and room 395.
not activeAug 12, 1997
fire section · other fire violations
remove hasp and/or padlock on entry door to room 117, room 114, room 292, room 290, room 299, room 299c, room 258, room 249, room 256, room 284, room 290, room 280, room 266. 1001hc repair fire sprinkler brackets supporting fire protection line in room 265, room 252. 904hc
not activeAug 12, 1997
plumbing and electrical section · provide adequate lighting (504g hc)
repair lite fixture in room 156.
not activeAug 12, 1997
interior surfaces section · replace floor covering (1001b,j,o hc)
in room 296
not activeAug 12, 1997
plumbing and electrical section · repair lightswitch (1001e hc)
install coverplate on entry lightswitch in room 263
not activeAug 12, 1997
sanitation section · remove rubbish or trash (1306,1307 hc)
in room 203, room 274, room 299d
not activeAug 12, 1997
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
correct location for room 387.
not activeAug 12, 1997
interior surfaces section · clean interior (1306 hc)
clean entire room number 149and room 260, eliminate mold/mildew, paint entire room and repair/replace floor covering. 1001hc & 1301hc remove all rubbish & clean room 203. 1001hc, 1301hc
not activeAug 12, 1997
plumbing and electrical section · repair toilet (1001f hc)
toilet leaking in room 139c.
not activeAug 12, 1997
sanitation section · other sanitation violations
repair bathroom fan in rooms 139a & room 139c. restore operation of bathroom window or install mechanical ventilation in room 319. 504hc
not activeAug 12, 1997
plumbing and electrical section · other plumbing and/or electrical violations
not activeAug 12, 1997
security requirements section · other security violations
repair front door stop & jamb for room 138 and door jamb and install strike for room 260. 1001hc, 706hc mark room number on door clearly for room 295, room 289, room 305. 706hc install/repair front door handle for room 287, room 299d, room 319, room 385. 1001hc, 706hc
not activeAug 12, 1997
plumbing and electrical section · repair sink (1001f hc)
leaking faucet in room 120, p-trap in room 212, eliminate basin stoppage in room 228, restore operation of basin drain in room 260
not activeAug 12, 1997
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
where work required.
not activeAug 12, 1997
interior surfaces section · repair damaged walls (1001b,h,o hc)
room 105-bathroom, room 143, room 361, around door in room 374, in bathroom of room 392, room 235, room 255, in bathroom of room 246, below sink in room 151, room 284.
not activeAug 12, 1997
interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc)
room 105-bathroom, in bathroom of room 392, in bathroom of 246
not activeAug 12, 1997
interior surfaces section · eliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)
room 105-bathroom, in bathroom of 392, in bathroom of 246
not activeAug 12, 1997
interior surfaces section · other interior violations
repair casing and wall around room 358 in the hallway and paint as necessary. 1001hc repair and/or replace bath lavy countertop and backsplash in room 108. patch hole at wall at sink waste penetration and paint as necessary in room 120, room 335, room 224, room 225 repair damaged walls at shower stall and around window in bathroom of room 346. 1001hc, 1301hc
not activeAug 12, 1997
interior surfaces section · repair floor covering (1001b,j,o hc)
in common hallway floor on 1st floor in corridor labeled 139a-139c and on the 2nd floor in corridor labeled 221-225.
not activeAug 12, 1997
building section · this notice includes violations for the areas noted.
this notice pertains to all common areas & individual rooms of this hotel. inspections performed on 8/6/97, 8/8/97, 8/11/97 & 8/12/97 to cover entire space.
not activeAug 12, 1997
security requirements section · provide single cylinder deadbolt locks with a minimum 1" throw for entry doors of the following units. (706 hc)
repair entry deadbolts in rooms 360, 374
not activeAug 12, 1997
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
where work required.
not activeAug 12, 1997
building section · replace broken glass window pane (1001(h),708 hc)
at 2nd floor at end of common hallway by room number 265.
not activeAug 12, 1997
interior surfaces section · paint ceilings (1001b,1301 hc)
room 105-bathroom, room 119, room 121, room 133, room 383, in bathroom of 392, in bathroom of 218, room 235, room 255, room 284.
not activeAug 12, 1997
interior surfaces section · paint walls (1001b,1301 hc)
room 105-bathroom, room 119, room 143, room 361, around door in room 374, in bathroom of 392, room 235, room 255, in bathroom of 246, interior door trim of room 268, below sink in room 151, room 284.
not activeMay 5, 1997
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
hotel unit #387 entry door - reinstall the peephole/135-degree viewer to mounting height of 58 inches. 706 hc.
not activeMay 5, 1997
fire section · recharge all fire extinguishers (905, 1001(m) hc)
in all floors of public hallways.
not activeMay 5, 1997
fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)
replacement to missing fire extinguisher in all floors of public hallways.
not activeMay 5, 1997
other section · miscellaneous violations
hotel unit #387 - steam baseboard heater shut-off valve is missing. 1001 hc. provide a shut-off heating valve.
not activeApr 24, 1997
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
hotel unit #115.
not activeApr 24, 1997
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
hotel unit #115 and 355.
not activeApr 24, 1997
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
hotel unit #115 - defective ceiling. 1001 hc.
not activeApr 24, 1997
interior surfaces section · locate source of water damage (703, 1001f hc)
hotel unit #115.
not activeApr 24, 1997
interior surfaces section · eliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)
men's 3rd floor - eliminate mildew and repaint. 1001/1301 hc.
not activeApr 24, 1997
interior surfaces section · repair damaged walls (1001b,h,o hc)
hotel unit #115 - peeling paint and repaint. 1001/1301 hc. men's 3rd floor - repair/seal defective wall behind the water closet. 1001 hc.; repair unsecure plastic divider in shower stall. 1001 hc.
not activeApr 24, 1997
interior surfaces section · replace floor covering (1001b,j,o hc)
hallway 2nd floor (#274 - 279) - carpet floor has been removed and expoxed nailing edges. 1001 hc. correct this deficiency.
not activeApr 24, 1997
other section · miscellaneous violations
hotel unit #115 & 355 - replace missing baseboard heater shut-off valves. 1001 hc. must be completed within 7 days.
not activeApr 24, 1997
interior surfaces section · other interior violations
men's 1st floor - replace the missing enclosure access panel opening in the ceiling. 1001 hc.
Page 9 of 10
← PrevNext →