not activeOct 7, 2003
building section · repair weather proofing at roof (1001(h),703 hc)
repair damaged roof. remove any items on roof (i.e. exercise equipment). repair broken glass at air well/light well.
not activeOct 7, 2003
other section · repair defective elevator (1001(l), 713 hc)
please have elevator repaired to stop at level with floors.
not activeOct 7, 2003
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
in unit #505, 3rd floor hallway, and where required. in unit #202's and #205's bathroom. #306, all areas.
not activeOct 7, 2003
interior surfaces section · repair damaged walls (1001b,h,o hc)
in unit #205's and #505's bathroom and where required. in unit #502, near entrance. in unit #402's behind toilet at wall/floor junctions and wall behind unit entry door. at 3rd. floor hallway. in unit #205: above kichen cabinet, near ceiling, and above bath window. #306, all areas.
not activeOct 7, 2003
interior surfaces section · repair floor covering (1001b,j,o hc)
in unit #505's bathroom and where required. in unit #402's kitchen, bathroom and living room (repair, clean and sanitize). #306, all areas.
not activeOct 7, 2003
interior surfaces section · other interior violations
seal around kitchen sink in unit #101 to prevent water damage on wall behind and under it. repair kitchen cabinet in unit #402.
not activeOct 7, 2003
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
#402 and #306: all walls and ceilings (including closet, and bathroom door). 3rd. floor hallway.
not activeOct 7, 2003
smoke detection section · repair smoke detector (908 911 hc)
in unit #306, #402, #502, and where required.
not activeOct 7, 2003
interior surfaces section · paint ceilings (1001b,1301 hc)
after repairs are done.
not activeOct 7, 2003
plumbing and electrical section · remove cord wiring (1001-e hc)
#502 and where required -fire hazard.
not activeSep 9, 2003
building section · other building violations
a janitor, housekeeper or other responsible person shall reside upon the premises. according to tenants there is no manager on-site in this building.
not activeSep 9, 2003
plumbing and electrical section · other plumbing violations
please open for inspection all rooms in basement area. the sound of a water leak was hear thru one of the doors. please make necessary repairs.
not activeSep 9, 2003
other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
and in gas meter area.
not activeSep 9, 2003
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
seal any openings that are 1/4 of an inch or bigger. they may serve as rodent entrance and/or harborage. set traps for rodent control and surveillance. all units.
not activeSep 9, 2003
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
open boiler room for inspection at time of reinspection. repair radiator in unit #108 and where required.
not activeSep 9, 2003
other section · maintain elevator in safe working condition (1001(l), 713 hc)
please post current elevator permit on elevator.
not activeSep 9, 2003
building section · repair window (1001(h),708 hc)
#503, to open and close properly.
not activeSep 9, 2003
plumbing and electrical section · repair sink (1001f hc)
make necessary repairs to washing machine plumbing lines to stop soapy water from surfacing at units kitchen sinks (i.e. #105). all work to be conducted under appropriate permits. repair leaking faucet in unit #509's kitchen sink.
not activeSep 9, 2003
other section · miscellaneous violations
repair stove in unit #504 -oven door does not close properly. repair kitchen cabinet in unit #504. repair/replace leaking refrigerator in unit #502.
not activeSep 9, 2003
other section · provide non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not (701c hc)
show location of thermostat at time of inspection.
not activeSep 9, 2003
other section · repair damaged walls (1001b,h,o hc)
at hallways in common areas. #106, #108, #204, all areas -including around and under kitchen sink. #104, bathroom and kitchen. #502, entrance, and where required.
not activeSep 9, 2003
plumbing and electrical section · repair lightswitch (1001e hc)
#503's closet light.
not activeSep 9, 2003
sanitation section · clean and sanitize (1306 hc)
maintain all areas of building in a clean and sanitary condition, including fire escapes.
not activeSep 9, 2003
building section · repair window glazing (1001(h),(j),& 708 hc)
replace broken glass in unit #504 -living room window, and in secondary stairways, and where required.
not activeSep 9, 2003
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
#104's and #506's bathroom -above bathtub. #106 and #503, walls and ceilings, all areas. #104 and #402's living room ceiling, and where required.
not activeSep 9, 2003
other section · repair damaged ceilings (1001b,h,o hc)
at hallways in common areas. #104, at bathroom. #106 and #108, all areas. #505, kitchen, and where required.
not activeSep 9, 2003
fire section · provide smoke enclosure doors (807 707 hc)
adjust entry door/door frame to unit 502, #503, #505, #509's and where required. entry door to fit tight, replace if necessary.
not activeSep 9, 2003
building section · repair stairs (1001(b)(13)hc)
repair/replace damaged riser (marble), at main entry way.
not activeSep 9, 2003
interior surfaces section · repair floor covering (1001b,j,o hc)
please clean/sanitize or replace carpet throughout unit #106, and #402. reglue kitchen linoleum in unit #504, #105, and where required. reglue bathroom linoleum in unit #105 and where required. please resurface flooring in lobby, hallways, and main stairways.
not activeSep 9, 2003
smoke detection section · repair smoke detector (908 911 hc)
repair/replace missing/damaged smoke detector in unit #504, #404, #310, #204, and where required. testing of all smoke detectors is strongly recommended.
not activeSep 9, 2003
sanitation section · other sanitation violations
pigeon-proof premises.
not activeSep 9, 2003
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
resurface bathtub in unit #506 and where required.
not activeSep 9, 2003
building section · repair window latches or hardware (1001(b)hc)
#503's window to lock properly.
not activeSep 9, 2003
security requirements section · other security violations
complainant stated that her door (#108), can be opened with keys to other units. please check and correct as necessary.
not activeSep 9, 2003
building section · building permit required (301 hc)
all repair work to be conducted under appropriate permits.
not activeSep 9, 2003
interior surfaces section · other interior violations
repair #504's kitchen cabinet drawer.
not activeSep 9, 2003
interior surfaces section · repair sub-floor (1001b,j,o hc)
#505's kitchen floor is shifting to the right.
not activeSep 9, 2003
building section · this notice includes violations for the areas noted.
925 geary street #104, #105, #106, #108, #204, #209, #210, #310, #402, #404, #406, #502, #503, #504, #505, #506, #509, etc. and common areas.
not activeSep 9, 2003
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeSep 9, 2003
building section · repair window sash cords (1001(h) hc)
#104's living room window. #108's kitchen window. #504's kitchen window. #503's bathroom window, and where required.
not activeSep 9, 2003
plumbing and electrical section · remove cord wiring (1001-e hc)
in units #104, #310, #505, and where required.
not activeSep 9, 2003
other section · provide shutoff tool for gas utility shutoff (712 hc)
in gas meter area.
not activeSep 9, 2003
fire section · other fire violations
remove i-locks from all entry doors to units (i.e. #308, #405, #408, #409, #501, #502, etc.). provide identifying numbers at or near entry doors of all units (missing on #307, 505, 509, 406, etc.).
not activeSep 9, 2003
sanitation section · eliminate cockroach and bed bug infestations (1001b, 1306 hc)
initiate or increase frequency of professional pest control services to obtain more immediate result in the elimination of cockroaches and bed bugs. all units and common areas. seal all cracks and crevices to eliminate harborage. (all units, ie. #210 -at base of doorway, #402 -under bathroom sink, at entrance doorway. #503 -wall near bedroom, #506 -under kitchen sink, etc.).
not activeSep 9, 2003
interior surfaces section · paint ceilings (1001b,1301 hc)
after repairs are done.
not activeSep 9, 2003
plumbing and electrical section · provide adequate lighting (504g hc)
replace burnt light bulbs regularly (i.e. secondary stairs).
not activeSep 9, 2003
interior surfaces section · paint walls (1001b,1301 hc)
after repairs are done.
not activeMay 29, 2002
smoke detection section · repair smoke detector (908 911 hc)
not activeMay 29, 2002
interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc) at bathroom, closet, living room (near window, window sills, etc.) and kitchen cabinets.
please remediate the chronic mold growth cited in this building through the use of a mold remediation contractor, under the supervision of a licensed industrial hygienist or other industry expert. housing inspection services is to be provided a report by the above mentioned industry experts outlining measures employed to abate the growth, and a mold clearance report upon completion of work.
not activeMay 29, 2002
building section · this notice includes violations for the areas noted.
925 geary street #305.