stoop
MAP
LeaderboardAbout

44 MCALLISTER ST

Tenderloin · San Francisco, CA · Parcel 0349004 · Last violation May 15, 2026 · Last complaint Nov 6, 2025

NeighborhoodTenderloin
More violations than 86% of nearby buildings
More violations than 86% of buildings and more complaints than 82% of buildings in Tenderloin. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 22 violations · 13 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
19 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Open fire-safety violations0
Open lead violations0
311 Housing Complaints
Total complaints since 2010
78
5 per year avg.↓ Down 24% in the last 2 years (13 vs 17 prior 2 yrs)
Complaint severity
Last 5 years
34
Severeⓘ3
Seriousⓘ26
Minorⓘ5
Dept. of Building Inspection Violations
Total violations since 1998
217
7 per year avg.↓ Down 41% in the last 2 years (22 vs 37 prior 2 yrs)
Open violations
19
Fire safetyⓘ0
Leadⓘ0

Top violation categories

5 yrsAll time
other sectionⓘ18 violations
building sectionⓘ17 violations
plumbing and electrical sectionⓘ12 violations
interior surfaces sectionⓘ11 violations
sanitation sectionⓘ4 violations
Unknownⓘ3 violations
security requirements section1 violations
smoke detection section1 violations

Top complaint types

5 yrsAll time
Mold And Mildew11 complaints
Infestation Bed Bugs5 complaints
Infestation Rodent Insect4 complaints
General Maintenance Not In List Above4 complaints
Plumbing Broken Leaking3 complaints
Paint Lead Violating Safe Practices2 complaints
Security Inadequately Secured Perimeter1 complaints
Clutter Hoarder Unit Interior Storage1 complaints
Doors Windows Broken Defective1 complaints
Elevators No Working Elevator 7 Or More Stories1 complaints
Bathroom1 complaints
Hide violations (217) ↑See complaints (78) →

Violation log

198 DBI violations · Closed

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeFeb 5, 2007plumbing and electrical sectionrepair deteriorated drainage pipes at exterior (1001f hc)the drain for the west tradesmans alley outside the rear entry door appears blocked. clear the drain and attach a drain cover.
See something wrong? File a complaint with SF 311
not activeFeb 5, 2007plumbing and electrical sectionrepair electrical outlet (1001e hc)the electrical outlet in the front fire escape corridor on the seventh floor appears to have shorted out. replace the outlet or confirm that it is in good working order.
not activeFeb 5, 2007fire sectionkeep smoke enclosure doors closed (807 hc)the fire doors leading to the rear fire escape were tied open on the 7th & 8th floors. these doors should remain closed.
not activeFeb 5, 2007plumbing and electrical sectionrepair toilet (1001f hc)repair the running toilet in #205.
not activeJul 12, 2005building section1)have a non temperable centrally located thermostat installed by a c10 licensed contractor. 701hc./1001hc. 2)provide 68 degrees to each habitable room between : 5:00 am-11:00 am 3:00 pm-10:00 pm. 701hc.lack of a requiered thermostat on the premises.
not activeFeb 7, 2005building sectionremove,treat and eliminate source of mildew under and around guestroom window in gr#517.1306hc.mildewed wall surfaces under guestgroom window.
not activeFeb 7, 2005building sectionclean and sanitize wall and ceiling surfaces in the: 1)community kitchen area side of stove,above the couter. 2)remove grease and dust from kitchen windows,lint from laundry room windows. 3)degrease hood and vent system. 4)degrease and clean fan housing. 5)remove lint from wall surfaces behind washer and dryer,on routine basis. 6)keep and maintain public areas in a clean and sanitary condition at all times.1306hc./1001hc.insanitary public areas.
not activeFeb 19, 2004building sectioncracked caulking around handwash basinreplace damaged cauling around,side of hand wash basin.1001hc. 2)caulk areaaround top of steam pipe to prevent roach harborage.1001hc.
not activeFeb 19, 2004building sectionloose detached hard wired smoke detector .repair or replace smoke detector unit in gr#519.908hc.
not activeFeb 19, 2004building sectioninadequate weather protection under entry door to gr#519.weathersrip bottom of entry door to gr#519, to prevent air infiltration.1001hc.
not activeDec 19, 2003building sectionlack of radiator units in a variety of guestrooms.1)install a radiator unit in the fallowing guestrooms: gr.#201b #201c #212 #220 #223 #307 #327 #400 #404 #521 #610 #628 #632 #815 #816. 1001hc. 2) provide 68 degrees f. to each habitable room.701hc.
not activeNov 10, 2003building sectiondefective toilet seat in 5th floor bathroomreplace defective toilet seat in 5th floor bathroom.1001hc.
not activeNov 10, 2003building sectionlack of radiator unit in gr#519.1)install a radiator unit in gr#519.1001hc. 2)provide 68 degrees f. from 5:00 am-11:00 am 3:00 pm-10:00 pm sec. 701hc.
not activeNov 10, 2003building sectionbroken cover plate to 2nd floor public bathroom,exposed wiring.replace broken cover plate in second floor public bathroom.1001hc.
not activeNov 10, 2003building section5th floor toilet partitions in need to be cleaned and sanitized.wash down ,clean and sanitize 5th floor toilet partitions.1306hc.
not activeNov 10, 2003building sectionleaking bathroom faucet in 2nd floor public bathroom.1repair/repack leaking second floor public bathroom faucet.1001hc.
not activeNov 10, 2003other sectioninspector commentsit is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeNov 10, 2003other sectioninspector commentsit is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 21, 2003building sectionextensive mold and mildew along guestroom/closet wall surfaces.a)locate source,remove,treat,and contain mold and mildew along guestroom wall surfaces : 1)side of bed. 2)linen closet. bclean,sanitize or replace carpeting reportedly filled with human urine stains and excrement.1306hc.
not activeJan 29, 2003building sectionfailure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02.submit a building permit application with plans to the department of building inspection within 15 days of this notice to comply with the residential hotel sprinkler ordinance #170-02, section 904 s.f.h.c.
not activeMar 28, 2002building sectiondefective waste pipe in #531,431,causing overhead leaks and ceiling damage on 3rd floor hallway ceiling as well as in #324.repair /replace defective waste line in gr#531,431.(hand wash basin )1001hc.
not activeMar 28, 2002building sectionwater damaged linen closet,walls and ceiling surfaces in #324.1)replace all buckling,soaked water damaged plaster in gr#324.1001hc. 2)replaster and paint unit #324.1301hc.
not activeMar 28, 2002building sectionwater damaged 3rd floor hallway ceiling.resheetrock/replaster and paint water damaged ceiling surfaces in 3rd floor hallway.1001hc.
not activeJan 5, 2001———
not activeSep 26, 2000building sectioninsanitary carpeting.replace insanitary carpeting.1306hc.
not activeSep 26, 2000building sectioninsanitary premisesclean and sanitize premises throughout.1306hc.
not activeSep 26, 2000building sectionlack of a hard wired smoke detector.replace missing hard wired smoke detector.908hc.
not activeSep 26, 2000building sectiondamaged steam line wrapping.rewrap damaged portion of steam line in unit #625.1001hc.
not activeSep 26, 2000building sectioncracked walls and ceiling surfaces.replaster and paint walls and ceiling surfaces in #625.1001hc./1301hc.
not activeSep 26, 2000building sectionmissing radiator unitinstall a radiator unit to the premises.701hc.
not activeDec 29, 1998other sectionmiscellaneous violationsrepair heater in room #622 (heater is leaking on to carpet ) sfhc 701.
not activeDec 29, 1998interior surfaces sectionrepair floor covering (1001b,j,o hc)repair carpets in room #622 (water damaged) repair carpet in hallway adjacent to room #609.
not activeOct 5, 1998fire sectioninstall directional signs at (801, 1001(m) hc)repair exit sign (cover missing) next to room #609
not activeOct 5, 1998plumbing and electrical sectionprovide adequate lighting (504g hc)provide adequate lighting at bathroom adjacent to room #625
not activeOct 5, 1998smoke detection sectionrepair smoke detector (908 911 hc)repair smoke detector in room #622
not activeOct 5, 1998interior surfaces sectionrepair damaged walls (1001b,h,o hc)repair lose plaster in bathroom over shower at walls and ceiling adjacent to room #725 repair water damaged ceiling at main dinning room
not activeOct 5, 1998interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)repair ceiling tile in bathroom over tub adjacent to room #725 repair ceiling tiles in kitchen at main dinning
not activeOct 5, 1998building sectionthis notice includes violations for the areas noted.44 mcallister st
not activeOct 5, 1998interior surfaces sectionpaint walls (1001b,1301 hc)repair peeling paint at hallway walls next to room #810 repair peeling paint at hallway ceiling next to room #329 repair peeling paint in bathroom over bath tub adjacent to room #825 repair peeling paint on bathroom door adjacent to room #725 repair peeling paint at stairway next to room #725,322 repair peeling paint in bathroom ceiling at second floor next to offices(mcallister st side)
not activeOct 5, 1998interior surfaces sectioneliminate mold/mildew on walls (1301,1001b(13),1306 hc)eliminate mold/mildew from walls in bathroom adjacent to room #825,225,725
not activeOct 5, 1998interior surfaces sectioneliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)eliminate mold/mildew from ceiling in bathroom adjacent to room #825
not activeOct 5, 1998interior surfaces sectionrepair floor covering (1001b,j,o hc)repair floor covering at hallway in front of room #517 repair floor tile at main hallway in front of elevator next to room #406
not activeOct 5, 1998plumbing and electrical sectionrepair toilet (1001f hc)replace toilet tank cover in bathroom next to room #327
not activeOct 5, 1998plumbing and electrical sectionrepair sink (1001f hc)repair faucet in bathroom next to room #210
not activeMar 20, 1998building sectionreplace broken glass window pane (1001(h),708 hc)in unit #222.
not activeMar 20, 1998building sectionrepair window latches or hardware (1001(b)hc)restore opening, closing & locking operation of all operable window sashes in unit #222.
not activeMar 20, 1998other sectioninspector commentsnote: investigate/service steam radiator system for possible leaks & malfunction in room #222.
not activeMar 20, 1998building sectionthis notice includes violations for the areas noted.all work is in reference to unit labeled #222.
not activeFeb 5, 2007
plumbing and electrical section · repair deteriorated drainage pipes at exterior (1001f hc)
the drain for the west tradesmans alley outside the rear entry door appears blocked. clear the drain and attach a drain cover.
not activeFeb 5, 2007
plumbing and electrical section · repair electrical outlet (1001e hc)
the electrical outlet in the front fire escape corridor on the seventh floor appears to have shorted out. replace the outlet or confirm that it is in good working order.
not activeFeb 5, 2007
fire section · keep smoke enclosure doors closed (807 hc)
the fire doors leading to the rear fire escape were tied open on the 7th & 8th floors. these doors should remain closed.
not activeFeb 5, 2007
plumbing and electrical section · repair toilet (1001f hc)
repair the running toilet in #205.
not activeJul 12, 2005
building section · 1)have a non temperable centrally located thermostat installed by a c10 licensed contractor. 701hc./1001hc. 2)provide 68 degrees to each habitable room between : 5:00 am-11:00 am 3:00 pm-10:00 pm. 701hc.
lack of a requiered thermostat on the premises.
not activeFeb 7, 2005
building section · remove,treat and eliminate source of mildew under and around guestroom window in gr#517.1306hc.
mildewed wall surfaces under guestgroom window.
not activeFeb 7, 2005
building section · clean and sanitize wall and ceiling surfaces in the: 1)community kitchen area side of stove,above the couter. 2)remove grease and dust from kitchen windows,lint from laundry room windows. 3)degrease hood and vent system. 4)degrease and clean fan housing. 5)remove lint from wall surfaces behind washer and dryer,on routine basis. 6)keep and maintain public areas in a clean and sanitary condition at all times.1306hc./1001hc.
insanitary public areas.
not activeFeb 19, 2004
building section · cracked caulking around handwash basin
replace damaged cauling around,side of hand wash basin.1001hc. 2)caulk areaaround top of steam pipe to prevent roach harborage.1001hc.
not activeFeb 19, 2004
building section · loose detached hard wired smoke detector .
repair or replace smoke detector unit in gr#519.908hc.
not activeFeb 19, 2004
building section · inadequate weather protection under entry door to gr#519.
weathersrip bottom of entry door to gr#519, to prevent air infiltration.1001hc.
not activeDec 19, 2003
building section · lack of radiator units in a variety of guestrooms.
1)install a radiator unit in the fallowing guestrooms: gr.#201b #201c #212 #220 #223 #307 #327 #400 #404 #521 #610 #628 #632 #815 #816. 1001hc. 2) provide 68 degrees f. to each habitable room.701hc.
not activeNov 10, 2003
building section · defective toilet seat in 5th floor bathroom
replace defective toilet seat in 5th floor bathroom.1001hc.
not activeNov 10, 2003
building section · lack of radiator unit in gr#519.
1)install a radiator unit in gr#519.1001hc. 2)provide 68 degrees f. from 5:00 am-11:00 am 3:00 pm-10:00 pm sec. 701hc.
not activeNov 10, 2003
building section · broken cover plate to 2nd floor public bathroom,exposed wiring.
replace broken cover plate in second floor public bathroom.1001hc.
not activeNov 10, 2003
building section · 5th floor toilet partitions in need to be cleaned and sanitized.
wash down ,clean and sanitize 5th floor toilet partitions.1306hc.
not activeNov 10, 2003
building section · leaking bathroom faucet in 2nd floor public bathroom.
1repair/repack leaking second floor public bathroom faucet.1001hc.
not activeNov 10, 2003
other section · inspector comments
it is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeNov 10, 2003
other section · inspector comments
it is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 21, 2003
building section · extensive mold and mildew along guestroom/closet wall surfaces.
a)locate source,remove,treat,and contain mold and mildew along guestroom wall surfaces : 1)side of bed. 2)linen closet. bclean,sanitize or replace carpeting reportedly filled with human urine stains and excrement.1306hc.
not activeJan 29, 2003
building section · failure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02.
submit a building permit application with plans to the department of building inspection within 15 days of this notice to comply with the residential hotel sprinkler ordinance #170-02, section 904 s.f.h.c.
not activeMar 28, 2002
building section · defective waste pipe in #531,431,causing overhead leaks and ceiling damage on 3rd floor hallway ceiling as well as in #324.
repair /replace defective waste line in gr#531,431.(hand wash basin )1001hc.
not activeMar 28, 2002
building section · water damaged linen closet,walls and ceiling surfaces in #324.
1)replace all buckling,soaked water damaged plaster in gr#324.1001hc. 2)replaster and paint unit #324.1301hc.
not activeMar 28, 2002
building section · water damaged 3rd floor hallway ceiling.
resheetrock/replaster and paint water damaged ceiling surfaces in 3rd floor hallway.1001hc.
not activeJan 5, 2001
—
not activeSep 26, 2000
building section · insanitary carpeting.
replace insanitary carpeting.1306hc.
not activeSep 26, 2000
building section · insanitary premises
clean and sanitize premises throughout.1306hc.
not activeSep 26, 2000
building section · lack of a hard wired smoke detector.
replace missing hard wired smoke detector.908hc.
not activeSep 26, 2000
building section · damaged steam line wrapping.
rewrap damaged portion of steam line in unit #625.1001hc.
not activeSep 26, 2000
building section · cracked walls and ceiling surfaces.
replaster and paint walls and ceiling surfaces in #625.1001hc./1301hc.
not activeSep 26, 2000
building section · missing radiator unit
install a radiator unit to the premises.701hc.
not activeDec 29, 1998
other section · miscellaneous violations
repair heater in room #622 (heater is leaking on to carpet ) sfhc 701.
not activeDec 29, 1998
interior surfaces section · repair floor covering (1001b,j,o hc)
repair carpets in room #622 (water damaged) repair carpet in hallway adjacent to room #609.
not activeOct 5, 1998
fire section · install directional signs at (801, 1001(m) hc)
repair exit sign (cover missing) next to room #609
not activeOct 5, 1998
plumbing and electrical section · provide adequate lighting (504g hc)
provide adequate lighting at bathroom adjacent to room #625
not activeOct 5, 1998
smoke detection section · repair smoke detector (908 911 hc)
repair smoke detector in room #622
not activeOct 5, 1998
interior surfaces section · repair damaged walls (1001b,h,o hc)
repair lose plaster in bathroom over shower at walls and ceiling adjacent to room #725 repair water damaged ceiling at main dinning room
not activeOct 5, 1998
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair ceiling tile in bathroom over tub adjacent to room #725 repair ceiling tiles in kitchen at main dinning
not activeOct 5, 1998
building section · this notice includes violations for the areas noted.
44 mcallister st
not activeOct 5, 1998
interior surfaces section · paint walls (1001b,1301 hc)
repair peeling paint at hallway walls next to room #810 repair peeling paint at hallway ceiling next to room #329 repair peeling paint in bathroom over bath tub adjacent to room #825 repair peeling paint on bathroom door adjacent to room #725 repair peeling paint at stairway next to room #725,322 repair peeling paint in bathroom ceiling at second floor next to offices(mcallister st side)
not activeOct 5, 1998
interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc)
eliminate mold/mildew from walls in bathroom adjacent to room #825,225,725
not activeOct 5, 1998
interior surfaces section · eliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)
eliminate mold/mildew from ceiling in bathroom adjacent to room #825
not activeOct 5, 1998
interior surfaces section · repair floor covering (1001b,j,o hc)
repair floor covering at hallway in front of room #517 repair floor tile at main hallway in front of elevator next to room #406
not activeOct 5, 1998
plumbing and electrical section · repair toilet (1001f hc)
replace toilet tank cover in bathroom next to room #327
not activeOct 5, 1998
plumbing and electrical section · repair sink (1001f hc)
repair faucet in bathroom next to room #210
not activeMar 20, 1998
building section · replace broken glass window pane (1001(h),708 hc)
in unit #222.
not activeMar 20, 1998
building section · repair window latches or hardware (1001(b)hc)
restore opening, closing & locking operation of all operable window sashes in unit #222.
not activeMar 20, 1998
other section · inspector comments
note: investigate/service steam radiator system for possible leaks & malfunction in room #222.
not activeMar 20, 1998
building section · this notice includes violations for the areas noted.
all work is in reference to unit labeled #222.
Page 4 of 4
← Prev