not activeMar 2, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 5, 2007
fire section · other fire violation (1001 b,i hc)
the fire alarm call box near #331 has been torn from the wall. re-attach the call box to the wall and insure that it is in working order.
not activeFeb 5, 2007
sanitation section · clear the garbage chutes (1001b hc)
clear the blocked garbage chutes.
not activeFeb 5, 2007
smoke detection section · provide smoke detector at stairs (911 hc)
install a smoke alarm at the top of each stairway. this can be a battery operated alarm.
not activeFeb 5, 2007
fire section · permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc)
remove the combustable storage in the following locations: 1)house phone room near #704, 2)mattresses, etc. stored under the rear fire escape.
not activeFeb 5, 2007
security requirements section · provide designated missing unit/apartment identification numbers to all units (706 hc)
provide a door number for #205.
not activeFeb 5, 2007
interior surfaces section · repair/install damaged or missing ventilation (1001b,g hc)
repair or install a ventilation fan the following locations: 1)#205 bathroom, 2)common bath near #329.
not activeFeb 5, 2007
other section · inspector comments
note: on reinspection day, property manager, owner or the owner's agent needs to demonstrate the workability of the fire escape ladders. the fire escapes are to be checked on all buildings during the course of a routine inspection. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written and signed report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or you are required to lower the ladder on re-inspection day to verify its proper full release. reminder: test and verify that all windows or doors leading to emergency fire escape are operational and unobstructed. advise occupants not to block the path of emergency exits on the inside. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeFeb 5, 2007
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
the date tags and guages for most fire extinguishers are unreadable. position the extinguishers in their cabinets so both can be read. fire extinguishers must be recharged and retagged annually.
not activeFeb 5, 2007
security requirements section · adjudt door closer (1001 b, j hc)
adjust the tradesmans door closer so that it closes and latches the door.
not activeFeb 5, 2007
building section · remove/repair thermostat (1001 b hc)
in the bathrooms near #'s 825,725,& 425 are damaged thermostats to inoperble (?) heat exchange units. remove/replace/repair these thermostats in that the mercury within pose a health hazard if released.
not activeFeb 5, 2007
building section · repair window latches or hardware (1001(b)hc)
repair/replace the broken window handle to the left bedroom window in #205.
not activeFeb 5, 2007
plumbing and electrical section · remove cord wiring (1001-e hc)
remove the cord wiring powering the wall light fixture near door c on the second floor.
not activeFeb 5, 2007
interior surfaces section · paint ceilings & walls (1001b,1301 hc)
prep and paint the peeling damaged surfaces in the following locations: 1)common bathroom near #225, 2)common bath near #327.
not activeFeb 5, 2007
building section · repair weather proofing on siding (1001(h),703 hc)
seal around the pipe passing through the exterior wall in the bathroom near #725.
not activeFeb 5, 2007
building section · repair entry threshold (1001b, j hc)
the threshold for the main entry door is loose and a trip hazard. repair or replace.
not activeFeb 5, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. at the time of reinspection provide access to all common areas including the roof, boiler, timeclock, thermostat, and all storage areas. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 5, 2007
plumbing and electrical section · repair deteriorated drainage pipes at exterior (1001f hc)
the drain for the west tradesmans alley outside the rear entry door appears blocked. clear the drain and attach a drain cover.
not activeFeb 5, 2007
plumbing and electrical section · repair electrical outlet (1001e hc)
the electrical outlet in the front fire escape corridor on the seventh floor appears to have shorted out. replace the outlet or confirm that it is in good working order.
not activeFeb 5, 2007
fire section · remove egress obstruction at (801,1001(l) hc)
the garbage receptacles stored in the east tradesmans alley are obstructing an emergency path of egress. move the receptacles to the rear yard.
not activeFeb 5, 2007
plumbing and electrical section · repair toilet (1001f hc)
repair the running toilet in #205.
not activeFeb 5, 2007
other section · inspector comments
test the emergency lighting in the stairways to insure they are in good operating condition.
not activeFeb 5, 2007
fire section · keep smoke enclosure doors closed (807 hc)
the fire doors leading to the rear fire escape were tied open on the 7th & 8th floors. these doors should remain closed.
not activeJul 12, 2005
building section · 1)have a non temperable centrally located thermostat installed by a c10 licensed contractor. 701hc./1001hc. 2)provide 68 degrees to each habitable room between : 5:00 am-11:00 am 3:00 pm-10:00 pm. 701hc.
lack of a requiered thermostat on the premises.
not activeFeb 7, 2005
building section · remove,treat and eliminate source of mildew under and around guestroom window in gr#517.1306hc.
mildewed wall surfaces under guestgroom window.
not activeFeb 7, 2005
building section · clean and sanitize wall and ceiling surfaces in the: 1)community kitchen area side of stove,above the couter. 2)remove grease and dust from kitchen windows,lint from laundry room windows. 3)degrease hood and vent system. 4)degrease and clean fan housing. 5)remove lint from wall surfaces behind washer and dryer,on routine basis. 6)keep and maintain public areas in a clean and sanitary condition at all times.1306hc./1001hc.
insanitary public areas.
not activeFeb 19, 2004
building section · loose detached hard wired smoke detector .
repair or replace smoke detector unit in gr#519.908hc.
not activeFeb 19, 2004
building section · inadequate weather protection under entry door to gr#519.
weathersrip bottom of entry door to gr#519, to prevent air infiltration.1001hc.
not activeFeb 19, 2004
building section · cracked caulking around handwash basin
replace damaged cauling around,side of hand wash basin.1001hc. 2)caulk areaaround top of steam pipe to prevent roach harborage.1001hc.
not activeDec 19, 2003
building section · lack of radiator units in a variety of guestrooms.
1)install a radiator unit in the fallowing guestrooms: gr.#201b #201c #212 #220 #223 #307 #327 #400 #404 #521 #610 #628 #632 #815 #816. 1001hc. 2) provide 68 degrees f. to each habitable room.701hc.
not activeNov 10, 2003
building section · leaking bathroom faucet in 2nd floor public bathroom.
1repair/repack leaking second floor public bathroom faucet.1001hc.
not activeNov 10, 2003
other section · inspector comments
it is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeNov 10, 2003
other section · inspector comments
it is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeNov 10, 2003
building section · lack of radiator unit in gr#519.
1)install a radiator unit in gr#519.1001hc. 2)provide 68 degrees f. from 5:00 am-11:00 am 3:00 pm-10:00 pm sec. 701hc.
not activeNov 10, 2003
building section · broken cover plate to 2nd floor public bathroom,exposed wiring.
replace broken cover plate in second floor public bathroom.1001hc.
not activeNov 10, 2003
building section · defective toilet seat in 5th floor bathroom
replace defective toilet seat in 5th floor bathroom.1001hc.
not activeNov 10, 2003
building section · 5th floor toilet partitions in need to be cleaned and sanitized.
wash down ,clean and sanitize 5th floor toilet partitions.1306hc.
not activeFeb 21, 2003
building section · extensive mold and mildew along guestroom/closet wall surfaces.
a)locate source,remove,treat,and contain mold and mildew along guestroom wall surfaces : 1)side of bed. 2)linen closet. bclean,sanitize or replace carpeting reportedly filled with human urine stains and excrement.1306hc.
not activeJan 29, 2003
building section · failure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02.
submit a building permit application with plans to the department of building inspection within 15 days of this notice to comply with the residential hotel sprinkler ordinance #170-02, section 904 s.f.h.c.
not activeMar 28, 2002
building section · water damaged 3rd floor hallway ceiling.
resheetrock/replaster and paint water damaged ceiling surfaces in 3rd floor hallway.1001hc.
not activeMar 28, 2002
building section · water damaged linen closet,walls and ceiling surfaces in #324.
1)replace all buckling,soaked water damaged plaster in gr#324.1001hc. 2)replaster and paint unit #324.1301hc.
not activeMar 28, 2002
building section · defective waste pipe in #531,431,causing overhead leaks and ceiling damage on 3rd floor hallway ceiling as well as in #324.
repair /replace defective waste line in gr#531,431.(hand wash basin )1001hc.
not activeSep 26, 2000
building section · cracked walls and ceiling surfaces.
replaster and paint walls and ceiling surfaces in #625.1001hc./1301hc.
not activeSep 26, 2000
building section · missing radiator unit
install a radiator unit to the premises.701hc.
not activeSep 26, 2000
building section · insanitary carpeting.
replace insanitary carpeting.1306hc.
not activeSep 26, 2000
building section · lack of a hard wired smoke detector.
replace missing hard wired smoke detector.908hc.
not activeSep 26, 2000
building section · insanitary premises
clean and sanitize premises throughout.1306hc.
not activeSep 26, 2000
building section · damaged steam line wrapping.
rewrap damaged portion of steam line in unit #625.1001hc.
not activeDec 29, 1998
other section · miscellaneous violations
repair heater in room #622 (heater is leaking on to carpet ) sfhc 701.