44 MCALLISTER ST

Tenderloin · San Francisco, CA · Parcel 0349004 · Last violation May 15, 2026 · Last complaint Nov 6, 2025

NeighborhoodTenderloin
More violations than 86% of nearby buildings
More violations than 86% of buildings and more complaints than 82% of buildings in Tenderloin. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 22 violations · 13 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
19 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Open fire-safety violations0
Open lead violations0
311 Housing Complaints
Total complaints since 2010
78
5 per year avg.↓ Down 24% in the last 2 years (13 vs 17 prior 2 yrs)
Reported issues
13
Heatⓘ3
Leadⓘ2
Pestsⓘ23
Dept. of Building Inspection Violations
Total violations since 1998
217
7 per year avg.↓ Down 41% in the last 2 years (22 vs 37 prior 2 yrs)
Open violations
19
Fire safetyⓘ0
Leadⓘ0

Top violation categories

5 yrsAll time
building sectionⓘ67 violations
other sectionⓘ48 violations
interior surfaces sectionⓘ31 violations
plumbing and electrical sectionⓘ31 violations
sanitation sectionⓘ14 violations
fire section10 violations
Unknownⓘ8 violations
security requirements section4 violations
smoke detection section4 violations

Top complaint types

5 yrsAll time
Infestation Rodent Insect17 complaints
Mold And Mildew15 complaints
General Maintenance Not In List Above8 complaints
Infestation Bed Bugs6 complaints
Plumbing Broken Leaking6 complaints
Ventilation Inadequate Or None3 complaints
Heat Lack Of Heat3 complaints
Elevators No Working Elevator 7 Or More Stories3 complaints
Paint Lead Violating Safe Practices2 complaints
Doors Windows Broken Defective2 complaints
Fire Alarm System2 complaints
Fire Hazard2 complaints
Paint Peeling2 complaints
Visitor Policy Violations1 complaints
Clutter Hoarder Unit Interior Storage1 complaints
Electrical Hazardous Condition1 complaints
Electrical Non Hazard1 complaints
Elevators Everthing Else1 complaints
Security Inadequately Secured Perimeter1 complaints
Bathroom1 complaints
Hide violations (217) ↑See complaints (78) →

Violation log

217 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeJun 4, 2019other sectionrepair stove (1001 hc)replace missing lights on stoves and repair fans that aren't functioning. observed lights missing at: both 8th floor stoves, both second floor stoves, both basement kitchen stoves stove fans not functioning at: both second floor stoves, and one 8th floor stove.
See something wrong? File a complaint with SF 311
not activeJun 4, 2019plumbing and electrical sectionmake necessary repairs to tub/shower (1001 hc)make following repairs to common area shower/bathrooms: -replace/repair shower hose in accessible showers. 7th floor head is missing from hose, 4th floor hose is missing, 2nd floor hose is missing. -replace shower curtains in all showers. -clear backed up drain at 7th floor accessible shower -repair broken/deteriorated grab bars at 2nd floor accessible bathroom -replace seat at 2nd floor accessible bathroom
not activeJun 4, 2019building sectionreplace broken glass window pane (1001(h),708 hc)replace broken window pane in room 709
not activeApr 4, 2019smoke detection sectionprovide smoke detector and carbon monoxide affidavit (420.4, 907.2.11 & 3401.6.1 sfbc)provide self-certification affidavit for smoke alarms and carbon monoxide detectors (enclosed).
not activeApr 4, 2019building sectionthis notice includes violations for the areas noted.common areas of 44 mcallister street
not activeApr 4, 2019building sectioncomply with seciton 604 of the san francisco housing code (604 hc)complete and return to housing inspection services the compliance affidavit for section 604 of the san francisco housing code (enclosed).
not activeApr 4, 2019fire sectionrepair manual release at fire escape window (801 hc)2nd floor fire escape window facing mcallister street is stuck shut. ensure that exit to fire escape can be opened from inside without use of a key, tool, special knowledge or effort.
not activeApr 4, 2019other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to a access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 25, 2019interior surfaces sectionremove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)remove any damaged/peeling paint in approved manner.
not activeMar 25, 2019interior surfaces sectionrepair damaged walls (1001b,h,o hc)repair cracks and holes in exterior wall of unit.
not activeMar 25, 2019other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to a access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. correction of violations cited in this notice may require building, plumbing and/or electrical permits. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). when applying for a permit, reference the complaint number from this notice of violation. you must have the proper permit signed-off and finalized before housing inspector returns in order for this violation to be abated.
not activeMar 25, 2019sanitation sectioneliminate cockroach infestation (1001b, 1306 hc)cockroaches observed in unit. have licensed pest control contractor treat building in approved manner to eliminate cockroaches. provide written documentation of treatment from pest control company at time of reinspection.
not activeMar 25, 2019interior surfaces sectionlocate source of water damage (703, 1001f hc)locate source of stains and damage at exterior wall. possible water stains.
not activeMar 25, 2019interior surfaces sectionrepair source of water damage (703,1001f hc)once source of stains and damaged walls is located, repair to prevent further damage.
not activeMar 25, 2019building sectionthis notice includes violations for the areas noted.44 mcallister unit 623
not activeMar 25, 2019sanitation sectionclean or sanitize (1306 hc)clean dust/debris from wall and ceiling fan.
not activeMar 25, 2019interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.—
not activeSep 24, 2018interior surfaces sectionprovide weather tight seal at the bottom of door (1001 hc)unit l02: at the time of inspection a gap was noted at the entry door to the guestroom. repair/seal.
not activeSep 24, 2018interior surfaces sectioneliminate/repair threshold at shower room near l02 (1001 hc) remove egress obstruction at shower room near l02 (801,1001(l) hc)common area: eliminate/repair loose/damaged threshold at shower room lcoated near l02. ensure that bathroom is wheelchair accessible and that damaged threshold does not act as an egress obstruction.
not activeSep 24, 2018plumbing and electrical sectionrepair shower wall and properly afix stool in shower (1001d,f hc)common area: at the time of inspection, in the shower room near unit l02, a damaged/loose stool was noted as well as a damaged wall surface in the shower area where the stool was affixed. repair/replace.
not activeSep 24, 2018sanitation sectionclean or sanitize lower level trash room near unti l02 (1306 hc)common area: at the time of inspection unsanitary floors and walls were noted in trash room. clean/sanitize.
not activeSep 24, 2018building sectionthis notice includes violations for the areas noted.unit l02 and common areas
not activeSep 24, 2018other sectioninspector commentsnote: as in previous years, your cooperation is now being requested to facilitate a housing code required periodic health and safety inspection of the building referenced above. our records show that the referenced property is due for this inspection, and your assistance is necessary to provide our inspector entry to accomplish this. chapters 1, 2 & 3 of the san francisco housing code require that the department of building inspection perform periodic health and safety inspections of the common and public areas of residential property and includes common hallways, required means of egress, fire escapes, roofs accessible by stairways, garages, basements, storage rooms/areas, boiler/utility rooms, laundry rooms, garbage rooms/areas, court yards and rear yards. please note that the interior of apartment units are not part of this review unless requested by a unit occupant at the time of inspection. due to the violations noted, this property constitutes a nuisance per the san francisco housing code section 1001(d). it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeSep 24, 2018sanitation sectioneliminate cockroach infestation (1001b, 1306 hc)common areas and unit l02: there is evidence of a cockroach infestation in the lowel level community kitchen, lower level trash room near l02, and unit l02. initiate or increase frequency of professional pest control services to obtain more immediate results in the elimination of infestation. show proof of services at time of reinspection. ensure areas where roaches have been spotted are treated including around ducts, flues, and in or around kitchen cabinetry.
not activeApr 20, 2018———
not activeFeb 13, 2018security requirements sectioninspectors commentthe complaint also stated that the steam heat pipes were banging and making noise: inspect the steam heat system and drain the system as needed to eliminate any banging pipes.
not activeFeb 13, 2018building sectionbuilding permit required (301 hc)a building permit is required for replacing windows. provide a copy of all completed permits to the housing inspector at the time of re-inspection.
not activeFeb 13, 2018other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice. all open notices of violation will be re-inspected at this time
not activeFeb 13, 2018building sectionrepair window sash frame (1001(h),708 hc)the lower sash of the double hung window in the 8th floor kitchen will not open; repair as needed to make this window operable.
not activeFeb 13, 2018building sectionrepair window latches or hardware (1001(b)hc)at the time of inspection a number of windows had missing or defective handles. replace all defective window hardware including the following: 1) entry lobby windows- broken handles. 2) third floor fire escape window won't latch or lock 3) 7th floor fire escape window won't close or lock. 4) 8th floor kitchen window has a broken handle.
not activeFeb 13, 2018building sectioninspectors commentviolations cited are located in the common areas.
not activeOct 5, 2016other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeOct 5, 2016other sectionrepair defective or non-working elevator (1001(l), 713 hc)at the time of inspection the elevator was operating erratically and the following violations were observed: 1)the elevators repeatedly got stuck on floors 6 & 7. -the door to elevator 1 would stay open for approx. 45-60 seconds for no apparent reason; the doors would then repeatedly open and close before finally closing and going to the wrong floor. -the door to elevator 2 stayed open for approx. 45-60 seconds for no apparent reason before closing and moving to another floor. 2) most buttons in both elevators and many of the call buttons at the different floor levels don't light. correct the cited violations. also, it's been reported that the elevators will temporarily shut down without warning. when this happens the digital display which indicates what floor the elevator cab is located on will instead display an asterisk. have an appropriatly licensed contractor inspect the elevator system and make the needed repairs to insure the system is operating reliably in a safe manner.
not activeMar 31, 2016building sectioninspectors commentviolations cited are located in unit #417.
not activeMar 31, 2016other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeMar 31, 2016plumbing and electrical sectionrepair or replace malfunctioning refrigerator (505.(c) (1001.(b)(13) hc)the refridgerators freezer door is missing causing frost to build up in the refridgerator; replace the freezer door.
not activeMar 31, 2016plumbing and electrical sectionother plumbing violationsat the time of inspection the radiator was leaking and the pan was full of water. repair the leaking radiator.
not activeJul 14, 2015other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJul 14, 2015building sectionthis notice includes violations for the areas noted.the common areas of 44 mcallister street
not activeJul 14, 2015building sectionmake necessary repairs to inoperable elevator. 1001(e) sfhcmake necessary repairs to inoperable elevator serving residential floors.
not activeMar 18, 2011fire sectioncertify alarm panel (909(d), 1001(d)(n) hc)provide annual certification of fire alarm system from a licensed fire alarm system company at re-inspection.
not activeMar 18, 2011fire sectionremove egress obsturction (810,1001(d) hc)remove locking device at roof door. the door shall be opened from the interior with no special effort or key. the means of egress path of travel must remain un-obstructed.
not activeMar 18, 2011other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is he/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMar 18, 2011building sectionthis notice includes violations for the areas noted.44 mcallister street - common area
not activeAug 23, 2010———
not activeAug 23, 2010———
not activeFeb 25, 2009———
not activeMar 20, 2007other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMar 20, 2007other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)provide the required amount of heat to #218.
not activeMar 2, 2007fire sectionremove flammable storage (904,1001(i) hc)remove the flammable storage in the basement maintenace room or store under a sprinkler head in a closed metal cabinet.
not activeJun 4, 2019
other section · repair stove (1001 hc)
replace missing lights on stoves and repair fans that aren't functioning. observed lights missing at: both 8th floor stoves, both second floor stoves, both basement kitchen stoves stove fans not functioning at: both second floor stoves, and one 8th floor stove.
not activeJun 4, 2019
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
make following repairs to common area shower/bathrooms: -replace/repair shower hose in accessible showers. 7th floor head is missing from hose, 4th floor hose is missing, 2nd floor hose is missing. -replace shower curtains in all showers. -clear backed up drain at 7th floor accessible shower -repair broken/deteriorated grab bars at 2nd floor accessible bathroom -replace seat at 2nd floor accessible bathroom
not activeJun 4, 2019
building section · replace broken glass window pane (1001(h),708 hc)
replace broken window pane in room 709
not activeApr 4, 2019
smoke detection section · provide smoke detector and carbon monoxide affidavit (420.4, 907.2.11 & 3401.6.1 sfbc)
provide self-certification affidavit for smoke alarms and carbon monoxide detectors (enclosed).
not activeApr 4, 2019
building section · this notice includes violations for the areas noted.
common areas of 44 mcallister street
not activeApr 4, 2019
building section · comply with seciton 604 of the san francisco housing code (604 hc)
complete and return to housing inspection services the compliance affidavit for section 604 of the san francisco housing code (enclosed).
not activeApr 4, 2019
fire section · repair manual release at fire escape window (801 hc)
2nd floor fire escape window facing mcallister street is stuck shut. ensure that exit to fire escape can be opened from inside without use of a key, tool, special knowledge or effort.
not activeApr 4, 2019
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to a access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 25, 2019
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
remove any damaged/peeling paint in approved manner.
not activeMar 25, 2019
interior surfaces section · repair damaged walls (1001b,h,o hc)
repair cracks and holes in exterior wall of unit.
not activeMar 25, 2019
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to a access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. correction of violations cited in this notice may require building, plumbing and/or electrical permits. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). when applying for a permit, reference the complaint number from this notice of violation. you must have the proper permit signed-off and finalized before housing inspector returns in order for this violation to be abated.
not activeMar 25, 2019
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
cockroaches observed in unit. have licensed pest control contractor treat building in approved manner to eliminate cockroaches. provide written documentation of treatment from pest control company at time of reinspection.
not activeMar 25, 2019
interior surfaces section · locate source of water damage (703, 1001f hc)
locate source of stains and damage at exterior wall. possible water stains.
not activeMar 25, 2019
interior surfaces section · repair source of water damage (703,1001f hc)
once source of stains and damaged walls is located, repair to prevent further damage.
not activeMar 25, 2019
building section · this notice includes violations for the areas noted.
44 mcallister unit 623
not activeMar 25, 2019
sanitation section · clean or sanitize (1306 hc)
clean dust/debris from wall and ceiling fan.
not activeMar 25, 2019
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeSep 24, 2018
interior surfaces section · provide weather tight seal at the bottom of door (1001 hc)
unit l02: at the time of inspection a gap was noted at the entry door to the guestroom. repair/seal.
not activeSep 24, 2018
interior surfaces section · eliminate/repair threshold at shower room near l02 (1001 hc) remove egress obstruction at shower room near l02 (801,1001(l) hc)
common area: eliminate/repair loose/damaged threshold at shower room lcoated near l02. ensure that bathroom is wheelchair accessible and that damaged threshold does not act as an egress obstruction.
not activeSep 24, 2018
plumbing and electrical section · repair shower wall and properly afix stool in shower (1001d,f hc)
common area: at the time of inspection, in the shower room near unit l02, a damaged/loose stool was noted as well as a damaged wall surface in the shower area where the stool was affixed. repair/replace.
not activeSep 24, 2018
sanitation section · clean or sanitize lower level trash room near unti l02 (1306 hc)
common area: at the time of inspection unsanitary floors and walls were noted in trash room. clean/sanitize.
not activeSep 24, 2018
building section · this notice includes violations for the areas noted.
unit l02 and common areas
not activeSep 24, 2018
other section · inspector comments
note: as in previous years, your cooperation is now being requested to facilitate a housing code required periodic health and safety inspection of the building referenced above. our records show that the referenced property is due for this inspection, and your assistance is necessary to provide our inspector entry to accomplish this. chapters 1, 2 & 3 of the san francisco housing code require that the department of building inspection perform periodic health and safety inspections of the common and public areas of residential property and includes common hallways, required means of egress, fire escapes, roofs accessible by stairways, garages, basements, storage rooms/areas, boiler/utility rooms, laundry rooms, garbage rooms/areas, court yards and rear yards. please note that the interior of apartment units are not part of this review unless requested by a unit occupant at the time of inspection. due to the violations noted, this property constitutes a nuisance per the san francisco housing code section 1001(d). it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeSep 24, 2018
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
common areas and unit l02: there is evidence of a cockroach infestation in the lowel level community kitchen, lower level trash room near l02, and unit l02. initiate or increase frequency of professional pest control services to obtain more immediate results in the elimination of infestation. show proof of services at time of reinspection. ensure areas where roaches have been spotted are treated including around ducts, flues, and in or around kitchen cabinetry.
not activeApr 20, 2018
—
not activeFeb 13, 2018
security requirements section · inspectors comment
the complaint also stated that the steam heat pipes were banging and making noise: inspect the steam heat system and drain the system as needed to eliminate any banging pipes.
not activeFeb 13, 2018
building section · building permit required (301 hc)
a building permit is required for replacing windows. provide a copy of all completed permits to the housing inspector at the time of re-inspection.
not activeFeb 13, 2018
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice. all open notices of violation will be re-inspected at this time
not activeFeb 13, 2018
building section · repair window sash frame (1001(h),708 hc)
the lower sash of the double hung window in the 8th floor kitchen will not open; repair as needed to make this window operable.
not activeFeb 13, 2018
building section · repair window latches or hardware (1001(b)hc)
at the time of inspection a number of windows had missing or defective handles. replace all defective window hardware including the following: 1) entry lobby windows- broken handles. 2) third floor fire escape window won't latch or lock 3) 7th floor fire escape window won't close or lock. 4) 8th floor kitchen window has a broken handle.
not activeFeb 13, 2018
building section · inspectors comment
violations cited are located in the common areas.
not activeOct 5, 2016
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeOct 5, 2016
other section · repair defective or non-working elevator (1001(l), 713 hc)
at the time of inspection the elevator was operating erratically and the following violations were observed: 1)the elevators repeatedly got stuck on floors 6 & 7. -the door to elevator 1 would stay open for approx. 45-60 seconds for no apparent reason; the doors would then repeatedly open and close before finally closing and going to the wrong floor. -the door to elevator 2 stayed open for approx. 45-60 seconds for no apparent reason before closing and moving to another floor. 2) most buttons in both elevators and many of the call buttons at the different floor levels don't light. correct the cited violations. also, it's been reported that the elevators will temporarily shut down without warning. when this happens the digital display which indicates what floor the elevator cab is located on will instead display an asterisk. have an appropriatly licensed contractor inspect the elevator system and make the needed repairs to insure the system is operating reliably in a safe manner.
not activeMar 31, 2016
building section · inspectors comment
violations cited are located in unit #417.
not activeMar 31, 2016
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeMar 31, 2016
plumbing and electrical section · repair or replace malfunctioning refrigerator (505.(c) (1001.(b)(13) hc)
the refridgerators freezer door is missing causing frost to build up in the refridgerator; replace the freezer door.
not activeMar 31, 2016
plumbing and electrical section · other plumbing violations
at the time of inspection the radiator was leaking and the pan was full of water. repair the leaking radiator.
not activeJul 14, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJul 14, 2015
building section · this notice includes violations for the areas noted.
the common areas of 44 mcallister street
not activeJul 14, 2015
building section · make necessary repairs to inoperable elevator. 1001(e) sfhc
make necessary repairs to inoperable elevator serving residential floors.
not activeMar 18, 2011
fire section · certify alarm panel (909(d), 1001(d)(n) hc)
provide annual certification of fire alarm system from a licensed fire alarm system company at re-inspection.
not activeMar 18, 2011
fire section · remove egress obsturction (810,1001(d) hc)
remove locking device at roof door. the door shall be opened from the interior with no special effort or key. the means of egress path of travel must remain un-obstructed.
not activeMar 18, 2011
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is he/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMar 18, 2011
building section · this notice includes violations for the areas noted.
44 mcallister street - common area
not activeAug 23, 2010
—
not activeAug 23, 2010
—
not activeFeb 25, 2009
—
not activeMar 20, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMar 20, 2007
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
provide the required amount of heat to #218.
not activeMar 2, 2007
fire section · remove flammable storage (904,1001(i) hc)
remove the flammable storage in the basement maintenace room or store under a sprinkler head in a closed metal cabinet.