not activeMay 2, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on monday, 02-june-2014 at 1:30 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated. important note: please be sure to review the attached "notice of violation warnings!" for information & costs associated with failure to comply with this notice of violation.
not activeMay 2, 2014
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable of maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
it was noted at time of inspection that baseboard heater in apartment #426 was not properly installed, electrical permits required in order to bring heater up to code: *note* permits must be signed off by assigned inspector (electrical, plumbing or building )before scheduled housing reinspection
not activeMay 2, 2014
sanitation section · eliminate bedbug infestation (1001b, 1306 hc)
you are required to follow the guidlines pursuant article 11, section 581 of the san francisco health code. pco report must be presented at time of re-inspection, no exceptions.
not activeMar 11, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 14-march-2014 at 8:30 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeMar 11, 2014
building section · this notice includes violations for the areas noted.
57 taylor street apartment #400
not activeMar 11, 2014
plumbing and electrical section · repair electrical outlet (1001e hc)
in kitchen of apartment #400
not activeMar 11, 2014
building section · replace broken glass window pane (1001(h),708 hc)
replace missing louvre glass in bathroom in apartment #400
not activeMar 11, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on monday, 11-april-2014 at 1:30 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeMar 11, 2014
interior surfaces section · replace kitchen cabinet (1001hc)
replace kitchen cabinet in apartment #400
not activeMar 11, 2014
interior surfaces section · re-caulk shower
remove old caulking in shower and re-caulk in bathroom in apartment #400
not activeMar 11, 2014
building section · this notice includes violations for the areas noted.
57 taylor street apartment #400
not activeMar 11, 2014
plumbing and electrical section · repair sink (1001f hc)
unclog sink drain in bathroom of apartment #400
not activeMar 11, 2014
plumbing and electrical section · repair sink (1001f hc)
in bathroom, provide shutoff valves in bathroom in apartment #400
not activeMar 11, 2014
interior surfaces section · repair damaged floor (1001b,j,o hc)
tear up floor covering in bathroom and expose all damaged area and call back inspector in order to point out all necessary repairs that are required in floor and if building permits will be required for repairs.
not activeMar 11, 2014
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
repair or replace baseboard heater in apartment #400
not activeFeb 24, 2014
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
in apartment #308
not activeFeb 24, 2014
sanitation section · eliminate bedbug infestation (1001b, 1306 hc)
in apartment #308 you are required to follow the guidlines pursuant article 11, section 581 of the san francisco health code. pco report must be presented at time of re-inspection, no exceptions.
not activeFeb 24, 2014
interior surfaces section · provide closet door (1001hc)
provide a closet door in apartment #308
not activeFeb 24, 2014
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
re-finish bathtub in bathroom of apartment #308
not activeFeb 24, 2014
interior surfaces section · eliminate mold/mildew (1301,1001b(13),1306 hc)
in apartment #308 around window facing west side of building
not activeFeb 24, 2014
building section · this notice includes violations for the areas noted.
57 taylor street apartment #308
not activeFeb 24, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on monday, 14-april-2014 at 1:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeMar 19, 2013
other section · due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed. it is also the owner's responsibility to provide prior notification of intended entry to all affected tenants, per california civil code 1954 (303b hc)
not activeMar 19, 2013
building section · this notice includes violations for the areas noted.
rm. 308.
not activeMar 19, 2013
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
a) replace missing heater. b) provide required heat/room temperature.
not activeMar 14, 2013
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
not activeMar 14, 2013
sanitation section · eliminate bedbug infestation (1001b, 1306 hc)
not activeMar 14, 2013
interior surfaces section · repair and paint damaged walls/ceilings/doors (1001b,h,o hc)
a) repair the entry door door jamb and loose strike plate. b) repair deteriorated floor threshold at entry door. c) repair the door and clothing hanger rod for the bathroom closet. d) repair and paint the walls near the bathroom closet and tub at floor level. e) repair and paint the water damaged bathroom ceiling.
not activeMar 14, 2013
interior surfaces section · repair source of water damage (703,1001f hc)
repair leak at bathroom ceiling.
not activeMar 14, 2013
building section · this notice includes violations for the areas noted.
#308
not activeMar 14, 2013
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
a) repair shower valve handle. b) repair shower wall tiles. c) replace deteriorated and stained caulking in shower.
not activeMar 14, 2013
other section · due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed. it is also the owner's responsibility to provide prior notification of intended entry to all affected tenants, per california civil code 1954 (303b hc)
not activeMar 14, 2013
plumbing and electrical section · repair electrical (1001e hc)
repair the main entry intercom system for the building.
not activeMar 14, 2013
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
not activeJan 30, 2013
interior surfaces section · paint walls/ceilings (1001b,1301 hc)
paint walls and ceilings throughout.
not activeJan 30, 2013
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
not activeJan 30, 2013
smoke detection section · replace smoke detector (908, 911 hc)
not activeJan 30, 2013
building section · this notice includes violations for the areas noted.
#314
not activeJan 30, 2013
sanitation section · replace medicine cabinet (1001 hc)
replace the damaged medicine cabinet in the bathroom.
not activeJan 30, 2013
interior surfaces section · repair floor covering (1001b,j,o hc)
replace damaged floor tile.
not activeJan 30, 2013
sanitation section · repair kitchen cabinets (505 hc)
repair all damaged kitchen cabinets.
not activeJan 30, 2013
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
repair/replace the heater and provide the required heat.
not activeJan 30, 2013
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
not activeJan 30, 2013
other section · due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed. it is also the owner's responsibility to provide prior notification of intended entry to all affected tenants, per california civil code 1954 (303b hc)
not activeJan 30, 2013
sanitation section · repair stove (505 hc)
replace the stove or replace the missing control knobs and make the stove fully operational. several burners were reported to be not working.
not activeDec 19, 2012
plumbing and electrical section · repair light (1001e hc)
replace missing light fixture at bathroom ceiling or cover the open wiring in a finished manner.
not activeDec 19, 2012
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
restore shower wall/tiles to finished condition.
not activeDec 19, 2012
building section · this notice includes violations for the areas noted.
#316
not activeDec 19, 2012
other section · inspector comments
due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed. it is also the owner's responsibility to provide prior notification of intended entry to all affected tenants per california civil code 1954 (303b hc)
not activeDec 19, 2012
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
eliminate mouse infestation.