not activeSep 24, 2014
building section · this notice includes violations for the areas noted.
all common areas of 445 ofarrell street
not activeSep 24, 2014
interior surfaces section · paint walls and ceilings (1001b,1301 hc)
areas around electrical panel; comments regarding possible lead based paint "disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 square feet. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97."
not activeJul 28, 2014
security requirements section · provide primary locking device at exterior door (706 hc)
install a single cylinder dead latch at the rear exit on the first floor
not activeJul 28, 2014
building section · this notice includes violations for the areas noted.
all common areas of 445 ofarrell street
not activeJul 28, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on wednesday, 06-august-at 1:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeJul 28, 2014
security requirements section · provide self-closing device at exterior door (706 hc)
install a self closing device at rear exit on the first floor
not activeJul 10, 2014
security requirements section · other security violations
replace deadlatch system to door to room #221
not activeJul 10, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 18-july-2014 at 1:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated. important note: please be sure to review the attached "notice of violation warnings!" for information & costs associated with failure to comply with this notice of violation.
not activeJul 10, 2014
building section · this notice includes violations for the areas noted.
445 ofarrell street room # 221
not activeJun 23, 2014
smoke detection section · in guestroom #322, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #224, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
smoke detection section · in guestroom #320, correct all violations cited in the column to the right.
(a) provide missing smoke detector (908, 911 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #304, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair light switch (1001e hc). (e) tenant reported that there was no heat (701c hc). (f) provide missing smoke detector (908, 911 hc). (g) provide carbon monoxide detector (420 sfbc). (h) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (i) repair damaged floor covering (1001b, 1306 hc). (j) provide designated guestroom number at entry door, should be a contrasting color (706 hc). (k) provide required fireproofing at all pipe penetrations (1001-h hc). (l) remove hasps or i-bolts on guestroom door (801, 1001-b hc). (m) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
fire section · in guestroom #410, correct all violations cited to the column to the right.
(a) provide designated guestroom number at entry door, should be a contrasting color (706 hc).
not activeJun 23, 2014
fire section · in guestroom #415, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall next to sink and repaint (1001-b, 1306 hc). (c) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
fire section · in guestroom #429, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall around sink and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (e) repair damaged floor covering, loose carpeting (1001b, 1306 hc). (f) remove hasps or i-bolts on guestroom door (801, 1001-b hc).
not activeJun 23, 2014
building section · repair or replace guestroom sink (1001-b,f hc)
porcelain on many guestroom sinks is chipped and underlying metl exposed and rusty making sinks difficult to keep clean. repair or replace all guestroom sinks where chips have exposed underlying metal, including those in specific guestroom locations indicated below. cracked or broken sinks must be replaced.
not activeJun 23, 2014
building section · provide carbon monoxide detector / alarms (420 sfbc)
carbon monoxide detector-alarms are required in all sleeping rooms on floors with fossil fuel-burning heater or appliances, fireplaces or attached garages and on all floors above and below a fossil fuel-burning heater or appliance, fireplace or attached garage. since there is a gas burning appliance in the basement of the hotel, carbon monoxide detector-alarms are required in all sleeping rooms on the first floor above the basement and in the common areas on the same floor. note: combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type of detector-alarms.
not activeJun 23, 2014
sanitation section · in guestroom #104, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace loose faucets at guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #204, correct all violations cited in the column to the right.
(a) provide door sweep, repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall next to bed and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
building section · replace guestroom sink drain pipes (1001-f hc)
several guestroom sinks leak at drains or have improper plastic drain pipes. replace sink drains where damaged, leaking or of unapproved materials including those in specific locations indicated below.
not activeJun 23, 2014
building section · repair, provide or adjust required hardware on smoke enclosure doors (706, 807 hc)
all guestroom entry doors are smoke enclosure doors and are required to be self closing and self latching (with handles that control the latch). many guestroom doors have damaged or missing door closers, damaged or missing door latch with handles or are out of adjustment. at all guestroom doors including specific guestroom locations indicated below, provide door closer and latch with handles and adjust as necessary so all doors fully self close and latch and are tight-fitting.
not activeJun 23, 2014
fire section · in guestroom #402, correct all violations in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) install latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
fire section · in guestroom #428, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall, ceiling, moulding and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, latch, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair light (1001e hc). (e) repair/replace damaged/rusted/chipped guestroom sink and faucet (505, 1001b,f hc). (f) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
building section · paint walls, ceilings and/or trim (1001-b, 1301, 1306 hc)
repaint all areas where paint is removed or damaged or where surfaces are repaired including specific guestroom locations indicated below.
not activeJun 23, 2014
building section · this notice includes violations for the areas noted.
room to room and common area inspection of the subject property.
not activeJun 23, 2014
sanitation section · in guestroom #106, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling above sink and in closet and repaint (1001-b, 1306 hc). (c) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #211, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches, also repair damaged door jam (706, 807, 1001-b hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #200, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide missing smoke detector (908, 911 hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
sanitation section · in guestroom #110, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged walls and ceilings and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
sanitation section · in guestroom #102, correct all violations cited in the column to the right.
(a) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
building section · replace substandard guestroom smoke enclosure doors (706, 807 hc)
several guestroom doors are deteriorated, are not tight fitting or have been replaced with unapproved doors. at all guestrooms including specific locations indicated below, replace all damaged doors and all unapproved replacement doors with approved one-and-three-eighths inch solid core wood door or rated metal doors. the replacement doors are required to be tight-fitting, self closing and self latching (with handles that control the latch) and have a deadbolt with thumb turn on he inside and in good condition for security and smoke enclosure purposes.
not activeJun 23, 2014
building section · provide minimum 135 degree viewer for guestroom entry doors (706 hc)
wherever viewers are missing or painted over and in specific guestroom locations indicated below, provide approved guestroom door viewers.
not activeJun 23, 2014
fire section · in guestroom #421, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
fire section · in guestroom #418, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
fire section · in guestroom #424, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
building section · repair windows (708, 1001-b,h hc)
in several guestrooms, window sash frames do not operate correctly, have broken or missing sash cords, do not latch and/or provide adequate seal. repair or replace and adjust as needed so all guestroom windows, including those at specific locations indicated below, operate correctly, can be latched and provide an adequate seal.
not activeJun 23, 2014
sanitation section · in guestroom #100, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall at closet door and repaint (1001-b, 1306 hc).
not activeJun 23, 2014
sanitation section · in guestroom #109, correct all violations cited in the column to the right.
(a) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #201, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair light (1001e hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #226, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling above tub and repaint (1001-b, 1306 hc). (c) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
smoke detection section · in guestroom #301, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) remove hasps or i-bolts on guestroom door (801, 1001-b hc).
not activeJun 23, 2014
smoke detection section · in guestroom #309, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) in the bathroom, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (d) repair running toilet (505, 1001b, hc). (e) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
fire section · in guestroom #411, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #206, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink and loose faucets (505, 1001b,f hc). (d) repair damaged floor covering (1001b, 1306 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #218, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) in bathroom and guestroom repair damaged wall and ceiling and repaint (1001-b, 1306 hc).
not activeJun 23, 2014
fire section · in guestroom #430, correct all violations cited in the column to the right.
(a) remove hasps or i-bolts on guestroom door (801, 1001-b hc).
not activeJun 23, 2014
fire section · in guestroom #405, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom tub and repair leaking faucet in tub (505, 1001b,f hc).
not activeJun 23, 2014
smoke detection section · in guestroom #307, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling and repaint (1001-b, 1306 hc). (c) repair/replace damaged/rusted/chipped guestroom sink and faucets (505, 1001b,f hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #329, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc).