not activeJul 17, 2017
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
at the time of inspection roaches were observed inside the apartment near the entry door. have a licensed pest control contractor eliminate the cockroach infestation. provide a copy of the pest control invoice and remediation plan to the housing inspector at the time of re-inspection.
not activeJul 17, 2017
plumbing and electrical section · kitchen 505(c) 1001.(g) hc
at the time of inspection one burner element to the electric cooktop was missing; replace the missing burner element.
not activeJul 17, 2017
plumbing and electrical section · other electrical violations
replace the kitchens missing ceiling light fixture cover.
not activeJul 17, 2017
smoke detection section · replace smoke detector (908, 911 hc)
replace the missing hardwired smoke alarm.
not activeJul 17, 2017
building section · inspectors comment
violations cited are located in #415.
not activeMay 18, 2017
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeMay 18, 2017
plumbing and electrical section · repair or replace malfunctioning refrigerator (505.(c) (1001.(b)(13) hc)
the gasket sealing the lower door of the refridgerator in #208 is failing; repair or replace the defective refridgerator door seal.
not activeOct 21, 2015
plumbing and electrical section · repair or replace malfunctioning electric range (505.(c) (1001.(b)(13) hc)
the larger electric range top burner in unit #208 is not working and the smaller burner only works intermittantly. repair or replace both burners.
not activeOct 21, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeOct 6, 2014
building section · this notice includes violations for the areas noted.
all violations listed below are located in unit #208 unless otherwise noted.
not activeOct 6, 2014
building section · repair apartment entry door (807, 1001-b hc)
at unit #208, surface of entry door is chipped. repair and repaint.
not activeOct 6, 2014
plumbing and electrical section · repair refrigerator (1001-b hc)
in unit #208, the refrigerator is out of level. it leans forward. re-level refrigerator.
not activeOct 6, 2014
building section · provide security at apartment door (706, 1001-b hc)
at unit #208, the approved strike plate has been removed and an unapproved strike plate has been installed that does not provide security or fire protection. provide approved strike plate at entry door.
not activeOct 6, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector to all areas cited within this notice. it is the responsibility of the property owner to provide tenants with notification, as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during reinspection(s).
not activeJan 25, 2013
other section · due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed. it is also the owner's responsibility to provide prior notification of intended entry to all affected tenants, per california civil code 1954 (303b hc)
not activeJan 25, 2013
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
repair/replace the broken shower head holder in #208.
not activeNov 7, 2011
interior surfaces section · repair damaged doors (1001b,h,o hc)
repair detached bathroom doors in #208 and 232.
not activeNov 7, 2011
other section · due to the violations noted, this property is defined as a nuisance per sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed. it is also the owner's responsibility to provide prior notification of intended entry to all affected tenants per california civil code 1954 (303b hc)
not activeJan 25, 2010
building section · this notice includes violations for the areas noted.
480 ellis street
not activeJan 25, 2010
other section · provide adequate permanent source of heat to each habitable room (701(c) hc).
provide heat to each occupied habitable space for 13 hrs. between 5:00 a.m and 11:00 a.m. and between 3:00 pm and 10:00 p.m. capable to maintaining a min. room temperture of 68 degrees f (20 degrees c). at the time of inspection, existing boiler system heat source was non-functional. repair or replace the boiler per this notice of violation.
not activeJan 25, 2010
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is he/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJul 15, 2009
interior surfaces section · repair damaged walls (1001(b)#13 hc)
repair damaged wall behind the bed. repaint as required.
not activeJul 15, 2009
interior surfaces section · replace floor covering (1001(b)#13 hc)
replace the damaged linoleum flooring and repair any damaged sub-flooring in the bathroom.
not activeJul 15, 2009
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is he/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJul 15, 2009
building section · this notice includes violations for the areas noted.
480 ellis street - unit #417
not activeNov 14, 2008
interior surfaces section · repair damaged walls (1001b,h hc)
in #329 repair and paint the damaged wall surface above the sink located in the studio room.
not activeNov 14, 2008
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeNov 14, 2008
interior surfaces section · paint ceilings & walls (1001b,1301 hc)
prep and paint the peeling deteriorated paint in the bathroom of #329.
not activeNov 14, 2008
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 16, 2008
other section · repair defective or non-working elevator (1001(l), 713 hc)
the handicap lift at the hotel lobby entry is not in service. make the needed repairs to return it to service. in the meantime insure that the basement access to the hotel elevator is maintained for the mobility impaired.
not activeApr 16, 2008
plumbing and electrical section · make necessary repairs to shower (1001 hc)
repair the following violations: 1)non-functioning shower seat in bath near #442. 2)shower door hinged on the wrong side in shower room near #443.
not activeApr 16, 2008
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 16, 2008
plumbing and electrical section · repair electrical oven/range tops (1001 b13 hc)
repair/replace the following defective equipment on the fourth floor: front kitchen: 1)one range top stove missing all burners. 2)one oven with no oven door handle and two missing burners. rear kitchen: 3)missing range top control knob.
not activeApr 16, 2008
plumbing and electrical section · repair sink (1001f hc)
repair/replace the damaged sink backsplash in the rear kitchen on the 4th floor.
not activeJun 30, 2006
fire section · remove egress obstruction at (801,1001(l) hc)
remove the egress obstructions in #221: power tools, sewing machines, carts, etc.
not activeJun 30, 2006
fire section · permanently reduce combustible storage. (1001(i) hc)
reduce the amount of combustable storage in #247.
not activeJun 30, 2006
fire section · remove all hasps and eye hooks from the exterior of guest room doors ( 706 (a ii) hc)
remove the hasps and eye hooks from the exterior of al doors including those on room #'s347, 351, & 353.
not activeJun 30, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJun 30, 2006
smoke detection section · replace smoke detector (908, 911 hc)
replace the missing smoke alarm in #257.
not activeJun 20, 2006
sanitation section · clean or sanitize (1306 hc)
clean the oven in the rear kitchen of the fourth floor as well as any other ovens in need of cleaning.
not activeJun 20, 2006
plumbing and electrical section · replace the missing fan cover (1001 b, g, hc)
replace the missing fan cover in the shower room near #343.
not activeJun 20, 2006
building section · repair window sash frame (1001(h),708 hc)
repair the upper sash of the window on the right in unit #452 so that the window closes completely.
not activeJun 20, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJun 20, 2006
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
eliminate the cockroaches in #452.
not activeJun 20, 2006
plumbing and electrical section · replace the shower liner (1001 b 13, f hc)
replace/repair the broken shower liner and door to the shower stall in the shower room near #443.
not activeJun 20, 2006
building section · repair the door (1001 b 13, j, hc)
make the following repairs: toilet room near #305- repair the loose entry door hinges. shower room near #305- repair the sticking door and loose door handle.
not activeJun 20, 2006
plumbing and electrical section · repair damaged walls (1001b,h,o hc)
repair the loose wall patch on the latch side of the entry door to unit #452.
not activeJun 7, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.