not activeMay 10, 2006
building section · replace defective, cloged ,leaking shower head.1001hc.
replace leaking shower head, with an energy saving type.1001hc.
not activeMay 10, 2006
building section · install a latching device to all fire doors leading to fire escapes.1001hc.
not activeMay 10, 2006
building section · install a handrail along stairs connecting lobby area with basement stairs.1001hc
lack of requiered handrail along basement stairs.
not activeMay 10, 2006
building section · remove and replace insanitary, defective, shower stall tracks, door and assembly.
loose , detached shower door tracks, in need of repair or replacement. management indicated that a new curtain /rod will be installed.
not activeMay 10, 2006
building section · clean bathroom after each work day.
not activeMay 10, 2006
building section · remove and replace worn, water damaged caulking surrounding tub.1001hc.
1)remove existing caulking and recaulk tub surrounds,tub wall and wall floor junction in the bathroom of unit #208.
not activeMay 10, 2006
building section · install exit signs and directional arrows along common hallways leading to exterior fire escapes.811hc.
lack of directional signs along public hallways.
not activeMay 10, 2006
building section · paint bathroom walls and ceiling surfaces in unit#208.
1)eliminate mold and mildew from ceiling surfaces above bathroom window. 2)sand,prime and paint bathroom walls and ceiling surfaces with a mildew retardent enamel based paint.1001hc./1301hc.
not activeMay 10, 2006
building section · repair fireproofing to basement ceiling with 5/8 of an inch sheetrock type x.1001hc.
basement ceiling surfaces are damaged with holes and opening at various locations.
not activeMay 10, 2006
building section · reglaze or resurface heavily scratched handwash basin, commode and tub.1001hc.
handwash basin and the interior of the commode, appers to be repeatedly scraped and scratched with a flat blade.
not activeMay 10, 2006
building section · have boiler unit certified by a licensed boiler contractor.1001hc.
boiler unit is lacking annual certification.
not activeApr 4, 2006
other section · provide shutoff tool for gas utility shutoff (712 hc)
install shut off tool in a visible and accessible location and adjacent to main gas valve.make sure that the type/size of the tool fits the existing valve(s)
not activeApr 4, 2006
fire section · maintain fire escape drop ladder in working condition (sec 908 hc)
note: property manager, owner or the owner's agent needs to provide a proof of the workability of the fire escape ladders. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written report from a qualified service company or licenced contractor stating that all parts and cables have tested and are functional or contact the housing inspector (within 30 days) to witness lowering the ladder in person. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeApr 4, 2006
building section · other building violations
where required: designated missing unit/apartment identification numbers to all units or other room door,to be a contrast color (706 hc) sec 107.10 s.f.b.c.) (706 hc) sec(107.10 s.f.b.c.)
not activeApr 4, 2006
other section · heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
guest rooms are heated with steam heat, thermostat is located in room #306 boiler is located in the basement time clock located adjacent to the boiler
not activeApr 4, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as schedule on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with the inspector, and provide all tenants with notification as required by california civil code section 1954(san francisco housing code section 303(b),if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 4, 2006
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
# 102 and where required.
not activeApr 4, 2006
building section · this notice includes violations for the areas noted.
811 geary st. heat sweep inspection routine inspection of the (common area) building sec.(303 a s.f.h.c.)
not activeApr 4, 2006
other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
post gas diagram in a visible location so tenants are aware of emergency gas shut off procedures.
not activeApr 4, 2006
fire section · other fire violations
provide 24 gauge galvanized iron sheetmetal covering for the door to the basement. (sec. 803 s.f.h.c.) (cover the basement side of the door)
not activeDec 7, 2004
interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc)
#308's bathroom, and where required.
not activeDec 7, 2004
plumbing and electrical section · repair toilet (1001f hc)
#308, #504.
not activeDec 7, 2004
building section · repair windows(1001(b)hc)
#205, #304, #308, #501, #508, #511, #602, #609 and where required.
not activeDec 7, 2004
sanitation section · other sanitation violations
clean and organize #207.
not activeDec 7, 2004
plumbing and electrical section · remove cord wiring (1001-e hc)
common areas (i.e. 4th floor hallway -near stairs).
not activeDec 7, 2004
sanitation section · clean and maintain (1306 hc)
all common areas of the building including side yard, fire escapes, exterior walls and windows. clean radiator in #611. walls and ceilings in #511, #205 and where required.
not activeDec 7, 2004
plumbing and electrical section · provide adequate lighting (504g hc)
have the emergency lights tested annually and replace any malfunctioning / expired backup batteries as required.
not activeDec 7, 2004
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
#305's bathroom window frame/sill, and where required.
not activeDec 7, 2004
fire section · provide smoke enclosure door closer (807,707 hc)
at fire escapes and where required.
not activeDec 7, 2004
interior surfaces section · repair floor covering (1001b,j,o hc)
#509, #510's bathroom, #609, and where required. clean #305's carpet.
not activeDec 7, 2004
fire section · remove egress obstruction at (801,1001(l) hc)
test and verify that all windows and doors leading to the emergency fire escape are operational and unobstructed. test manual releases on window security bars on a regular basis including window hardware. advise occupants not to block the path of emergency exits on the inside particularly in sleeping rooms. remove any existing double cylinder locking devices that requires a key for exiting and replace with a single cylinder (dead-latch) lock.
not activeDec 7, 2004
fire section · other fire violations
discontinue use of cooking burners in guest rooms (509, etc.).
not activeDec 7, 2004
plumbing and electrical section · repair lights (1001e hc)
provide covers to ceiling lights as required (i.e. #511). repair #201's bathroom light.
not activeDec 7, 2004
plumbing and electrical section · repair sink (1001f hc)
leak at #308's faucet. resurface #206.
not activeDec 7, 2004
smoke detection section · maintain smoke detectors (908 911 hc)
it is recommended that smoke detectors be tested on a regular basis and all batteries be replaced annually to maintain a working and functional device. advise occupants not to disconnect the batteries or remove the units inside the apartments or from public areas.
not activeDec 7, 2004
interior surfaces section · for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises.
not activeDec 7, 2004
other section · miscellaneous violations
#508, adjust bathroom cabinet doors. provide identifying numbers/letters to manager's unit.
not activeDec 7, 2004
other section · inspector comments: open #211 for inspection at time of reinspection. it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice.
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice.
not activeDec 7, 2004
fire section · maintain fire escape drop ladders in working condition (sec 908 hc)
note: property manager, owner or the owner's agent needs to provide a proof of the workability of the fire escape ladders. non-working fire escape drop ladder is a life safety hazard and must be corrected immediately. provide a written report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or contact the housing inspector (within 30 days) to witness lowering the ladder in person. test and verify that all windows or doors leading to emergency fire escape are operational and unobstructed. advise occupants not to block the path of emergency exits on the inside. **reminder** all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeDec 7, 2004
interior surfaces section · paint ceilings (1001b,1301 hc)
after repairs are done, including manager's unit.
not activeDec 7, 2004
building section · this notice includes violations for the areas noted.
811 geary street.
not activeDec 7, 2004
interior surfaces section · other interior violations
repair #304's gap at bathroom door frame. repair #308's bathroom door to latch.
not activeDec 7, 2004
security requirements section · provide deadlatch locks with min 1/2" throw at exit doors (706 hc)
doors to fire escapes. all means of egress doors, including security gates, must be equipped with an approved manual release mechanism that shall be operable from the inside without the use of a key, tool or any special knowledge or effort
not activeDec 7, 2004
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
#204, #609, and where required.
not activeDec 7, 2004
fire section · remove egress obstruction at (801,1001(l) hc)
**tripping hazard** remove all stored items and planters from fire escape. this area must remain clear and clean at all times.
not activeDec 7, 2004
interior surfaces section · repair damaged walls (1001b,h,o hc)
#509, #607, #609, #404's at tub junction. and where required.
not activeDec 7, 2004
building section · repair window latches or hardware (1001(b)hc)
#209's bedroom, and where required.
not activeDec 7, 2004
building section · repair window glazing (1001(h),(j),& 708 hc)
#510"s bedroom; #208's bedroom and bathroom, and where required.
not activeDec 7, 2004
sanitation section · pigeon proof premises (1001b, 1306 hc)
and clean pigeon droppings.
not activeDec 7, 2004
smoke detection section · certify central alarm system (908, 909 hc)
restore system into its working condition. make sure that central alarm system is functional, backup battery is charged and certification is current & posted as required by the fire department.