not activeApr 18, 2005
interior surfaces section · repair damaged walls (1001b,h,o hc)
fill holes at bottom portion of walls in room 510.
not activeApr 18, 2005
interior surfaces section · repair damaged walls (1001b,h,o hc)
seal hole around sprinkler head in closet, room 510.
not activeApr 18, 2005
security requirements section · other security violations
tenant reports that doorknob is loose and screw is missing; check doorknob and replace screw as necessary, room 510.
not activeJul 22, 2004
building section · paint walls and ceiling surfaces of the public bathrooms/tub rooms on each floor.1301hc.
public bathrooms in need to be painted.
not activeJul 22, 2004
building section · 1)provide adequate ventilation to all tub rooms. 2)install mechanical ventilation devices capable to exchange 5 air changes per hour,to each public bathroom.504hc.
lack of requiered ventilation to public bathrooms.
not activeJul 22, 2004
building section · 1)remove lint,clean and sanitize areas around ,under,behind laundry machines. 2)remove lint from overhead pipes in the basement/laundry room areas. 3)discard excessive storage,clean and sanitize laundry room area.1306hc.
laundry room,storage areas in need to be cleaned.
not activeAug 8, 2003
building section · use of any form of cooking equipment in guestrooms are prohibited.
discontinue use of cooking equipment in gr#414,constituting a potential fire hazard,overloading electrical circuits. sec 709hc.
not activeAug 8, 2003
building section · inoperative ,disconnected hard wire smoke detector.
replace or repair inoperative smoke detector unit.908hc.
not activeAug 8, 2003
building section · leaking hot water faucet.
repair leaking hot water faucet in hand wash basing gr#414.1001hc.
not activeAug 8, 2003
building section · flaking paint along wall surfaces above bed area.
replaster and paint damaged wall surfaces in gr#414.1301hc.
not activeAug 8, 2003
building section · carpeting is filled with burnt marks.
replace burnt,soiled carpeting in gr#414.1306hc.
not activeApr 25, 2003
building section · damaged,peeling paint throughout gr#517
1) remove,properly contain peeling paint and plaster from walls and ceiling surfaces in gr#517.1001hc./1301hc. 2)paint premises throughout.1301hc.
not activeApr 25, 2003
building section · overhead leaks causing ceiling damage in bathroom area above shower head.
1)asses cause and repair overhead leaks causing ceiling damage in bathroom of gr#517.1001hc. 2)replaster and paint affected bathroom ceiling surfaces.1301hc.
not activeApr 25, 2003
building section · rodent infestation of the premises.
1)intensify peast and rodent control to the premises. 2)plug up all wall/floor openings,rodent prroof gr#517.1001hc.
not activeApr 25, 2003
building section · dirty ,insanitary carpeting.
clean,shampoo or replace carpeting in gr#517.1306hc.
not activeSep 21, 2001
other section · pigeon feeding.
discontinue harboring,feeding pigeons constituting a nusinace,being a potential breeding ground for roaches and vermin.1306hc.
not activeApr 24, 2001
building section · mildewed shower room ceiling
1)remove mold and mildew from all shower room ceilings.1306hc. 2)replastrer and paint damaged public bathroom walls and ceiling surfaces on all floors.1301hc.
not activeApr 24, 2001
building section · lack of a shower handle to 3rd floor bathroom
install handle to 3rd floor shower room.1001hc.
not activeApr 24, 2001
building section · broken toilet tank cover on 5th floor .
replace cracked 5th floor tank cover in public bathroom across #526.1001hc.
not activeApr 24, 2001
building section · damaged ,corroded ceiling light in the shower rooms,exposed lights in the tub rooms.
1)replace all corroded ceiling lights in the shower rooms.1001hc./504hc. 2)provide a cover over exposed ceiling lights in the tub rooms.1001hc.
not activeApr 24, 2001
building section · rusty sink
1)resurface chiped,worn sink in the 6th floor tub room. 2)remove rust from sink in 4th floor tub room.1301hc. 3)resurface chiped,rusty tub in 3rd floor tub room.1001hc.
not activeMar 16, 2001
building section · lack of fire hose handle on 5th floor.
replace missing 5th floor fire hose handle.1001hc./908hc.
not activeMar 16, 2001
building section · accumulation of lint behind washing machine.
remove lint from behind washing machine,clean trap.1001hc.
not activeJul 18, 2000
building section · roach and vermin infestation in #416.
provide drastic pest control measures until roach and vermin infestation is under control.1001hc.
not activeJul 18, 2000
building section · walls and ceiling surfaces are in need to be painted.
replaster and paint walls and ceiling surfaces in gr #416.1301hc.
not activeJul 18, 2000
building section · stoped up sink
unstop hand wash basin in #416.1001hc
not activeJul 18, 2000
building section · heavily mildewed public tub and shower room walls and ceiling surfaces.
remove layers of mildew from walls and ceiling surfaces of each and every public tub and shower room in building. 1306hc.
not activeJul 18, 2000
building section · broken and worn toilet seats
replace all toilet seats in each and every bathroom. 1001hc.
not activeJul 18, 2000
building section · leaking faucets in sinks and tubs
repair and/or replace handles as required to prevent leaking faucets in each and every bathroom.1001hc.
not activeJul 18, 2000
building section · rusty sinks and tubs
remove rust and resurface chipped enamel in all sinks and tubs at each and every bathroom. 1001hc.
not activeJul 18, 2000
building section · dirty and missing louvered window panels
tub rooms 603, 503, 403, 303, 203: 1. provide and install missing louvers in windows.1001hc 2. clean and sanitzie all louvered windows.
not activeJul 18, 2000
building section · seriously water damaged ceiling in tub room across from gr #503.
tub room across from #503: 1. locate source of water leak in ceiling. repair as required. 1001hc. 2. replace water damaged ceiling with 5/8": type x waterproof gyp bd. 3. repair and replaster wall behind showerhead.
not activeJul 18, 2000
building section · soiled, insanitary carpeting in gr #416.
replace soiled insanitary carpeting in gr#416.1306hc.
not activeJul 18, 2000
building section · soiled,ripped,insanitary mattress.
replace warn,soiled mattress in #416.1308hc.
not activeJul 18, 2000
building section · heavily stained,insanitary curtains.
replace soiled,insanitary curtains in #416.1306hc.
not activeJul 18, 2000
building section · water damaged floor surfaces under hand wash basin.
repair/replace water damaged floor surfaces under the hand wash basin in #416.1001hc.
not activeJul 18, 2000
building section · dirty and worn floors.
clean, sanitize, and repaint floors in each and every public tub, shower, and toilet room in building. 1306hc.
not activeJul 18, 2000
building section · walls and ceiling surfaces are in need of repair and paint.
1)replaster and paint public bathroom walls and ceiling surfaces. 2)replace all water damaged sheetrock with \5/8 of an inch sheetrock type x.1001hc./1301hc.
not activeApr 21, 2000
other section · comply with the record maintenance, availability and posting requirements of chapter 41 of the san francisco administrative code (hco).
note that rent receipts must clearly designate the following information for every guest room rental payment. 1. the date the rent receipt is issued. 2. the guest room number, and rental amount paid for. 3. the duration of time paid for. 4. the name of the occupant or person/agency who made the rental payment. 5.the name of the person who issued the rent receipt.
not activeApr 21, 2000
other section · comply with the record maintenance, availability and posting requirements of chapter 41 of the san francisco administrative code (hco).
the following violations of the hco were found as a result of an on-site inspection by inspector sarkany on april 26, 2000 and an examination, and subsequent review by inspector bosque, of the hco records submitted to the offices of the department of building inspection (dbi) on june 1, 2000 for the residential hotel known as the shawmut hotel located at 516 o'farrell street. the following violations are to be corrected immediately: 1. the weekly reports were not posted, or available at the time of the on-site inspection of april 26, 2000 and only one weekly report was available for review during the examination on june 1, 2000. the hotel owner/operator has failed to post and maintain weekly reports for a period of not less than 2 years. these actions & practices violate sections 41.9(b) and 41.11(c) of the hco. 2. all the required daily logs were not available at the time of the on-site inspection on april 26, 2000. the examination on june 1, 2000 revealed that daily logs had not been properly maintained to contain the requisite information on a daily basis for a period of not less than 2 years: (a) whether all guest rooms were being used for residential use, tourist use or vacant, and (b) the name of the registered occupants. these actions and practices violate sections 41.9(a), 41.9(b) and 41.11(c) of the hco. 3. the rent receipts were not properly maintained for all transactions (for a period of not less than 2 years) in violation of sections 41.9(a), 41.9(b) and 41.11(c) of the hco. the sample rent receipt submitted for review on june 1 ,2000 did not contain the requisite information. the hotel owner/operator is instructed to submit hco records (daily logs, weekly reports & rental receipts) for the period of june 1, 2000 through august 8, 2000 to inspector bosque at the dbi offices (1660 mission street, 6th floor) on august 9, 2000 at 11:00 a.m. please contact inspector bosque at (415) 558-6202 if you have questions regarding this notice.
not activeFeb 28, 2000
building section · insanitary premises.
remove piles of accumulations of flamables,bags,debries,paper,personal belongings from #319, constituting a fire,health hazard.1306hc. clean and sanitize premises throughout.1306hc.
not activeDec 8, 1999
sanitation section · remove rubbish or trash at garbage area (1304,1306,1001b hc)
discontinue use of the room adjacent to the sixth floor garbage room as a secondary garbage room. this smaller room is neither fire rated nor vented and is therefore unsuitable as a garbage storage area.
not activeDec 8, 1999
building section · replace broken glass window pane (1001(h),708 hc)
replace the broken glass pane of the 3rd floor fire escape access window.
not activeFeb 11, 1999
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
404 (vent)
not activeFeb 11, 1999
plumbing and electrical section · repair sink (1001f hc)
308
not activeFeb 11, 1999
plumbing and electrical section · repair toilet (1001f hc)
625 & 404
not activeFeb 11, 1999
interior surfaces section · repair floor covering (1001b,j,o hc)
526, 404 (bathrm.)
not activeFeb 11, 1999
interior surfaces section · paint ceilings (1001b,1301 hc)
& repair any damage to 606,602 & 525
not activeFeb 11, 1999
interior surfaces section · paint walls (1001b,1301 hc)
not activeFeb 11, 1999
other section · miscellaneous violations
reattach shower rod