not activeJun 14, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJun 13, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJun 13, 2007
interior surfaces section · paint ceilings (1001b,1301 hc)
paint the repaired surfaces.
not activeJun 13, 2007
interior surfaces section · repair damaged ceilings (1001b,h hc)
repair the water damaged ceilings in the following locations of the commercial space at 585 post st.: 1)main showroom floor. 2)office on the second floor. ****there are mushroom like fungal growths protruding through the water damaged ceiling in the office. these damaged surfaces must be opened for inspection and repair. call the housing inspector to arrange a site inspection before these areas are closed up.
not activeJun 13, 2007
interior surfaces section · repair source of water damage (703,1001f hc)
there is water damage to the ceilings of the commercial space at 585 post. have a licensed plumber locate and repair the source of the water damage from the residential hotel above. provide a copy of the plumbers invoice or finaled job card at the time of reinspection.
not activeMar 2, 2007
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
recharge and retag all out of date fire extinguishers.
not activeMar 2, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 22, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 22, 2007
smoke detection section · repair central alarm system (908, 909 hc)
provide new annual certification for the alarm system panel.
not activeApr 5, 2006
other section · it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 5, 2006
interior surfaces section · repair damaged walls & ceilings (1001b,h hc)
on the taylor st. side repair the damaged wall and ceiling surfaces at: -wall surfaces of the upper floors at the rear stairwell, -corridor at 2nd & 3rd floors.
not activeApr 5, 2006
interior surfaces section · replace light fixtures (1001b 10 hc)
the light fixtures for the fire escape corridors on the taylor st. side are missing. replace the missing fixtures and bulbs.
not activeMar 6, 2006
other section · it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMar 6, 2006
fire section · install directional signs at (801, 1001(m) hc)
on all floors install emergency directional signs leading towards the fire escapes.
not activeMar 6, 2006
interior surfaces section · locate source of water damage (703, 1001f hc)
locate and repair the source of water damage to the 4th floor corridor ceiling.
not activeMar 6, 2006
interior surfaces section · paint ceilings (1001b,1301 hc)
paint the repaired 4th floor corridor ceiling.
not activeMar 6, 2006
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
the ceiling of the 4th floor corridor leading to the rear fire escape shows evidence of water damage. repair the damage.
not activeNov 22, 2005
building section · replace soiled ,worn carpeting in gr#407.1306hc.
not activeNov 22, 2005
building section · 1)provide systematic ,routine licensed pest control measures until bed bug infestation is under control in gr#407.1001hc. 2)seal all open cracks and crevices,in order to prevent harborage of bed bugs.1001hc.
bed bug infestation in gr#407.
not activeNov 22, 2005
building section · replaster and paint walls and ceiling surfaces in gr#407.1301hc.
not activeNov 22, 2005
building section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeNov 27, 2001
building section · presence of mildew on guestroom walls in gr#509.
1)locate source of water seepage,causing mold and mildew to grow on the guestroom walls. 2)eliminate mold and mildew with a strong hypochloric sollution. 3)spot paint affected areas. 4)eliminate potted plants causing excessive moistured in the guestroom,constituting a fertile environment for fungy and mold to grow.1001hc./1306hc./1301hc.
not activeAug 30, 2000
other section · lack of heat in #319.
provide 68 degrees f.for 13 hours to #319 from 6:00 am-11:00 am 3:00 pm-10:00 pm.
not activeJul 6, 2000
building section · water damaged tub enclosure
replace /paint water damaged tub enclosure at 4th floor tub room across from #405.1001hc.
not activeJul 6, 2000
building section · missing louver windows in shower rooms.
replace missing louver windows in shower rooms on all floors.1001hc.
not activeJul 6, 2000
building section · overhead leak from 5th floor shower into 4th floor shower.
1)repair plumbing leaks from 5th floor shower room causing ceiling damage to 4th floor shower room ceiling.1001hc. 2)replaster and paint water damaged bathroom ceiling surfaces.1001hc./1301hc.
not activeJul 6, 2000
building section · insanitary,deteriorated conditions in gr#314
1)replaster and paint walls and ceiling surfaces in #314.1001hc./1301hc. 2)replace insanitary,warn carpeting.1306hc. 3)replace missing smoke detector.908hc. 4)clean and sanitize premises throughout.1306hc.
not activeJul 6, 2000
building section · inoperative boiler(repeated violations)
1)repair inoperative boiler.(48 hours notice.) 2)restore/provide 68 degrees f. to each habitable room for 13 hgours.701hc. 3)replace malfunctioning,stripped shut of valve/handle to radiator unit in gr#319.1001hc. 4)ballance radiator unit to assure proper operation.1001hc. note: due to repeated heat violations a citation will be issued unless the boiler operation will be restored and maintained.
not activeJul 6, 2000
building section · mildewed /warn tub room walls and ceiling surfaces.
1) remove layers of mildew,paint tub room walls and ceiling surfaces on all floors.1306hc/1301hc.
not activeJul 6, 2000
building section · floor wall junction/tub wall juction in need to be caulked.
replace old mildewed caulk from floor wall junction of each shower room and tub wall junction in tub rooms.1001hc.
not activeJun 8, 2000
building section · inoperative boiler
1)repair inoperative boiler.701hc. 2)provide 68 degrees f. to each an every habitable room.701hc.
not activeJun 8, 2000
building section · inoperative central panel smoke detector/fire alarm
repair/replace central panel smoke detector/fire alarm system.1001hc.908hc.
not activeNov 9, 1999
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
provide pest control measures until insect infestation is under control.1001hc.
not activeNov 9, 1999
sanitation section · remove rubbish or trash at garbage area (1304,1306,1001b hc)
1)remove debries,rubbish,piles ,bags from the premises. 2)clean and sanitize both sleepingroom as well as the bathroom throughout. 3)wash down insanitary walls and ceiling surfaces, clean and shampoo carpting.1306hc.
not activeNov 9, 1999
plumbing and electrical section · repair lightswitch (1001e hc)
replace exposed wall switch in the bathroom,constituting an electrical hazard .1001hc.
not activeSep 21, 1998
interior surfaces section · repair damaged walls (1001b,h,o hc)
repair the damaged walls in the tub rooms by rooms #314, #414 and #514, there is damaged paint and plaster particularly by the faucet.
not activeSep 21, 1998
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
fire extinguishers were last serviced on 06/15/1997.
not activeSep 21, 1998
other section · miscellaneous violations
repair the broken glass at the fire extinguisher box by room #401.
not activeSep 21, 1998
security requirements section · provide self-closing devices at exterior doors (706 hc)
repair /replace the self closing device at the roof door.
not activeSep 21, 1998
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeSep 21, 1998
building section · replace window sash cord (1001(h),708 hc)
replace the sash cords at the toilet room window opposite room #225.
not activeSep 21, 1998
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair the damaged ceilings in the shower room opposite #202, in the toilet room opposite room #212, in the shower room opposite #302 and in the tub room by #314.
not activeDec 2, 1997
interior surfaces section · eliminate mold/mildew on ceiling (1301,1001b(13),1306 hc)
eliminate the mold and mildew from the ceiling of the tub room opposite #405.
not activeDec 2, 1997
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeDec 2, 1997
interior surfaces section · repair damaged walls (1001b,h,o hc)
repair the cracked, peeling paint at the secondary stairway between the 5th and 3rd floor landings and at the main stairway between the 4th and 3rd floor landing.
not activeDec 2, 1997
other section · repair non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not. (701c hc)
the thermostat must be made non tamperable, a locking cover must be provided.
not activeDec 2, 1997
security requirements section · provide self-closing devices at exterior doors (706 hc)
provide a self closing device at the exit door by #217.
not activeDec 2, 1997
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
the timeclock was set from 5:00am to 9:00am and from 5:00pm to 9:00pm at the time of inspection.
not activeMay 22, 1997
interior surfaces section · repair damaged walls (1001b,h,o hc)
at 2nd, 3rd floor bathrooms.