not activeMay 30, 2014
interior surfaces section · reinstall the weatherstripping 1212 a2 sfhc
re-install or replace the weatherstripping on the doors of units 310, 311, 312, 313, 314 and 315. the weather stripping is to be installed so that the vinyl compression strip is squeezed by the surface of the door to insure an effective seal that reliably limits air infiltration. sweeps at the bottom of the door should be similarly effective.
not activeMay 30, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMay 30, 2014
interior surfaces section · repair damaged ceilings 1001b, d, h, o sfhc
in unit 615 repair the damaged ceilings in the closet and the bedroom.
not activeMay 30, 2014
interior surfaces section · repair source of water damage 703, 1001f sfhc
in unit 615 the ceiling is damaged in the bedroom area and the closet. find and fix the source of water damage.
not activeMay 30, 2014
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless otherwise noted all violations were observed on the date of inspection at 1000 sutter street, units 310. 615.
not activeNov 4, 2013
interior surfaces section · repair damaged walls (1001b,h,o hc)
all walls areas involved in the bathroom of unit 524 shall be cleaned, sanitized from the residue evident from faulty piping. after being properly prepared in an approved manner these walls shall be dry-walled if necessary, taped, sanded, primed and painted to a smooth, durable and cleanable surface. caulk and seal all interior corners to provide a smooth and cleanable surface. any gaps exceeding 1/8" shall be filled or covered with solid material. all new or treated wood or drywall surfaces shall be painted.
not activeNov 4, 2013
other section · inspector comments
it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice. all open notices of violation will be re-inspected at this time.
not activeNov 4, 2013
interior surfaces section · repair source of water damage (703,1001f hc)
in addition to any plumbing work necessary in the unit above; all wall, floor and ceiling areas impacted by the repair shall be handled in a similar fashion to the directions which follow.
not activeNov 4, 2013
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
all ceiling areas involved in the bathroom of unit 524 shall be cleaned, sanitized from the residue evident from faulty piping. after being properly prepared in an approved manner these walls shall be dry-walled if necessary, taped, sanded, primed and painted to a smooth, durable and cleanable surface. caulk and seal all interior corners to provide a smooth and cleanable surface. any gaps exceeding 1/8" shall be filled or covered with solid material. all new or treated wood or drywall surfaces shall be painted.
not activeNov 4, 2013
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless otherwise noted all violations occur at 1000 sutter street, unit 524.
not activeNov 4, 2013
plumbing and electrical section · make necessary repairs to plumbing (1001f hc)
wall stains and delapidation indicate a plumbing problem in the unit or ceiling assembly above. find the source of the leak and repair.
not activeAug 23, 2012
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
in room #121
not activeAug 23, 2012
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 28-september-2012 at 2:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeAug 23, 2012
building section · this notice includes violations for the areas noted.
1000 sutter street room# 121
not activeMar 5, 2012
building section · repair window latches or hardware (1001(b)hc)
install missing window latch on window going out onto the lighwell area.
not activeMar 5, 2012
interior surfaces section · eliminate rodent infestation (1001b, 1306 hc)
provide pest control to eliminate possible rodent infestation.
not activeMar 5, 2012
building section · this notice includes violations for the areas noted.
items in unit #123.
not activeMar 5, 2012
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
remove peeling paint from inside of the tub and inspect drainage to be sure that tub is draining properly.
not activeMar 5, 2012
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 5, 2012
interior surfaces section · clean interior (1306 hc)
clean soiled stained floor in bathroom.
not activeMar 5, 2012
interior surfaces section · paint walls (1001b,1301 hc)
paint stained walls in units adjacent to bathroom.
not activeMar 10, 2011
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on monday, 11-march-2011 at 2:30 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeMar 10, 2011
other section · repair defective or non-working elevator (1001(l), 713 hc)
repair freight elevator.
not activeMar 10, 2011
building section · this notice includes violations for the areas noted.
all common areas of 1000 sutter street.
not activeJul 28, 2008
other section · move non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not. (701c hc)
move the heat thermostat from the common dining room to a centrally located guest room.
not activeJul 28, 2008
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJul 22, 2008
building section · this notice includes violations for the areas noted.
1000 sutter street room # 921
not activeJul 22, 2008
building section · repair window frame locking hardware (1001(h),708 hc)
all windows in room # 921 need to lock.
not activeJul 22, 2008
plumbing and electrical section · other plumbing and/or electrical violations
tack down all loose wiring.
not activeJul 22, 2008
interior surfaces section · clean stains in carpet.
not activeJul 22, 2008
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on monday, 25-august-2008 at 2:30 pm. reinspection of premise to include all areas referenced above. it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeJul 22, 2008
security requirements section · hollow core or panel entry doors on the following units must be replaced with solid core doors or reinforced with min. 3/8" plywood or approved equal or repaired (706 hc)
room# 921.
not activeMar 11, 2008
building section · remove,contain and properly dispose of peeling paint and plaster from
1) wall surfaces at side of guestroom window in gr#316. 2) install a containment barrier. 3) replaster, prime and paint flaking portions of wall surfaces side of guestroom window in unit # 816. sec. 1001hc./1301hc.
not activeNov 1, 2007
building section · hire the services of a qualified plumbing contractor in order to:
repair/replace leaking portion of the drain pipe serving the air conditioning unit, discharging at base of the lightwell. sec. 1001hc.
not activeJun 11, 2007
building section · building & roofing permit required (301 hc)
not activeJun 11, 2007
building section · repair roof deck (1001(b)(13) hc)
repair the fire damaged hole in the roof, approx. 4'x5', over the boiler room. roofing and building permit required.
not activeJun 11, 2007
fire section · repair fire proofing with approved materials (hc 1001(m), 809)
repair the fire damaged ceiling and wall surfaces in the boiler room. permit required.
not activeJun 11, 2007
fire section · permit required.
permit required for the repair of the fire resistive surfaces.
not activeJun 11, 2007
plumbing and electrical section · provide plumbing permit (103.1.1 pc)
plumbing permit required for plumbing work.
not activeJun 11, 2007
plumbing and electrical section · repair drainage pipes at exterior (1001f hc)
reconnect the roof drain and plumbing lines damaged during the roof fire over the boiler room. plumbing pwermit required for this work.
not activeJun 11, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJan 8, 2007
building section · side dining room door opening into sutter street is not tight fitting in need of adjustment.
1)repair adjust fire door and hardware,in the dining room area. 2)make door tight fitting, in order to assure proper security.
not activeNov 10, 2006
building section · 1)remove, contain and properly dispose of peeling paint and plaster along lobby ceiling surfaces adjacent to mid ceiling light.1001hc. 2)replaster and paint damaged portion of ceiling surfaces.1001hc./1301hc.
peeling paint and plaster along lobby ceiling surfaces.
not activeNov 10, 2006
building section · repair defective,leaking roof surfaces.
damaged roof causing celing leaks in the lobby area.