not activeJan 13, 2016
building section · lead warning (continued)
information packets are available at the housing division of the san francisco department of building inspection, 1660 mission street at the 6th floor counter. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by that dust. ordinance #446-97.
not activeJan 13, 2016
plumbing and electrical section · repair lightswitch 1001e sfhc
the light switch to this unit emits an audible crackle when switched. repair or replace the light switch.
not activeJan 13, 2016
building section · paint the window 1301 sfhc
once repairs on this window are complete prep, prime and paint to complete the repair.
not activeJan 13, 2016
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. 303 sfhc if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeJan 13, 2016
building section · lead warning
disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal: follow the approved methods of the epa rrp or other similar lead abatement training. this structure was constructed prior to 1979 and therefore presumed to contain lead. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3426, sfbc)
not activeJan 13, 2016
building section · repair window sash frame 1001d, h, 708 sfhc
the window in this unit is showing signs of rot and deterioration. the paint is severly peeling. repair or replace the window sash frames to eliminate any rot and insure that glass panels are secured appropriately with glazer's putty or other approved method providing a weather proof condition. ensure that the sash and frame provide smooth and easy operation and a weather tight condition with a working latch. window is to remain open at any desired position with the balance of a counter weight.
not activeJan 13, 2016
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 1040 bush street, unit 217.
not activeJan 13, 2016
building section · repair door and frame 1001d, b13 sfhc
the guest room entry door is hanging from the top hinge and does not self close as intended. the screws in the top hinge are tearing out from the door and jamb. doors and jambs shall be tight fitting, in good condition, self-closing and self-latching. conduct repair to meet these requirements.
not activeMar 12, 2014
building section · this notice includes violations for the areas noted.
these violations are in the bathrooms in the common areas of the building.
not activeMar 12, 2014
building section · install grab bars in all common area water closets, lavatories and bathing facilities to comply with ordinance 029-13 (301, 505(j), 1002(g) hc).
building permit is required.
not activeMar 12, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner can not attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 6, 2012
building section · repair window sash cords (1001(h) hc)
repair the numerous broken sash cords in the bathrooms of every floor.
not activeApr 6, 2012
other section · due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed.
not activeAug 7, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeAug 7, 2007
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
replace the missing shower head and seat in the handicap shower on the 3rd floor.
not activeMay 15, 2006
smoke detection section · central alarm system (909 hc)
provide certification: reminder central alarm panel are required to be cerifed annually by a licenced contractor and post ceritification on the panel door (sec 908,909,(b) s.f.h.c.
not activeMay 15, 2006
building section · this notice includes violations for the areas noted.
1040 bush st. *heat sweep inspection *routine inspection of the (common area) building sec.(303 a s.f.h.c.)
not activeMay 15, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as schedule on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with the inspector, and provide all tenants with notification as required by california civil code section 1954(san francisco housing code section 303(b),if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMay 15, 2006
other section · heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
heat sweep inspection: a random room inspection was performed (tenants were present at the time of initial inspection) guest rooms are provided with steam heater (radiator) boiler is located on the ground fl. adjacent to the residential kitchen
not activeMay 15, 2006
fire section · remove egress obstruction at (801,1001(l) hc)
all storage from the ground level exterior side passageway to the street, (this area must remain clear and clean at all times.)
not activeMay 15, 2006
fire section · maintain fire escape drop ladder in working condition (sec 908 hc)
note: property manager, owner or the owner's agent needs to provide a proof of the workability of the fire escape ladders. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written report from a qualified service company or licenced contractor stating that all parts and cables have tested and are functional or contact the housing inspector (within 30 days) to witness lowering the ladder in person. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeMay 15, 2006
other section · provide non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not (701c hc)
relocate the existing thermostat (located in the office). upon reinspection: provide access to the new location of the thermostat. (habitable room) note: thermostat shall be installed at point of three feet above the floor.
not activeDec 13, 2002
building section · failure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02.
submit a building permit application with plans to the department of building inspection within 15 days of this notice to comply with the residential hotel sprinkler ordinance #170-02, section 904 s.f.h.c.
not activeMar 13, 2001
building section · construction material along rear passageway to street constituting an egress obstruction.
1)remove all construction materials from rear yard/passageway to street. empty construction materials from the wheel barrel on freequent basis.1306hc. 2)sweep up broken glass from rear yard. 3)install requiered lighting to rear passageway to street.504 hc. 4)keep all exit doors from basement,dining area open and unobstructed at all times.801hc./1001hc.
not activeMar 13, 2001
building section · inadequate lighting along interior stairs connecting 1st floor with cafeteria.
install additional lighting along interior stairs connecting 1st floor with cafeteria. 504hc./1001hc.
not activeMar 13, 2001
building section · lack of handrails along rear stairs connecting cafeteria with rear yard.
install two handrails to rear interior stairs.1001hc.
not activeMar 13, 2001
building section · untarped chute causing construction dust and debries to scatter on adjacent properties,cars,pedestrians.
install a tarp over chute used to discharge construction debries into debries box. at all times.1001hc.
not activeFeb 14, 2000
building section · defective roof.
replace damaged roof surfaces.1001hc.
not activeJan 20, 2000
building section · thermostat
replace/relocate non temperable thermostat/wiring from 1st to 2nd floor.701hc.
not activeFeb 24, 1999
interior surfaces section · repair damaged walls (1001b,h,o hc)
repair damaged walls(cracking and peeling)in the following rooms:106-115-117-122-124-229-234-200-223-220-331-336-337-317. also in the bath/shower room on the second floor:where areas are cracking, chipping and/or peeling in various locations.
not activeFeb 24, 1999
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair damaged ceilings(cracking and peeling) in the following rooms:100-114-116-117-124-229-232-206-211-212-220-336-307-300(bath)-311. also the areas in first floor bath/shower room, second floor bath/shower room and on the area above the third floor landing.
not activeFeb 24, 1999
building section · this notice includes violations for the areas noted.
1040 bush
not activeFeb 24, 1999
other section · provide shutoff tool for gas utility shutoff (712 hc)
in a visable area near the gas meters.
not activeFeb 24, 1999
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeFeb 24, 1999
other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
in a visable area near the gas meters.
not activeFeb 24, 1999
plumbing and electrical section · provide adequate lighting (504g hc)
provide adequate lighting for the ground floor terminal path from the rear fire escape to the street. permit is required.
not activeFeb 24, 1999
interior surfaces section · paint ceilings (1001b,1301 hc)
after all the areas are repaired, painting is required.
not activeFeb 24, 1999
interior surfaces section · paint walls (1001b,1301 hc)
after all the areas are repaired, painting is required.