stoop
MAP
LeaderboardAbout

998 BUSH ST

Nob Hill · San Francisco, CA · Parcel 0275006 · Last violation Nov 8, 2024 · Last complaint Apr 27, 2026

NeighborhoodNob Hill
Above-average violations for the neighborhood
More violations than 75% of buildings and more complaints than 89% of buildings in Nob Hill. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 3 violations · 23 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
All DBI violations have been resolved
Notices of Violation issued by the Department of Building Inspection, by current status.
Open fire-safety violations0
Open lead violations0
311 Housing Complaints
Total complaints since 2013
29
2 per year avg.↑ Up 1050% in the last 2 years (23 vs 2 prior 2 yrs)
Reported issues
23
Heatⓘ0
Leadⓘ0
Pestsⓘ4
Dept. of Building Inspection Violations
Total violations since 1999
143
5 per year avg.↓ Down 75% in the last 2 years (3 vs 12 prior 2 yrs)
Open violations
0
Fire safetyⓘ0
Leadⓘ0

Top violation categories

5 yrsAll time
other section48 violations
building section37 violations
fire section21 violations
interior surfaces section12 violations
plumbing and electrical section7 violations
security requirements section6 violations
smoke detection section4 violations
sanitation section4 violations
Unknown4 violations

Top complaint types

5 yrsAll time
Elevators Everthing Else15 complaints
Infestation Rodent Insect4 complaints
Elevators No Working Elevator 7 Or More Stories4 complaints
Clutter Hoarder Unit Interior Storage2 complaints
Illegal Construction No Permit Exceeds Permit Scope1 complaints
Light Wells Dirty Flooded1 complaints
Plumbing Broken Leaking1 complaints
Ventilation Inadequate Or None1 complaints
Hide violations (143) ↑See complaints (29) →

Violation log

143 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeJun 22, 2006fire sectionsmoke enclosure door closer (807,707 hc)the (2) boiler room doors must be self closing,flush to the door stop and latch without any outside assistance.
See something wrong? File a complaint with SF 311
not activeMay 17, 2006smoke detection sectioncentral alarm system (908, 909 hc)provide certification: reminder central alarm panel are required to be cerifed annually by a licenced contractor and post ceritification on the panel door (sec 908,909,(b) s.f.h.c. resecure to the wall, the 5th floor fire alarm pull station
not activeMay 17, 2006fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)expired 04/18/2006 all expired fire extinguisher in the building **reminder** all fire extinguishers are required to be recharged and serviced annually and date tag must be posted and current.
not activeMay 17, 2006plumbing and electrical sectionprovide adequate lighting (504g hc)repair public corridor ceiling light fixture on the 4th fl. light flickering(possible light bulb/loose wiring)adjacent to the gas meter closet. repair/replace recess ceiling light outside of #112 entry door
not activeMay 17, 2006other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as schedule on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with the inspector, and provide all tenants with notification as required by california civil code section 1954(san francisco housing code section 303(b),if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMay 17, 2006fire sectionother fire violationsinoperable emergency exit lights have the emergency exit tested annually and replace any inoperable lights /expired back-up batteries
not activeMay 17, 2006other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)upon reinspection: provide access to the building's boiler system. *boiler room *time clock *thermostat
not activeMay 17, 2006fire sectionother fire violationswhere required: provide garbage chute hopper doors hopper doors must be self closing,flush to the opening
not activeMay 17, 2006security requirements sectionprovide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)501
not activeMay 17, 2006building sectionthis notice includes violations for the areas noted.980 bush st. * heat sweep inspection * routine inspection of the (common area) building sec.(303 a s.f.h.c.)
not activeMay 17, 2006fire sectionmaintain fire escape drop ladder in working condition (sec 908 hc)note: property manager, owner or the owner's agent needs to provide a proof of the workability of the fire escape ladders. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written report from a qualified service company or licenced contractor stating that all parts and cables have tested and are functional or contact the housing inspector (within 30 days) to witness lowering the ladder in person. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeFeb 28, 2006other sectioninspector commentsat the time of inspection it was reported that homeless people enter the building and sleep on the lobby furniture. the buildings entry doors, etc. were secure at the time of inspection. it's the complaintents belief that tenants are lax about security while entering and exiting. please review your security policies in this regard.
not activeFeb 28, 2006interior surfaces sectionclean interior (1306 hc)the tan colored couch in the main lobby is stained with what appears to be blood. the stain is on the side closest to the front entry door. remove the stain and clean the sofa as needed.
not activeFeb 28, 2006security requirements sectionhollow core or panel entry doors on the following units must be replaced with solid core doors or reinforced with min. 3/8" plywood or approved equal (706 hc)the door to unit #414 has holes in its face and is a hollow core door with a 1/4" panel veneer. replace or repair the door to eliminate the holes and reinforce the door to at least minimum standards.
not activeFeb 28, 2006other sectionit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.—
not activeFeb 13, 2006other sectionit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.—
not activeFeb 13, 2006smoke detection sectionprovide smoke detector at stairs (911 hc)the penthouse stairway is lacking a smoke alarm. install a battery operated or hard wired smoke alarm.
not activeFeb 13, 2006fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)the service tag for fire extinguisher near #304 is out of date. recharge and retag this and all fire extinguishers not serviced within the last 12 months.
not activeNov 19, 2002building sectioninoperative boiler system.1)repair/restore inoperative boiler. 2)provide 68 degrees f. for 13 hours from: 5:00 am-11:00 am 3:00 pm-10:00 pm to each habitable room.701hc.
not activeMay 24, 2002building sectionpiles of lumber and bricks are falling off the roof causing a potential hazardous condition.remove all construction debries,brikc,lumber from roof surfaces.1001hc.
not activeFeb 12, 2002building sectionspalding stucco along east courtyard wall of 980 bush st, littering 972 bush's st. side passageway.remove all lo0se stucco,restucco east courtyard wall of 980 bush st.1001hc.
not activeFeb 12, 2002building sectioncracked se corner of n wing masonary wall,constituting a potential hazard.1)have north wing masonary wall inspected by a structural engineer. 2)repair/replace cracked portion of south east corner of north masonary wall by a licensed contractor.1001hc.
not activeFeb 12, 2001———
not activeDec 27, 2000other sectionprovide shutoff tool for gas utility shutoff (712 hc)—
not activeDec 27, 2000sanitation sectionaddendum 1/30/01: provide adequate lighting (504g hc)in corridor to fire escape windows: provide adequate lighting where exposed electrical wires are dangling from ceiling at each floor.
not activeDec 27, 2000other sectionpost enclosed gas meter instructional diagram in a public area. (712 hc)—
not activeDec 27, 2000sanitation sectionaddendum 1/30/01: remove rubbish or trash (1306,1307 hc)at courtyard: remove rubbish & trash creating a rat harborage. this trash constitutes a health, safety, &/or fire hazard (1001(k) hc)
not activeDec 27, 2000other sectioninspector commentspossible hco violation: see handwritten nav issued on 12/27/00 & hand delivered to george kehn, resident manager.
not activeDec 27, 2000building sectionthis notice includes violations for the areas noted.public areas of 980 bush: 63 dwelling units & 10 guest rooms in a 6-story bldg w/ 5 flrs of occupancy over a basement.
not activeDec 27, 2000fire sectionaddendum 1/30/01: install directional signs at (801, 1001(m) hc)over windows to fire escape at south side of building on each floor.
not activeDec 27, 2000other sectionmiscellaneous violationsrepair corroded leaking boiler as required.
not activeDec 27, 2000building sectionrepair weather proofing on siding (1001(h),703 hc)repair damaged weatherproofing at front entrance.
not activeDec 27, 2000other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)—
not activeDec 27, 2000fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)as required through-out building.
not activeNov 20, 2000building sectionstoped up drain lineunstop drain line.1001hc.
not activeNov 20, 2000building sectionaccumulation of contruction debries in the courtyard.remove piles of construction debries from the courtyard. 1306hc.
not activeSep 25, 2000building sectiondamaged ceiling in the basement area above storage lockers.repair all damaged portions of basement ceiling with 5/8 of an inch sheetrock type x.1001hc.
not activeSep 25, 2000building sectionconstruction,demolition debries scattered all around.1)remove all construction debries from rear yard.1001hc. 2)remove all lumber,construction materirals,flamables from boiler room.1001hc. 3)remove all stored items on top of storage lockers,obstructing sprinkle pathway.1001hc.
not activeSep 17, 1999other sectionset timeclock to provide the required amount and hours of heat. (701c hc)set timeclock for the hours specified above.
not activeSep 17, 1999fire sectionother fire violationsinstall door closer on roof door.
not activeSep 17, 1999other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)—
not activeSep 17, 1999plumbing and electrical sectionother plumbing and/or electrical violationsreplace damaged wiring for thermostat. install new wiring properly.
not activeSep 17, 1999fire sectionprovide date tag for fire extinguisher type 2a 10bc or equivalent (905, 1001(m) hc)provide clear covers for fire extinguisher boxes so that datetag and fire extinguishers can be seen.
not activeJun 22, 2006
fire section · smoke enclosure door closer (807,707 hc)
the (2) boiler room doors must be self closing,flush to the door stop and latch without any outside assistance.
not activeMay 17, 2006
smoke detection section · central alarm system (908, 909 hc)
provide certification: reminder central alarm panel are required to be cerifed annually by a licenced contractor and post ceritification on the panel door (sec 908,909,(b) s.f.h.c. resecure to the wall, the 5th floor fire alarm pull station
not activeMay 17, 2006
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
expired 04/18/2006 all expired fire extinguisher in the building **reminder** all fire extinguishers are required to be recharged and serviced annually and date tag must be posted and current.
not activeMay 17, 2006
plumbing and electrical section · provide adequate lighting (504g hc)
repair public corridor ceiling light fixture on the 4th fl. light flickering(possible light bulb/loose wiring)adjacent to the gas meter closet. repair/replace recess ceiling light outside of #112 entry door
not activeMay 17, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as schedule on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with the inspector, and provide all tenants with notification as required by california civil code section 1954(san francisco housing code section 303(b),if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMay 17, 2006
fire section · other fire violations
inoperable emergency exit lights have the emergency exit tested annually and replace any inoperable lights /expired back-up batteries
not activeMay 17, 2006
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
upon reinspection: provide access to the building's boiler system. *boiler room *time clock *thermostat
not activeMay 17, 2006
fire section · other fire violations
where required: provide garbage chute hopper doors hopper doors must be self closing,flush to the opening
not activeMay 17, 2006
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
501
not activeMay 17, 2006
building section · this notice includes violations for the areas noted.
980 bush st. * heat sweep inspection * routine inspection of the (common area) building sec.(303 a s.f.h.c.)
not activeMay 17, 2006
fire section · maintain fire escape drop ladder in working condition (sec 908 hc)
note: property manager, owner or the owner's agent needs to provide a proof of the workability of the fire escape ladders. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written report from a qualified service company or licenced contractor stating that all parts and cables have tested and are functional or contact the housing inspector (within 30 days) to witness lowering the ladder in person. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeFeb 28, 2006
other section · inspector comments
at the time of inspection it was reported that homeless people enter the building and sleep on the lobby furniture. the buildings entry doors, etc. were secure at the time of inspection. it's the complaintents belief that tenants are lax about security while entering and exiting. please review your security policies in this regard.
not activeFeb 28, 2006
interior surfaces section · clean interior (1306 hc)
the tan colored couch in the main lobby is stained with what appears to be blood. the stain is on the side closest to the front entry door. remove the stain and clean the sofa as needed.
not activeFeb 28, 2006
security requirements section · hollow core or panel entry doors on the following units must be replaced with solid core doors or reinforced with min. 3/8" plywood or approved equal (706 hc)
the door to unit #414 has holes in its face and is a hollow core door with a 1/4" panel veneer. replace or repair the door to eliminate the holes and reinforce the door to at least minimum standards.
not activeFeb 28, 2006
other section · it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 13, 2006
other section · it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 13, 2006
smoke detection section · provide smoke detector at stairs (911 hc)
the penthouse stairway is lacking a smoke alarm. install a battery operated or hard wired smoke alarm.
not activeFeb 13, 2006
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
the service tag for fire extinguisher near #304 is out of date. recharge and retag this and all fire extinguishers not serviced within the last 12 months.
not activeNov 19, 2002
building section · inoperative boiler system.
1)repair/restore inoperative boiler. 2)provide 68 degrees f. for 13 hours from: 5:00 am-11:00 am 3:00 pm-10:00 pm to each habitable room.701hc.
not activeMay 24, 2002
building section · piles of lumber and bricks are falling off the roof causing a potential hazardous condition.
remove all construction debries,brikc,lumber from roof surfaces.1001hc.
not activeFeb 12, 2002
building section · spalding stucco along east courtyard wall of 980 bush st, littering 972 bush's st. side passageway.
remove all lo0se stucco,restucco east courtyard wall of 980 bush st.1001hc.
not activeFeb 12, 2002
building section · cracked se corner of n wing masonary wall,constituting a potential hazard.
1)have north wing masonary wall inspected by a structural engineer. 2)repair/replace cracked portion of south east corner of north masonary wall by a licensed contractor.1001hc.
not activeFeb 12, 2001
—
not activeDec 27, 2000
other section · provide shutoff tool for gas utility shutoff (712 hc)
not activeDec 27, 2000
sanitation section · addendum 1/30/01: provide adequate lighting (504g hc)
in corridor to fire escape windows: provide adequate lighting where exposed electrical wires are dangling from ceiling at each floor.
not activeDec 27, 2000
other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
not activeDec 27, 2000
sanitation section · addendum 1/30/01: remove rubbish or trash (1306,1307 hc)
at courtyard: remove rubbish & trash creating a rat harborage. this trash constitutes a health, safety, &/or fire hazard (1001(k) hc)
not activeDec 27, 2000
other section · inspector comments
possible hco violation: see handwritten nav issued on 12/27/00 & hand delivered to george kehn, resident manager.
not activeDec 27, 2000
building section · this notice includes violations for the areas noted.
public areas of 980 bush: 63 dwelling units & 10 guest rooms in a 6-story bldg w/ 5 flrs of occupancy over a basement.
not activeDec 27, 2000
fire section · addendum 1/30/01: install directional signs at (801, 1001(m) hc)
over windows to fire escape at south side of building on each floor.
not activeDec 27, 2000
other section · miscellaneous violations
repair corroded leaking boiler as required.
not activeDec 27, 2000
building section · repair weather proofing on siding (1001(h),703 hc)
repair damaged weatherproofing at front entrance.
not activeDec 27, 2000
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
not activeDec 27, 2000
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
as required through-out building.
not activeNov 20, 2000
building section · stoped up drain line
unstop drain line.1001hc.
not activeNov 20, 2000
building section · accumulation of contruction debries in the courtyard.
remove piles of construction debries from the courtyard. 1306hc.
not activeSep 25, 2000
building section · damaged ceiling in the basement area above storage lockers.
repair all damaged portions of basement ceiling with 5/8 of an inch sheetrock type x.1001hc.
not activeSep 25, 2000
building section · construction,demolition debries scattered all around.
1)remove all construction debries from rear yard.1001hc. 2)remove all lumber,construction materirals,flamables from boiler room.1001hc. 3)remove all stored items on top of storage lockers,obstructing sprinkle pathway.1001hc.
not activeSep 17, 1999
other section · set timeclock to provide the required amount and hours of heat. (701c hc)
set timeclock for the hours specified above.
not activeSep 17, 1999
fire section · other fire violations
install door closer on roof door.
not activeSep 17, 1999
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
not activeSep 17, 1999
plumbing and electrical section · other plumbing and/or electrical violations
replace damaged wiring for thermostat. install new wiring properly.
not activeSep 17, 1999
fire section · provide date tag for fire extinguisher type 2a 10bc or equivalent (905, 1001(m) hc)
provide clear covers for fire extinguisher boxes so that datetag and fire extinguishers can be seen.
Page 3 of 3
← Prev