Class BClosed
Apr 20, 2021Apt 401
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE DOOR IN THE 4th ROOM FROM NORTH LOCATED AT APT 401, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Apr 20, 2021Apt 214
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT EAST & NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 214, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Apr 20, 2021Apt 312
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE GASKETS AT REFRIGERATOR DOORS IN THE KITCHEN LOCATED AT APT 312, 3rd STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Apr 20, 2021Apt 401
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BASE CABINET AT EAST WALL IN THE KITCHEN LOCATED AT APT 401, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Apr 20, 2021Apt 319
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 319, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST
Class BClosed
Apr 20, 2021Apt 217
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASHBASIN IN THE BATHROOM LOCATED AT APT 217, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BClosed
Mar 19, 2021Apt 315
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE HOLLOW CORE DOOR AT ENTRANCE IN THE BATHROOM LOCATED AT APT 315, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Feb 23, 2021Apt 614
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 5 SQUARE FEET AT THE CEILING IN THE BATHROOM LOCATED AT APT 614, 6th STORY, 4th APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH ORIGINAL VIOLATION 13864143 ISSUED 21-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 802
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 5 SQUARE FEET AT THE CEILING IN THE BATHROOM LOCATED AT APT 802, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH ORIGINAL VIOLATION 13863910 ISSUED 21-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 517
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CEILING, APPROXIMATELY 5 SQUARE FEET. IN THE BATHROOM LOCATED AT APT 517, 5th STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13866090 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 507
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CEILING, APPROXIMATELY 1 SQUARE FEET IN THE BATHROOM LOCATED AT APT 507, 5th STORY, 3rd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13866097 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 115
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AROUND BATHTUB WALLS APPROX 1 SQUARE FEET IN THE BATHROOM LOCATED AT APT 115, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13865199 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 113
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AROUND BATHTUB WALLS 1 SQUARE FEET IN THE BATHROOM LOCATED AT APT 113, 1st STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13865185 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 505
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING, APPROXIMATELY 3 SQUARE FEET. IN THE BATHROOM LOCATED AT APT 505, 5th STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13866100 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 217
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 2 SQUARE FEET AT CEILING IN THE BATHROOM LOCATED AT APT 217, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH ORIGINAL VIOLATION 13865648 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 519
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING, APPROXIMATELY 4 SQUARE FEET. IN THE BATHROOM LOCATED AT APT 519, 5th STORY, 3rd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13866088 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 718
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 5 SQUARE FEET AT THE SOUTH WALL AND CEILING IN THE BATHROOM LOCATED AT APT 718, 7th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH ORIGINAL VIOLATION 13863921 ISSUED 21-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 23, 2021Apt 607
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CEILING AND ALL WALLS, APPROXIMATELY 6 SQUARE FEET. IN THE BATHROOM LOCATED AT APT 607, 6th STORY, 3rd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 13865946 ISSUED 22-OCT-20 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BClosed
Feb 4, 2021Apt 1018
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CEILING APPROX 10 SQ FT IN THE BATHROOM LOCATED AT APT 1018, 10th STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BClosed
Feb 4, 2021Apt 1111
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CEILING APPROX 10 SQ FT IN THE BATHROOM LOCATED AT APT 1111, 11th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 4, 2021Apt 401
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 401, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Feb 4, 2021Apt 401
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 401, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Jan 26, 2021Apt 917
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 917, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Jan 25, 2021Apt 917
NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 917, 9th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Jan 25, 2021Apt 302
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 302, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH''
Class BClosed
Jan 5, 2021Apt 401
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 401, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Nov 27, 2020Apt 413
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERABLE LOCATED AT APT 413, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST
Class BClosed
Nov 27, 2020Apt 413
NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. LOCATED AT APT 413, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST
Class BClosed
Nov 23, 2020Apt 616
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). ''MISSING'' LOCATED AT APT 616, 6th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Nov 23, 2020Apt 616
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR ''DEFECTIVE'' LOCATED AT APT 616, 6th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 28, 2020Apt 214
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE EXTERIOR GLASS AT UPPER SASH IN THE 2nd ROOM FROM NORTH LOCATED AT APT 214, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 28, 2020Apt 214
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE BOTTOM WINDOW SASH IN THE 3rd ROOM FROM NORTH LOCATED AT APT 214, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 27, 2020Apt 209
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). ''MISSING'' LOCATED AT APT 209, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Oct 26, 2020Apt 711
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECIVE LOCATED AT APT 711, 7th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 804
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 804, 8th STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 716
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX. 10 SQUARE FEET AT THE CEILING IN THE BATHROOM LOCATED AT APT 716, 7th STORY, 6th APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosedRENT IMPAIRING
Oct 26, 2020Apt 716
REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN DRAIN PIPE AT THE BATHTUB IN THE BATHROOM LOCATED AT APT 716, 7th STORY, 6th APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 519
NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 519, 5th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Oct 26, 2020Apt 804
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 804, 8th STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 802
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WEST WALL IN THE PRIVATE HALLWAY LOCATED AT APT 802, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 802
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE NORTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 802, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 802
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST WALL IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 802, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 802
ABATE THE NUISANCE OF BEDBUGS · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF BEDBUGS IN THE ENTIRE APARTMENT LOCATED AT APT 802, 8th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 718
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE THE ENTRANCE DOOR IN THE BATHROOM LOCATED AT APT 718, 7th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 718
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST WALL IN THE PRIVATE HALLWAY LOCATED AT APT 718, 7th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 711
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 711, 7th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 709
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES ELECTRICAL OUTLET AT THE SOUTH WALL IN THE KITCHEN LOCATED AT APT 709, 7th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
Class BClosed
Oct 26, 2020Apt 615
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 615, 6th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 615
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 615, 6th STORY, 5th APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
Class BClosed
Oct 26, 2020Apt 302
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 18 SQUARE FEET AT CEILING IN THE BATHROOM LOCATED AT APT 302, 3rd STORY, 2nd APARTMENT FROM SOUTH AT WEST