Class BClosedRENT IMPAIRING
Nov 17, 2025
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING AT PUBLIC HALL, 6th STORY, SECTION AT EAST
Class BClosed
Nov 17, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 17, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING ADJACENT TO LAUNDRY ROOM ENTRANCE AT PUBLIC HALL, 1st STORY, SECTION AT EAST
Class BOpen
Nov 17, 2025Apt 5LL
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT ELECTRICAL OUTLET AT SOUTH WALL IN THE 5th ROOM FROM NORTH LOCATED AT APT 5LL, 4th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT EAST
Class BClosed
Nov 17, 2025Apt 7EE
REPAIR BROKEN, LOOSE CONNECTION · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REPAIR THE BROKEN OR DEFECTIVE CONNECTION AT WASTELINE AT SINK IN THE KITCHEN LOCATED AT APT 7EE, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT EAST
Class BOpen
Nov 17, 2025Apt 5LL
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE 5th ROOM FROM NORTH LOCATED AT APT 5LL, 4th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT EAST
Class BClosed
Nov 17, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 2nd STORY, SECTION AT EAST
Class BClosed
Nov 17, 2025Apt 5F
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 5F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 17, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 17, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND SOUTH WALL AT PUBLIC HALL, 1st STORY, SECTION AT EAST
Class BClosed
Nov 17, 2025Apt 3B
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 3B, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Nov 14, 2025Apt 5S
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 14, 2025Apt 5S
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 14, 2025Apt 5S
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT WEST WALL IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 14, 2025Apt 5S
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 14, 2025Apt 5S
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 14, 2025Apt 5S
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 14, 2025Apt 5S
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WEST WALL IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 13, 2025Apt 6B
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FEET AT NORTH WALL AND WINDOW RECESS IN THE BATHROOM LOCATED AT APT 6B, 5th STORY, 4th APARTMENT FROM NORTH AT EAST , SECTION AT WEST ORIGINAL VIOLATION 18097808 ISSUED 11-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Nov 13, 2025Apt 5E
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FEET AT WINDOW RECESS IN THE 1st BATHROOM FROM EAST LOCATED AT APT 5E, 4th STORY, 7th APARTMENT FROM NORTH AT EAST , SECTION AT WEST ORIGINAL VIOLATION 18097830 ISSUED 11-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Nov 13, 2025Apt 3N
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FEET AT WEST WALL IN THE BATHROOM LOCATED AT APT 3N, 3rd STORY, 7th APARTMENT FROM SOUTH AT WEST , SECTION AT WEST ORIGINAL VIOLATION 18099214 ISSUED 11-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Nov 10, 2025Apt 2F
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SINK IN THE KITCHEN LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 7, 2025Apt 5S
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRIC OUTLET AT WEST WALL IN THE BATHROOM LOCATED AT APT 5S, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''WEST''
Class BClosed
Nov 7, 2025Apt 5S
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 5S, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''WEST''
Class BClosed
Nov 7, 2025Apt 5S
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 5S, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''WEST''
Class BClosed
Nov 7, 2025Apt 5S
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''WEST''
Class BOpen
Nov 7, 2025Apt 3DD
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... NORTH WALL WITHIN CLOSET IN THE PRIVATE HALLWAY LOCATED AT APT 3DD, 2nd STORY, 6th APARTMENT FROM WEST AT NORTH , SECTION ''AA-MM'' ORIGINAL VIOLATION 18077442 ISSUED 09-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Nov 7, 2025Apt 5S
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''WEST''
Class BClosed
Nov 5, 2025Apt 6HH
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT INSIDE SINK CABINET BASE CABINET FROM NORTH AT EAST WALL IN THE KITCHEN LOCATED AT APT 6HH, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION AT EAST ORIGINAL VIOLATION 18066676 ISSUED 03-JUL-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Nov 3, 2025Apt 5S
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL GLAZE AT BATHTUB IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 5S
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING BOTTOM ESCUTCHEON PLATE AT RISER IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 5S
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 5S
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT NORTH WALL IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 5S
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 2H
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 2H
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 2H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 2H
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS AND CEILING AT NORTH 2 BATHROOM IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 2H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 5S
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL OUTLET COVER AT NORTH WALL IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025
REFIT DOORS ETC. · EGRESS
§ 27-2005 HMC: REFIT NORTH FIRE STAIR EXIT DOOR AT PUBLIC HALL (LABELED AS FLOOR 2) , 1st STORY, SECTION ''A-S''
Class BClosed
Nov 3, 2025
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT BUILDING ENTRANCE DOOR AT BASEMENT
Class BClosed
Nov 3, 2025Apt 2H
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS IN THE 1st BATHROOM FROM NORTH LOCATED AT APT 2H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 2H
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING AT NORTH 2 BATHROOM IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 2H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''A-S''
Class BClosed
Nov 3, 2025Apt 5S
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR ALL WALLS IN THE BATHROOM LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''A-S''
Class BClosed
Nov 3, 2025
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE COMPACTOR CLOSET AT PUBLIC HALL ( LABELED AS FLOOR 5 ) , 4th STORY, SECTION ''AA-MM''
Class BClosed
Oct 24, 2025Apt 3P
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS BATHTUB IN THE 1st BATHROOM FROM EAST LOCATED AT APT 3P, 2nd STORY, 9th APARTMENT FROM SOUTH AT WEST
Class BClosed
Oct 20, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING EAST AND SOUTH WALLS AT LOBBY
Class BClosed
Oct 20, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING EAST AND SOUTH WALLS AT BASEMENT AT LOBBY
Class BClosed
Oct 15, 2025Apt 2LL
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ/FT AT THE CEILING AND SOUTH AND WEST WALLS IN THE BATHROOM LOCATED AT APT 2LL, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 18014601 ISSUED 16-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Oct 14, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING, AT PUBLIC HALL, CELLAR ENTRANCE STORY
Class BClosed
Oct 14, 2025Apt 5S
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 4th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT WEST