41-25 CASE STREET

Queens · ZIP 11373 · BIN 4039107 · Elmhurst · Last violation Jul 30, 2026 · Last complaint Jul 30, 2026

NeighborhoodElmhurst
More violations than 99% of nearby buildings
More violations than 99% of buildings and more complaints than 99% of buildings in Elmhurst. Size-normalized against residential buildings in the neighborhood for issues in the last 10 years.
ViolationsComplaints
Activity TrendsLast 5 years
More activity recently than in past years
Last 2 yrs: 621 violations · 584 complaints
'21'26ViolationsComplaints
▼ View all activity over time
Severityⓘopen violations
58 immediately hazardous (Class C) violations still open
Class C violations include lead paint, mold, pest infestations, heat/hot water failure, and structural hazards — the most serious category.
Class Cimmediately hazardous58Class Bhazardous166
Housing Preservation & Development Violations
Total violations since 2001
1,045
40 per year avg.↑ Up 207% in the last 2 years (621 vs 202 prior 2 yrs)
Open violations
269
Class C (immed. haz.)ⓘ58
Class B (hazardous)ⓘ166
Rent-impairingⓘ15
Housing Preservation & Development Complaints
Total complaints since 2004
1,251
54 per year avg.↑ Up 164% in the last 2 years (584 vs 221 prior 2 yrs)
Complaint Resolution
No access14%Violation issued25%No violation26%Phone resolved34%Other1%(1,251)
Urgency breakdown
Last 12 mo.

Top violation categories

5 yrsAll time
Maintenanceⓘ269 violations
Water Supplyⓘ95 violations
Cleaningⓘ88 violations
Egressⓘ80 violations
Extermination & Rodent Eradicationⓘ70 violations
Paintingⓘ62 violations
Smoke Detecting Devicesⓘ45 violations
Carbon Monoxide Detecting Devicesⓘ41 violations
Top complaint groupsⓘ
5 yrsAll time
Heat / hot waterⓘ355 complaints
Bldg maintenanceⓘ131 complaints
Mold & pestsⓘ113 complaints
Water & plumbingⓘ100 complaints
Appliancesⓘ15 complaints
Safety & fireⓘ13 complaints
Electricalⓘ11 complaints
Adminⓘ1 complaints
Hide violations ↑See complaints →

Violation log

592 violations · Class B

All classesClass AClass BClass CClass IAllOpenClosed
ClassStatusApt
See something wrong? File a complaint with 311
Open violation ages
▪ < 30 days4% (12)
▪ 30–90 days12% (31)
▪ 3–12 months40% (106)
▪ 1–3 years35% (94)
▪ 3+ years9% (25)
Prior 4 yr.
Immed. Emergency5%3%
Emergency50%69%
Non-Emergency45%28%
(238)
(591)
Issued
Description
Class BOpen5AOct 10, 2025REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed—Oct 9, 2025REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT BULKHEAD , 6th STORY
Class BClosedRENT IMPAIRING—Oct 9, 2025LEAKY ROOF · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILNG AT BULKHEAD AT PUBLIC HALL STAIRS, 6th STORY, SECTION AT NORTH
Class BClosed—Oct 9, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING, WINDOW RECESS AT EAST, AND EAST WALL AT PUBLIC HALL, 1st STORY
Class BClosed—Oct 9, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING, WINDOW RECESS AT EAST, AND EAST WALL AT PUBLIC HALL, 1st STORY
Class BClosed—Oct 9, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS LEADING TO BULKHEAD AT PUBLIC HALL STAIRS, 6th STORY, SECTION AT NORTH
Class BClosed—Oct 9, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING, EAST WALL AND NORTH WALLS AT PUBLIC HALL, 1st STORY
Class BClosed—Oct 9, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT WEST WALL LEADING TO BULKHEAD AT PUBLIC HALL STAIRS, 6th STORY, SECTION AT NORTH
Class BClosed—Oct 9, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER ON CELING, EAST AND NORTH WALLS AT PUBLIC HALL, 1st STORY
Class BOpen5GOct 8, 2025CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST
Class BOpen5SOct 7, 2025REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH''
Class BOpen3AOct 6, 2025TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT SOUTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17939522 ISSUED 05-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BOpen3AOct 6, 2025TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT AT SOUTH WALL IN THE 4th ROOM FROM NORTH AT WEST LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17939523 ISSUED 05-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed—Oct 3, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT LOBBY, 1st STORY
Class BClosed4TOct 3, 2025REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''KT''
Class BOpen4TOct 3, 2025REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VINYL FLOORING IN THE KITCHEN LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''KT''
Class BClosed4TOct 3, 2025REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''KT''
Class BClosed—Sep 30, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed—Sep 30, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed2OSep 25, 2025REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE GASKET AT REFRIGERATOR DOOR IN THE KITCHEN LOCATED AT APT 2O, 2nd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION ''EAST''
Class BClosed—Sep 25, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AND NORTH WALL AT PUBLIC HALL, 1st STORY
Class BClosed—Sep 22, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATIERIAL AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed—Sep 22, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING AND EAST WALL AT PUBLIC HALL, 1st STORY
Class BClosed4KSep 15, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed—Sep 15, 2025REMOVE ACCUMULATION OR RUBBISH · CLEANING§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE 1ST OUTER COURT FROM EAST AT SOUTH (BUILDING FRONT).
Class BClosed—Sep 15, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT EAST WALL AT PUBLIC HALL, 1st STORY, SECTION AT NORTH
Class BClosed—Sep 15, 2025REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCHSET AT DOOR LEADING TO STAIRCASE AT PUBLIC HALL STAIRS, 4th STORY, SECTION AT NORTH
Class BClosed4FSep 15, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE AT NORTH WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed—Sep 15, 2025REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR AT COMPACTOR CLOSET DOOR , 1st STORY
Class BClosed4FSep 15, 2025REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed4FSep 15, 2025REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed4FSep 15, 2025REPAIR · MAINTENANCE§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL BUZZER RETURN SYSTEM PANEL AT NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed4KSep 15, 2025REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed4KSep 15, 2025REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed1HSep 15, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST
Class BClosed—Sep 15, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed1HSep 15, 2025REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, EAST WALL, AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST
Class BClosed—Sep 15, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING, NORTH WALL, AND WEST WALL AT PUBLIC HALL, 1st STORY
Class BClosed4FSep 15, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed1HSep 15, 2025TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQUARE FEET AT CEILING, EAST WALL, AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST
Class BClosed—Sep 12, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed—Sep 10, 2025REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING, NORTH AND WEST WALL , 1st STORY
Class BClosed—Sep 10, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING, NORTH AND WEST WALL , 1st STORY
Class BClosed—Sep 3, 2025REPAIR PLASTER · MAINTENANCE§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed3KAug 11, 2025REPAIR WITH SIMILAR MATERIAL · MAINTENANCE§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosedRENT IMPAIRING—Aug 11, 2025F/E ADJUST THE DROP LADDER · EGRESS§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS OFF GRAVITY HOOK AT 2ND FROM WEST AT NORTH, BUILDING FRONT AT FIRE ESCAPE
Class BClosed3KAug 11, 2025TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT AT EAST, SOUTH AND WEST WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed3KAug 11, 2025REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed3KAug 11, 2025SECURE LOOSE MATTER · MAINTENANCE§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WALL CABINET AT NORTH WALL IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BOpen5SAug 5, 2025TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17810117 ISSUED 05-APR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
Class BOpen
Oct 10, 2025Apt 5A
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Oct 9, 2025
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AT BULKHEAD , 6th STORY
Class BClosedRENT IMPAIRING
Oct 9, 2025
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILNG AT BULKHEAD AT PUBLIC HALL STAIRS, 6th STORY, SECTION AT NORTH
Class BClosed
Oct 9, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING, WINDOW RECESS AT EAST, AND EAST WALL AT PUBLIC HALL, 1st STORY
Class BClosed
Oct 9, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING, WINDOW RECESS AT EAST, AND EAST WALL AT PUBLIC HALL, 1st STORY
Class BClosed
Oct 9, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS LEADING TO BULKHEAD AT PUBLIC HALL STAIRS, 6th STORY, SECTION AT NORTH
Class BClosed
Oct 9, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING, EAST WALL AND NORTH WALLS AT PUBLIC HALL, 1st STORY
Class BClosed
Oct 9, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT WEST WALL LEADING TO BULKHEAD AT PUBLIC HALL STAIRS, 6th STORY, SECTION AT NORTH
Class BClosed
Oct 9, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER ON CELING, EAST AND NORTH WALLS AT PUBLIC HALL, 1st STORY
Class BOpen
Oct 8, 2025Apt 5G
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 5G, 5th STORY, 4th APARTMENT FROM NORTH AT EAST
Class BOpen
Oct 7, 2025Apt 5S
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''SOUTH''
Class BOpen
Oct 6, 2025Apt 3A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT SOUTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17939522 ISSUED 05-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BOpen
Oct 6, 2025Apt 3A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT AT SOUTH WALL IN THE 4th ROOM FROM NORTH AT WEST LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH ORIGINAL VIOLATION 17939523 ISSUED 05-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
Class BClosed
Oct 3, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT LOBBY, 1st STORY
Class BClosed
Oct 3, 2025Apt 4T
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''KT''
Class BOpen
Oct 3, 2025Apt 4T
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VINYL FLOORING IN THE KITCHEN LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''KT''
Class BClosed
Oct 3, 2025Apt 4T
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4T, 4th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION ''KT''
Class BClosed
Sep 30, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 30, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 25, 2025Apt 2O
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE GASKET AT REFRIGERATOR DOOR IN THE KITCHEN LOCATED AT APT 2O, 2nd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION ''EAST''
Class BClosed
Sep 25, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AND NORTH WALL AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 22, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATIERIAL AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 22, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING AND EAST WALL AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 15, 2025Apt 4K
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Sep 15, 2025
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE 1ST OUTER COURT FROM EAST AT SOUTH (BUILDING FRONT).
Class BClosed
Sep 15, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT EAST WALL AT PUBLIC HALL, 1st STORY, SECTION AT NORTH
Class BClosed
Sep 15, 2025
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCHSET AT DOOR LEADING TO STAIRCASE AT PUBLIC HALL STAIRS, 4th STORY, SECTION AT NORTH
Class BClosed
Sep 15, 2025Apt 4F
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE AT NORTH WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Sep 15, 2025
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT DOOR AT COMPACTOR CLOSET DOOR , 1st STORY
Class BClosed
Sep 15, 2025Apt 4F
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Sep 15, 2025Apt 4F
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Sep 15, 2025Apt 4F
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BELL BUZZER RETURN SYSTEM PANEL AT NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Sep 15, 2025Apt 4K
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Sep 15, 2025Apt 4K
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 4K, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Sep 15, 2025Apt 1H
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST
Class BClosed
Sep 15, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 15, 2025Apt 1H
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, EAST WALL, AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST
Class BClosed
Sep 15, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING, NORTH WALL, AND WEST WALL AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 15, 2025Apt 4F
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Sep 15, 2025Apt 1H
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQUARE FEET AT CEILING, EAST WALL, AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 5th APARTMENT FROM WEST AT NORTH , SECTION AT WEST
Class BClosed
Sep 12, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Sep 10, 2025
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING, NORTH AND WEST WALL , 1st STORY
Class BClosed
Sep 10, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT THE CEILING, NORTH AND WEST WALL , 1st STORY
Class BClosed
Sep 3, 2025
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Aug 11, 2025Apt 3K
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosedRENT IMPAIRING
Aug 11, 2025
F/E ADJUST THE DROP LADDER · EGRESS
§ 27-2005 ADM CODE FIRE ESCAPE DEFECTIVE. ADJUST THE DROPLADDER SO THAT IT WILL SLIDE EASILY IN THE GUIDE RODS OFF GRAVITY HOOK AT 2ND FROM WEST AT NORTH, BUILDING FRONT AT FIRE ESCAPE
Class BClosed
Aug 11, 2025Apt 3K
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT AT EAST, SOUTH AND WEST WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Aug 11, 2025Apt 3K
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Aug 11, 2025Apt 3K
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WALL CABINET AT NORTH WALL IN THE KITCHEN LOCATED AT APT 3K, 3rd STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BOpen
Aug 5, 2025Apt 5S
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ FEET AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 5S, 5th STORY, 1st APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 17810117 ISSUED 05-APR-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).