Class BClosed
May 20, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES OUTLETS AT THE EAST AND NORTH WALLS AND LIGHT FIXTURE AT CEILING IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 118 LOWER LEVEL, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 20, 2016Apt 118
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE CLOSET DOOR IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 118 LOWER LEVEL, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 20, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES OUTLETS AT EAST AND SOUTH WALLS AND LIGHT FIXTURE AT CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 118 LOWER LEVEL, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 20, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT THE CEILING IN THE KITCHEN LOCATED AT APT 118 LOWER LEVEL, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE IN THE FOYER LOCATED AT APT 118, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE,ALL WALL RECEPTICALS AT ROOM EAST SOUTH 3 LOCATED AT APT 118, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE AT CLOSET IN THE FOYER LOCATED AT APT 118, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE IN THE FOYER LOCATED AT APT 118 UPPER LEVEL, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES WALL RECEPTACLE AND LIGHT FIXTURE IN THE BATHROOM LOCATED AT APT 118 UPPER LEVEL, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 118, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE IN THE KITCHEN LOCATED AT APT 118, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 13, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES CEILING LIGHT FIXTURE AT INTERIOR STAIRS 1ST AND 2ND STORY LOCATED AT APT 118, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
May 10, 2016Apt 703
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE TUB PROCELIN PAINT IN THE BATHROOM LOCATED AT APT 703 LOWER LEVEL, 7th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 10, 2016
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE , AT COMPACTOR CLOSET, 3rd STORY
Class BClosed
May 10, 2016
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE , AT COMPACTOR CLOSET, 4th STORY
Class BClosed
May 4, 2016Apt 118
NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 118, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 4, 2016Apt 118
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR AT LOWER LEVEL IN THE ENTIRE APARTMENT LOCATED AT APT 118, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 4, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES OUTLET AT EAST WALL AND LIGHT FIXTURE AT CEILING IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 118 LOWER LEVEL, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
May 4, 2016Apt 118
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES OUTLET AT THE EAST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 118 LOWER LEVEL, 1st STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Apr 29, 2016Apt 1707
ABATE THE NUISANCE OF BEDBUGS · EXTERMINATION & RODENT ERADICATION
§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF BEDBUGS IN THE ENTIRE APARTMENT LOCATED AT APT 1707, 17th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Mar 2, 2016Apt 117
ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION
§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 117, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Mar 2, 2016Apt 117
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 117, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 22, 2016Apt 505
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE GASKET AT THE REFRIGERATOR IN THE KITCHEN LOCATED AT APT 505 LOWER LEVEL, 5th STORY, 5th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 22, 2016Apt 505
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CAULKING AROUND BATHTUB IN THE BATHROOM LOCATED AT APT 505 UPPER LEVEL, 5th STORY, 5th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 22, 2016Apt 1507
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE BASEBOARD HEATER COVER IN THE ENTIRE APARTMENT LOCATED AT APT 1507, 15th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 22, 2016Apt 1507
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR INOPERATIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1507, 15th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 22, 2016Apt 1507
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). INOPERATIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1507, 15th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 18, 2016Apt 1907
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING AND WALLS AT INTERIOR STAIRS LOCATED AT APT 1907, 19th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 18, 2016Apt 1907
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND WALLS AT INTERIOR STAIRS LOCATED AT APT 1907, 19th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 18, 2016Apt 1907
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR AT INTERIOR STAIRS LOCATED AT APT 1907, 19th STORY, 7th APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 17, 2016Apt 703
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CLOSET WALL AT EAST IN THE 1st ROOM FROM EAST LOCATED AT APT 703, 7th STORY, 3rd APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2016Apt 1902
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1902, 19th STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2016Apt 1902
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 1902, 19th STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2016Apt 1902
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 1902, 19th STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2016Apt 1902
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH IN THE 2nd ROOM FROM EAST LOCATED AT APT 1902, 19th STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 11, 2016Apt 1902
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH IN THE 1st ROOM FROM EAST LOCATED AT APT 1902, 19th STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Dec 28, 2015Apt 1707
ABATE THE NUISANCE OF BEDBUGS · EXTERMINATION & RODENT ERADICATION
§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF BEDBUGS IN THE 1st ROOM FROM EAST LOCATED AT APT 1707 LOWER LEVEL, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Dec 8, 2015Apt 429
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 429, 4th STORY, 5th APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 8, 2015Apt 429
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 429, 4th STORY, 5th APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 8, 2015Apt 429
ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION
§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 429, 4th STORY, 5th APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 1, 2015Apt 429
NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 429, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 1, 2015Apt 429
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES , IN THE BATHROOM LOCATED AT APT 429, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 1, 2015Apt 429
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 429, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Dec 1, 2015Apt 429
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTER BALANCE TO THE LOWER SASH OF THE SECOND WINDOW FROM SOUTH AT WEST IN THE 1st ROOM FROM NORTH LOCATED AT APT 429, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 24, 2015Apt 429
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 429, 4th STORY, 5th APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 24, 2015Apt 132
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... COVERING APPROXIMATELY 1 SQUARE FOOT AT THE CEILNG IN THE BATHROOM LOCATED AT APT 132, 1st STORY, 6th APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 24, 2015Apt 132
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE LOCATED AT APT 132, 1st STORY, 6th APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 24, 2015Apt 132
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE LOCATED AT APT 132, 1st STORY, 6th APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 24, 2015Apt 132
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE VENTILATION SYSTEM MOUNTED AT THE WALL IN THE BATHROOM LOCATED AT APT 132, 1st STORY, 6th APARTMENT FROM EAST AT SOUTH
Class BClosed
Nov 24, 2015Apt 429
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE COUNTERBALANCE ON LOWER SASH ON 2ND WINDOW FROM EAST IN THE 2nd ROOM FROM EAST LOCATED AT APT 429, 4th STORY, 5th APARTMENT FROM EAST AT SOUTH