Class BClosed
Jan 22, 2026Apt B1
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B1, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Jan 22, 2026Apt D1
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT D1, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH
Class CClosed
Jan 22, 2026
PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER
§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED FROM REAR EAST FIRE PASSAGEWAY TO CELLAR AT BOILER ROOM
Class BClosed
Jan 22, 2026Apt B1
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B1, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Jan 22, 2026Apt B1
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE AND DETACHED SINK CABINET AT WEST WALL IN THE KITCHEN LOCATED AT APT B1, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Jan 22, 2026Apt D1
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT D1, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH
Class CClosed
Jan 22, 2026Apt B1
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT B1, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class AClosed
Jan 22, 2026Apt D1
CLEANSE · CLEANING
§ 27-2011 ADM CODE CLEANSE TO THE SATISFACTION OF THIS DEPARTMENT THE VISIBLE MOLD AT CAULKING AND GROUT JOINTS OF THE CERAMIC TILES AT SOUTH AND WEST WALLS AROUND BATHTUB, IN THE BATHROOM LOCATED AT APT D1, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH
Class CClosed
Jan 22, 2026
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM AT PUBLIC HALL, 1st STORY
Class CClosed
Jan 22, 2026
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE AND DETACHED METAL CANOPY ABOVE AT WEST BUILDING ENTRANCE DOOR
Class BOpen
Jan 22, 2026Apt B1
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HANDLE KNOB AT SHUT OFF VALVE OF THE RADIATOR AT WEST WALL, IN THE 4th ROOM FROM NORTH LOCATED AT APT B1, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpenRENT IMPAIRING
Jan 21, 2026Apt B1
INADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT B1, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpenRENT IMPAIRING
Jan 21, 2026Apt D1
INADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT D1, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTH
Class BClosed
Jan 20, 2026Apt B7
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE FOYER LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class BClosed
Jan 20, 2026Apt B7
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL COVER AT CEILING IN THE KITCHEN LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class BClosed
Jan 20, 2026Apt B7
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT NORTH WALL IN THE KITCHEN LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class BClosed
Jan 20, 2026Apt B7
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF AT EAST WALL IN THE KITCHEN LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class BClosed
Jan 20, 2026Apt B7
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF AT CEILING IN THE FOYER LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class BClosed
Jan 20, 2026Apt B7
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class BClosed
Jan 20, 2026Apt B7
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''WEST''
Class COpen
Jan 20, 2026
PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER
§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM LOCKED DOOR AT BASEMENT AT BOILER ROOM
Class COpen
Jan 20, 2026
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
Class CClosedRENT IMPAIRING
Jan 16, 2026Apt D1
INADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT D1, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''WEST''
Class CClosedRENT IMPAIRING
Jan 16, 2026Apt D1
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT D1, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''WEST''
Class BClosedRENT IMPAIRING
Jan 15, 2026
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ITEMS AT PUBLIC HALL, 1st STORY
Class AClosed
Jan 12, 2026Apt B7
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT AT CEILING. IN THE BATHROOM LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026Apt B7
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND NORTH WALL IN THE KITCHEN LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026Apt B7
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT CEILING IN THE KITCHEN LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026Apt B7
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026Apt B7
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026
PROVIDE GARGABE CANS · COLLECTION OF WASTE
§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL.
Class CClosed
Jan 12, 2026
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE WEST YARD
Class CClosed
Jan 12, 2026Apt B7
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class CClosed
Jan 12, 2026Apt B7
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT NORTH WALL IN THE KITCHEN LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026Apt B7
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT CEILING IN THE FOYER LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class BClosed
Jan 12, 2026Apt B7
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE FOYER LOCATED AT APT B7, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''
Class CClosed
Dec 26, 2025
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE AT WEST COURT
Class CClosed
Oct 3, 2025Apt B3
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st CLOSET FROM WEST AT NORTH WALL DOOR, 1st CLOSET FROM WEST AT NORTH WALL DOOR FRAME IN THE PRIVATE HALLWAY LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class AClosed
Oct 3, 2025Apt B3
PAINT METAL · PAINTING
§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION THE 1st RISER FROM SOUTH AT WEST WALL IN THE 5th ROOM FROM EAST LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class CClosed
Oct 3, 2025Apt B3
INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS
§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1, WG TO REPLACE = 0, WG TO REPAIR = 1 IN THE ENTIRE APARTMENT LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class AClosed
Oct 3, 2025Apt B3
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 1st ROOM FROM EAST, THE 9th BATHROOM LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class CClosed
Oct 3, 2025Apt B3
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st WINDOW FRAME FROM WEST AT NORTH WALL IN THE KITCHEN LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class CClosed
Oct 3, 2025Apt B3
CORRECT THE LEAD-BASED PAINT TESTED INCONCLUSIVE OR POSTIVE FOR METAL/CERAMIC SUBSTRATE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD-PAINT THAT IS XRF TESTED INCONCLUSIVE FOR LEAD CONTENT AT 0.5MG/CM2 AND IS PRESUMED LEAD PAINT AS SET FORTH IN (28 RCNY §11-07(b)) AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE-USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(b)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class CClosed
Oct 3, 2025Apt B3
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) BASEBOARD AT NORTH WALL IN THE 5th ROOM FROM EAST LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class AClosed
Oct 3, 2025Apt B3
PAINT METAL · PAINTING
§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION THE 1st RADIATOR FROM WEST AT NORTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class AClosed
Oct 3, 2025Apt B3
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE WEST WALL, EAST WALL IN THE KITCHEN LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class CClosed
Oct 3, 2025Apt B3
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) BASEBOARD AT EAST WALL, PICTURE MOULDING AT SOUTH WALL, PICTURE MOULDING AT EAST WALL, NORTH WALL, SOUTH WALL, EAST WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT B3, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class BClosed
Sep 29, 2025Apt C7
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT C7, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Sep 29, 2025Apt C7
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT AT CEILING, NORTH, WEST AND EAST WALLS IN THE BATHROOM LOCATED AT APT C7, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Sep 29, 2025Apt C7
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT C7, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH