Class CClosed
Nov 27, 2024Apt 3R
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR IN THE ENTRANCE LOCATED AT APT 3R, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class AClosed
Nov 25, 2024Apt 3R
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES THE ELECTRICAL OUTLET AT CLOSET IN THE 1st ROOM FROM EAST LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 25, 2024
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE THE 5TH TREAD UP FROM 1ST STORY LANDING AT PUBLIC HALL STAIRS, 1st STORY
Class CClosed
Nov 25, 2024
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DEFECTIVE HINGES AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 25, 2024
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT COMMUNITY BATHROOM, 2nd STORY
Class BClosed
Nov 25, 2024Apt 3R
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE 1st ROOM FROM EAST LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 25, 2024Apt 3R
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE 1st ROOM FROM EAST LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 25, 2024
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL AND EAST WALL AT COMMUNITY BATHROOM, 2nd STORY
Class BClosed
Nov 25, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT CELLAR
Class BOpen
Nov 25, 2024Apt 3R
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER SASH WINDOW AT THE 2ND WINDOW FROM EAST AT SOUTH IN THE 1st ROOM FROM EAST LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class CClosed
Nov 25, 2024
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PAINTED SPRINKLER HEAD AT LOBBY
Class BClosed
Nov 25, 2024
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE LIGHT FIXTURE AT CEILING AT LOBBY, 1st STORY
Class COpen
Nov 22, 2024Apt 3F
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR IN THE ENTRANCE LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BOpen
Nov 22, 2024Apt 3F
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class CClosed
Nov 22, 2024
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS AT COMMUNITY BATHROOM, 2nd STORY
Class CClosed
Nov 22, 2024
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT VESTIBULE AT PUBLIC HALL, 1st STORY
Class BOpen
Nov 22, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILES AT PUBLIC HALL
Class CClosed
Nov 22, 2024
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF AT LIGHT FIXTURE AT CEILING AT LOBBY, 1st STORY
Class BClosed
Nov 22, 2024Apt 3F
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE VENTILATION SYSTEM AT CEILING IN THE KITCHEN LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BClosed
Nov 22, 2024Apt 3F
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RADIATOR SHUT OFF VALVE. 1ST RADIATOR AT WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BClosed
Nov 22, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE REGLAZE AT BATHTUB AT COMMUNITY BATHROOM, 2nd STORY
Class AOpen
Nov 22, 2024Apt 3F
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT ALL CEILINGS AND ALL WALLS IN THE ENTIRE APARTMENT LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BOpen
Nov 22, 2024Apt 3F
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class CClosed
Nov 22, 2024
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE LIGHT FIXTURE AT CEILING AT LOBBY, 1st STORY
Class CClosed
Nov 22, 2024Apt 3F
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTERBALANCE LOWER SASH 1ST WINDOW AT WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3F, 2nd STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class CClosed
Nov 21, 2024
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PAINT ON SPRINKLER HEAD AT PUBLIC HALL
Class AOpen
Nov 20, 2024Apt 3R
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOM SYSTEM FROM BUILDING ENTRANCE TO RETURN BUZZER AT NORTH WALL IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 20, 2024
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRE AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 20, 2024
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE LIGHT FIXTURE AT CEILING AT PUBLIC HALL, 1st STORY
Class CClosed
Nov 20, 2024Apt 3R
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE 1st ENTRANCE FROM EAST LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class CClosed
Nov 20, 2024
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT VESTIBULE DOOR
Class BClosed
Nov 20, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT PUBLIC HALL, 3rd STORY
Class BClosed
Nov 20, 2024
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE LIGHT FIXTURE AT CEILING AT PUBLIC HALL, 1st STORY
Class CClosed
Nov 20, 2024
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT VESTIBULE DOOR
Class BClosed
Nov 20, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD TREAD, 5TH UP FROM BOTTOM AT PUBLIC HALL STAIRS, 1st STORY
Class BClosed
Nov 20, 2024Apt 3R
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT WEST WALL IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 20, 2024
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RADIATOR SHUT-OFF KNOB AT EAST AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 20, 2024Apt 3R
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 20, 2024Apt 3R
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 20, 2024Apt 3R
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTERBALANCE AT LOWER SASH AT 2ND WINDOW FROM EAST AT SOUTH IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 20, 2024Apt 3R
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RADIATOR SHUT-OFF KNOB AT SOUTH IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 20, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD TREAD, 5TH UP FROM BOTTOM AT PUBLIC HALL STAIRS, 1st STORY
Class BClosed
Nov 20, 2024
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RADIATOR SHUT-OFF KNOB AT EAST AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 20, 2024
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRE AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 20, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT PUBLIC HALL, 3rd STORY
Class BOpen
Nov 20, 2024
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION SYSTEM AT NORTH WALL AT COMMUNITY BATHROOM, 2nd STORY
Class BOpen
Nov 20, 2024Apt 3R
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 2nd ROOM FROM EAST AT SOUTH LOCATED AT B-ROOM 3R, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST
Class BClosed
Nov 19, 2024
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD TREAD, 5TH UP FROM BOTTOM AT PUBLIC HALL STAIRS, 1st STORY
Class BClosed
Nov 19, 2024
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRIC WIRE AT CEILING AT PUBLIC HALL, 1st STORY
Class BClosed
Nov 19, 2024
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE LIGHT FIXTURE AT CEILING AT PUBLIC HALL, 1st STORY