Class COpen
May 15, 2025Apt 3D
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT DOOR TO PUBLIC HALL IN THE 2nd ROOM FROM EAST LOCATED AT B-ROOM 3D, 3rd STORY, 1st B-ROOM FROM EAST AT SOUTH
Class COpen
May 15, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR TO PUBLIC HALL AT COMMUNITY BATHROOM, 3rd STORY
Class CClosed
May 5, 2025
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE GLASS PANE AT BUILDING ENTRANCE DOOR , 1st STORY
Class AOpen
May 1, 2025
POST GAS LEAK NOTICE · POSTING/SIGNAGE
§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY
Class BOpen
May 1, 2025Apt 3D
REFIT DOORS ETC. · EGRESS
§ 27-2005 HMC: REFIT AT SOUTH ENTRANCE DOOR IN THE ENTRANCE LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class AOpen
May 1, 2025Apt 3D
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RUBBER GASKET AT REFRIGERATOR DOORS IN THE KITCHEN LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpen
May 1, 2025Apt 3D
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR AT WEST ENTRANCE DOOR IN THE ENTRANCE LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpen
May 1, 2025Apt 3D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH,WEST WALL AND CEILING IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpenRENT IMPAIRING
May 1, 2025Apt 3D
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER THE CEILING IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpen
May 1, 2025Apt 3D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST WALL AND CEILING IN THE 2nd ROOM FROM EAST LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpen
May 1, 2025Apt 3D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL IN CLOSET 1ST CLOSET AT NORTH IN THE 2nd ROOM FROM EAST LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class AOpen
May 1, 2025
POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE
§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
Class AOpen
May 1, 2025
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
Class BOpen
Apr 8, 2025Apt 3D
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpen
Mar 20, 2025Apt 3D
ADJUST DOOR TO PREVENT GAP - FIRE CODE/EGRESS · EGRESS
28 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT DOOR IN THE ENTRANCE LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpen
Mar 20, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WEST WALL AT CELLAR
Class COpen
Mar 20, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT COMMUNITY BATHROOM, 3rd STORY
Class CClosed
Mar 20, 2025Apt 3D
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET IN THE ENTRANCE LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class AOpen
Mar 20, 2025
POST GAS LEAK NOTICE · POSTING/SIGNAGE
§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED
Class AOpen
Mar 20, 2025
POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE
§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
Class AOpen
Mar 20, 2025
POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE
§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
Class COpen
Mar 20, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT BUILDING ENTRANCE , 1st STORY
Class AOpen
Mar 20, 2025
POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE
§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
Class AOpen
Mar 20, 2025
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
Class AOpen
Mar 20, 2025
POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING.
Class AOpen
Mar 20, 2025
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AND WEST WALL AT CELLAR
Class AOpen
Mar 20, 2025
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY
Class BOpen
Mar 20, 2025Apt 3D
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BOpen
Jan 10, 2025Apt 3D
NO CO DETECTOR OR DETECTOR NOT OPERATIONAL · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. LOCATED AT B-ROOM 3D, 3rd STORY, 1st B-ROOM FROM EAST AT SOUTH
Class BOpen
Jan 10, 2025Apt 3D
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT B-ROOM 3D, 3rd STORY, 1st B-ROOM FROM EAST AT SOUTH
Class CClosed
Jan 10, 2025Apt 3D
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGE AT ENTRANCE DOOR LOCATED AT B-ROOM 3D, 3rd STORY, 1st B-ROOM FROM EAST AT SOUTH
Class COpen
Jun 24, 2024Apt D
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DEFECTIVE HINGES LOCATED AT B-ROOM D, 3rd STORY
Class AOpen
Jun 24, 2024Apt D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE RUBBER GASKET SEAL ON REFRIGERATOR UPPER AND LOWER DOORS IN THE KITCHENETTE LOCATED AT B-ROOM D, 3rd STORY
Class AClosed
Apr 11, 2024
FILE ANNUAL BEDBUG REPORT · FILING: BEDBUGS
(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
Class AClosed
Mar 24, 2023
FILE ANNUAL BEDBUG REPORT · FILING: BEDBUGS
(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
Class AClosed
Mar 2, 2022
FILE ANNUAL BEDBUG REPORT · FILING: BEDBUGS
(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
Class AClosed
Apr 13, 2021
FILE ANNUAL BEDBUG REPORT · FILING: BEDBUGS
(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
Class AOpen
Aug 20, 2008
PROVIDE ENCLOSURE AT · FIRE EGRESS AND PROTECTION
§ 65 M/D LAW PROVIDE UNDER COMPLETED PERMIT, A PROPER ENCLOSURE FOR THE CENTRAL HEATING PLANT, CELLAR CENTER.
Class IClosed
—
FILE A VALID REGISTRATION · ANNUAL PROPERTY REGISTRATION
§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
Class IClosed
—
FILE A VALID REGISTRATION · ANNUAL PROPERTY REGISTRATION
§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.