Class BClosed
Mar 5, 2025
REPLACE · MAINTENANCE
D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING VENT IN WALL BOILER ENCLOSURE CELLAR REAR.
Class BClosed
Mar 5, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE NORTH MASONRY WALL BOILER ENCLOSURE CELLAR REAR.
Class AClosed
Mar 5, 2025
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
D26-41.15 ADM CODE POST A SIGN ON WALL OF ENTRANCE STORY IDENTIFYING OWNER AND MANAGING AGENT.
Class AClosed
Mar 5, 2025
PAINT WINDOW FRAMES AND SASHES · PAINTING
D26-12.03 ADM CODE PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE EXTERIOR WINDOW FRAMES AND SASHES ALL STYS FRONT & REAR OF BLDG.
Class AClosed
Mar 5, 2025
POST FLOOR SIGN · POSTING/SIGNAGE
D26-21.03 ADM CODE PAINT OR POST A SIGN INDICATING FLOORS ON WALLS NEAR STAIRS ALL STYS PUB HALLS.
Class AOpen
Mar 5, 2025
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR . AT PUBLIC HALL
Class AClosed
Mar 5, 2025
ABATE THE NUISANCE · MAINTENANCE
D26-10.01 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF EXPOSED ELECTRIC WIRES CLG FIXTURE 1 STY PUB HALL.
Class AClosed
Mar 5, 2025
PROVIDE SHOE FOR DROP LADDER · FIRE EGRESS AND PROTECTION
§ 53, 187, 231 M/D LAW AND DEPARTMENT RULES AND REGULATIONS. PROVIDE A SHOE PROPERLY SECURED TO BOTTOM OF STRING OF DROPLADDER REAR FIRE ESCAPE.
Class BClosed
Mar 5, 2025
REMOVE ACCUMULATION OR RUBBISH · CLEANING
§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE FLOOR AT BLDG. ENTRANCE; EAST , 1st STORY
Class BClosedRENT IMPAIRING
Mar 5, 2025
REMOVE ENCUMBRANCES · EGRESS
D26-10.01, 10.05 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ARTICLES 1 STY PUB HALL.
Class AClosed
Mar 5, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PLASTERBOARD CEILING THROUGHOUT CELLAR.
Class BClosed
Mar 5, 2025
REPLACE · MAINTENANCE
D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING HANDRAIL FRONT ENTRANCE STOOP.
Class BClosedRENT IMPAIRING
Mar 5, 2025
REMOVE ENCUMBRANCES · EGRESS
D26-10.01, 10.05 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF HOUSEHOLD ARTICLES 3RD STY PUBLIC HALL.
Class AClosed
Mar 5, 2025
REPLACE · MAINTENANCE
D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING ELECTRIC LIGHT BULB IN NORTH FIXTURE FRONT ENTRANCE TO BLDG.
Class CClosedRENT IMPAIRING
Mar 4, 2025Apt 7T
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 7T, 7th STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BOpen
Feb 18, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT EAST WALL AT PUBLIC HALL, 5th STORY
Class BOpen
Feb 18, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDENT MATERIAL AT EAST WALL AT PUBLIC HALL, 5th STORY
Class AOpen
Feb 13, 2025
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING., 1st STORY
Class COpen
Feb 13, 2025
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM ... , 1st STORY
Class BOpen
Feb 13, 2025Apt 5B
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER THE ROOF IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class AOpen
Feb 13, 2025
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR ... , 1st STORY
Class AOpen
Feb 13, 2025
POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE
§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD., 1st STORY
Class BOpen
Feb 13, 2025Apt 5B
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Feb 10, 2025Apt 506
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDING THE MAXIMUM TEMPERATURE OF 130 DEGREES AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 506, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
Class CClosed
Feb 5, 2025Apt 4A
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDING THE MAMIUM TEMPERATUE OF 130 DEGREES AT ALL HOT WATER FIXTURE BATHROOM AND KITCHEN SINK IN THE ENTIRE APARTMENT LOCATED AT APT 4A, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosedRENT IMPAIRING
Jan 30, 2025Apt 1A
REMOVE OBSTRUCTIONS · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN THE BATHTUB WASTE LINE IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Jan 30, 2025Apt 1A
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Jan 30, 2025Apt 1A
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Jan 28, 2025
PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER
§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM INDIVIDUAL HEATING SYSTEM AT BOILER ROOM
Class CClosedRENT IMPAIRING
Jan 27, 2025Apt 3A
INADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
Class CClosedRENT IMPAIRING
Jan 23, 2025Apt 3H
INADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2029 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FOR THE APARTMENT IN THE ENTIRE APARTMENT LOCATED AT APT 3H, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
Class CClosed
Jan 22, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT COMPATOR DOOR AT PUBLIC HALL, 5th STORY
Class CClosed
Jan 16, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT REFUSE DOOR AT PUBLIC HALL, 2nd STORY
Class BClosed
Jan 14, 2025Apt 6S
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING LOUVER CONTROL COVER OVER VENT AT CEILING IN THE 4th ROOM FROM EAST AT NORTH LOCATED AT APT 6S, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH
Class BClosed
Jan 14, 2025Apt 6S
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE THERMOSTAT CONTROL BOX AT WEST WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 6S, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH
Class BClosed
Jan 14, 2025Apt 6S
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF EXCESSIVE AIR BLOWING OUT FROM MECHANICAL VENT AT CEILING IN THE 4th ROOM FROM EAST AT NORTH LOCATED AT APT 6S, 6th STORY, 3rd APARTMENT FROM WEST AT NORTH
Class CClosed
Jan 9, 2025Apt 511
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 511, 5th STORY, 6th APARTMENT FROM EAST AT SOUTH
Class CClosed
Jan 6, 2025
PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER
§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT ROOF LEADING TO BOILER ROOM. AT BOILER ROOM
Class BOpen
Dec 23, 2024Apt 5B
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosedRENT IMPAIRING
Dec 23, 2024Apt 502
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE 1st ROOM FROM EAST LOCATED AT B-ROOM 502, 5th STORY, 1st B-ROOM FROM NORTH AT EAST
Class BOpen
Dec 23, 2024Apt 5B
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM WEST AT NORTH
Class COpen
Dec 23, 2024
PROVIDE ACCESS TO BOILER ROOM · HEAT AND HOT WATER
§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BASEMENT AT BOILER ROOM
Class AOpen
Dec 23, 2024
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL
Class AOpen
Dec 23, 2024
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT FIRE STAIRS, 5th STORY
Class BOpenRENT IMPAIRING
Dec 23, 2024
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BOXES AT PUBLIC HALL, 5th STORY
Class AOpen
Dec 23, 2024
POST GAS LEAK NOTICE · POSTING/SIGNAGE
§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL
Class AOpen
Dec 23, 2024
POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING.
Class AOpen
Dec 23, 2024
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL
Class AOpen
Dec 23, 2024
POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE
§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL
Class COpen
Dec 23, 2024
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL