Class CClosed
Oct 15, 2025Apt C25
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING LOWER WINDOW SASH LEADING TO FIRE ESCAPE IN THE 1st ROOM FROM NORTH LOCATED AT APT C25, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Oct 15, 2025Apt E25
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH LEADING TO FIRE ESCAPE WINDOW IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT E25, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
Class CClosed
Oct 15, 2025Apt D25
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT D25, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Oct 15, 2025Apt E26
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH IN THE KITCHEN LOCATED AT APT E26, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class BClosed
Oct 15, 2025Apt E25
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E25, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
Class CClosed
Oct 15, 2025Apt E17
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER WINDOW SASH IN THE 1st ROOM FROM NORTH LOCATED AT APT E17, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Oct 10, 2025Apt D20
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D20, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
Class AClosed
Oct 10, 2025Apt B20
RESET WATER CLOSET BOWL · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL .. IN THE BATHROOM LOCATED AT APT B20, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2514''
Class BClosed
Oct 10, 2025Apt B20
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD SADDLE DOOR ENTRANCE IN THE BATHROOM LOCATED AT APT B20, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2514''
Class BClosed
Oct 10, 2025Apt 17A
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD BASE CABINET AT WASH BASIN IN THE BATHROOM LOCATED AT APT 17A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''2512''
Class BClosed
Oct 10, 2025Apt D20
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D20, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
Class CClosed
Oct 10, 2025Apt B20
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT B20, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2514''
Class CClosed
Oct 10, 2025Apt D24
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT D24, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class CClosed
Oct 10, 2025Apt D24
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE BATHROOM LOCATED AT APT D24, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Oct 10, 2025Apt D26
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT D26, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Oct 10, 2025Apt D26
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING IN THE BATHROOM LOCATED AT APT D26, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Oct 10, 2025Apt 17A
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE LOWER SASH WINDOW, WINDOW AT EAST WALL IN THE 4th ROOM FROM NORTH LOCATED AT APT 17A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''2512''
Class BClosed
Oct 10, 2025Apt B20
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM EAST LOCATED AT APT B20, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2514''
Class BClosed
Oct 10, 2025Apt 17A
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE LOWER SASH WINDOW, WINDOW AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 17A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''2512''
Class BClosed
Oct 9, 2025Apt E24
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E24, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class BClosed
Oct 9, 2025Apt E24
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E24, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class CClosedRENT IMPAIRING
Oct 9, 2025
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT BULKHEAD CEILING AT PUBLIC HALL, 5th STORY
Class BClosed
Oct 9, 2025Apt D24
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT D24, 4th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class BClosed
Oct 9, 2025Apt B24
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER WINDOW SASH SPRING BALANCE AT 1ST WINDOW FROM NORTH AT EAST IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT B24, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class AClosed
Oct 9, 2025
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE BULKHEAD AT PUBLIC HALL, 5th STORY
Class BClosed
Oct 9, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT WEST WALL AT INTERMEDIATE LANDING AT PUBLIC HALL, 4th STORY, SECTION ''2516''
Class BClosedRENT IMPAIRING
Oct 9, 2025
INADEQUATE LIGHTING · ARTIFICIAL LIGHTING
§ 27-2038 ADM CODE PROVIDE ADEQUATE LIGHTING FOR THE FIXTURE AT CEILING 5TH STORY PUBLIC HALL AT PUBLIC HALL, 5th STORY
Class AClosed
Oct 9, 2025
POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES
§27-2045(B)(5) HMC, § 12-06, 12-10 RCNY POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN PRIVATE DWELLINGS MISSING
Class BClosed
Oct 9, 2025Apt B24
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER WINDOW SASH SPRING BALANCE AT 1ST WINDOW FROM WEST AT NORTH IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT B24, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class BClosed
Oct 9, 2025Apt D24
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER WINDOW SASH SPRING BALANCE AT 1ST WINDOW FROM WEST AT NORTH IN THE KITCHEN LOCATED AT APT D24, 4th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class BClosedRENT IMPAIRING
Oct 9, 2025
REMOVE ENCUMBRANCES · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF FURNITURE AT BULK HEAD AT PUBLIC HALL, 5th STORY
Class BClosed
Oct 9, 2025Apt B24
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOWER WINDOW SASH SPRING BALANCE AT 1ST WINDOW FROM SOUTH AT WEST IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT B24, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2516''
Class CClosed
Oct 9, 2025
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, SECTION ''2516''
Class BClosed
Oct 9, 2025
DOOR NOT SELF-CLOSING · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING AT BULK HEAD DOOR AT PUBLIC HALL, 5th STORY
Class AClosed
Oct 9, 2025
POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE
§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, SECTION ''2516''
Class CClosed
Oct 9, 2025
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE BULK HEAD CEILING AT PUBLIC HALL, 5th STORY
Class CClosed
Oct 8, 2025
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORY
Class BClosed
Oct 8, 2025Apt C18
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT C18, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Oct 8, 2025Apt C18
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE 1ST ELECTRICAL OUTLET FROM FROM WEST AT SOUTH WALL IN THE KITCHEN LOCATED AT APT C18, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Oct 8, 2025Apt C18
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ABOVE THE CEILING IN THE BATHROOM LOCATED AT APT C18, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class AClosed
Oct 8, 2025
CLEANSE · CLEANING
§ 27-2011 ADM CODE CLEANSE TO THE SATISFACTION OF THIS DEPARTMENT THE ALL STAIRS AND LANDINGS AT LOBBY, 1st STORY, SECTION ''2514''
Class AClosed
Oct 8, 2025
POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE
§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT LOBBY, 1st STORY, SECTION ''2514''
Class CClosed
Oct 8, 2025Apt C18
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE [HINGE] DOOR IN THE ENTRANCE LOCATED AT APT C18, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class AClosed
Oct 8, 2025
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR AT LOBBY, 1st STORY, SECTION ''2514''
Class BClosed
Oct 8, 2025
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT LOBBY AT PUBLIC HALL, 1st STORY, SECTION ''2512''
Class CClosed
Oct 8, 2025
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM AT LOBBY, 1st STORY, SECTION ''2514''
Class BClosed
Oct 8, 2025Apt C18
REPAIR LEAKY FAUCETS · WATER SUPPLY
§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS WASTELINE AT SINK BASIN IN THE KITCHEN LOCATED AT APT C18, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Oct 7, 2025Apt D18
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING LIGHT FIXTURE AT CEILING IN THE BATHROOM LOCATED AT APT D18, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class AClosed
Oct 7, 2025Apt D18
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE KITCHEN LOCATED AT APT D18, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Oct 7, 2025Apt D18
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT D18, 4th STORY, 1st APARTMENT FROM WEST AT NORTH