Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT BULKHEAD AT PUBLIC HALL, SECTION AT SOUTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 2nd STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 1st STORY
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 4th STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 3rd STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 4th STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 5th STORY, SECTION AT NORTH
Class BClosedRENT IMPAIRING
Jul 1, 2019
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK THROUGHOUT BULKHEAD CEILING AT PUBLIC HALL, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT ALL WALLS AT BULKHEAD AT PUBLIC HALL, SECTION AT NORTH
Class BClosed
Jul 1, 2019Apt 1D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 1D, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT BULKHEAD AT PUBLIC HALL, SECTION AT NORTH
Class BClosedRENT IMPAIRING
Jul 1, 2019
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK THROUGHOUT BULKHEAD CEILING AT PUBLIC HALL, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 5th STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 3rd STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 2nd STORY, SECTION AT NORTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 1st STORY
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 2nd STORY, SECTION AT SOUTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 3rd STORY, SECTION AT SOUTH
Class BClosed
Jul 1, 2019
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AND ALL WALLS AT PUBLIC HALL, 4th STORY, SECTION AT SOUTH
Class BClosed
Jun 28, 2019Apt 6D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosedRENT IMPAIRING
Jun 28, 2019Apt E
REMOVE ILLEGAL FASTENING · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING GATE AT FIRE ESCAPE WINDOW ON EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosedRENT IMPAIRING
Jun 28, 2019Apt E
REMOVE ILLEGAL FASTENING · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING LOCKABLE DOOR KNOB ASSEMBLY INSTALLED ON DOOR TO ROOM WITH FIRE ESCAPE WINDOW IN THE 1st ROOM FROM NORTH LOCATED AT APT E, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
Class BClosed
Dec 13, 2018Apt 1
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 4th ROOM FROM NORTH AT EAST LOCATED AT APT 1, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BClosed
Sep 17, 2018Apt 2D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE EAST CLOSET WALLS AND CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Sep 17, 2018Apt 2D
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE SPRING BALANCES UPPER WINDOW SASH AT THE 1ST AND 2ND WINDOWS FROM WEST AT NORTH IN THE 1st ROOM FROM NORTH LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Sep 17, 2018Apt 2D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE FLOOR IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Sep 17, 2018Apt 2D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE SOUTH WALL IN THE BATHROOM LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Sep 17, 2018Apt 2D
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE SPRING BALANCES LOWER WINDOW SASH, AT HE SECOND WINDWO FROM SOUTH AT WEST IN THE 3rd ROOM FROM NORTH LOCATED AT APT 2D, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
Class BClosed
Aug 2, 2018Apt 1D
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES LOCATED AT APT 1D, 5th STORY, 2nd APARTMENT FROM WEST AT NORTH
Class BClosed
Jul 27, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CONCRETE CEILING FRONT OF THE BUILDING AT FIRE PASSAGE WAY
Class BClosed
Mar 27, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT BULKHEAD CEILING AND ALL WALLS AT PUBLIC HALL
Class BClosedRENT IMPAIRING
Mar 27, 2018
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER BULKHEAD CEILING AT PUBLIC HALL
Class BClosed
Mar 27, 2018Apt 6D
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING BASEBOARD AT SOUTH WALL IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Mar 27, 2018Apt 6D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Mar 27, 2018Apt 6D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AND ALL WALLS IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosedRENT IMPAIRING
Mar 27, 2018Apt 6D
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Mar 27, 2018
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS AT BULKHEAD AT PUBLIC HALL
Class BClosed
Mar 20, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT CEILING AND WALLS AT BULKHEAD AT PUBLIC HALL, SECTION ''NORTH''
Class BClosed
Mar 20, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT CEILING AT ALL STORIES AT PUBLIC HALL, SECTION ''SOUTH''
Class BClosed
Mar 20, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT CEILING AT ALL STORIES AT PUBLIC HALL, SECTION ''NORTH''
Class BClosed
Feb 15, 2018Apt E
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR FRAME AND CASING IN THE BATHROOM LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 15, 2018Apt E
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 15, 2018Apt E
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 15, 2018Apt E
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 15, 2018Apt E
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT NORTH WALL (18 SQ FT ) IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 12, 2018Apt E
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT EAST WALL IN THE KITCHEN LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Feb 12, 2018Apt E
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE CLOSET DOOR IN THE PRIVATE HALLWAY LOCATED AT APT E, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BClosed
Jan 29, 2018Apt 6D
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6D, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Jan 29, 2018Apt 6D
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 6D, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class BClosed
Jan 29, 2018Apt 6D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE KITCHEN LOCATED AT APT 6D, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH