Class CClosed
May 31, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT ALL WALLS AT PUBLIC HALL, 2nd STORY
Class CClosed
May 31, 2018
REPLACE · MAINTENANCE
§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING SHEETROCK AT CEILING AT PUBLIC HALL, 2nd STORY
Class CClosed
May 31, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT PUBLIC HALL, 2nd STORY
Class CClosedRENT IMPAIRING
May 21, 2018
REMOVE ILLEGAL FASTENING · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF AN UNACCEPTABLE ELECTROMAGNECTIC LOCKING DEVICE INSTALLED AT BUILDING VESTIBULE ENTRANCE DOOR , 1st STORY
Class CClosed
May 21, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILED FLOOR AT AT BATH , 4th STORY
Class CClosed
May 21, 2018
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE WINDOW ,UPPER AND LOWER SASH(MISSING) AT SOUTH WALLAT WEST SECTION , 7th STORY
Class CClosed
May 21, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT ENTRANCE TO BATH AT EAST SIDE AT SOUTH , 3rd STORY
Class CClosed
Apr 13, 2018
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AT COMMUNITY BATHROOM, 6th STORY
Class CClosed
Apr 13, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR AT PUBLIC HALL, 6th STORY
Class CClosed
Apr 13, 2018
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK CEILING AT COMMUNITY BATHROOM, 6th STORY, SECTION AT NORTH
Class CClosed
Apr 13, 2018
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AT COMMUNITY BATHROOM, 6th STORY, SECTION AT NORTH
Class CClosed
Apr 13, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEILING AT PUBLIC HALL, 6th STORY
Class CClosedRENT IMPAIRING
Apr 6, 2018
REMOVE ILLEGAL FASTENING · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF AN UNACCEPTABLE ELECTROMAGNETIC LOCKING DEVICE INSTALLED AT VESTIBLE DOOR AT PUBLIC HALL, 1st STORY
Class CClosed
Apr 6, 2018
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM SIGN MISSING AT PUBLIC HALL, 1st STORY
Class CClosed
Mar 8, 2018Apt 7B8
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FIRE DAMAGE IN THE ROOM LOCATED AT B-ROOM 7B8, 7th STORY, 2nd B-ROOM FROM EAST AT SOUTH
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE HARDWOOD FLOOR AT PUBLIC HALL, 5th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WALLS AT PUBLIC HALL, 5th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE HARDWOOD FLOOR AT PUBLIC HALL, 6th STORY
Class CClosed
Mar 8, 2018
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE UPPER AND LOWER WINDOW GLASS AT PUBLIC HALL, 7th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WALLS AT PUBLIC HALL, 6th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE HARDWOOD FLOOR AT PUBLIC HALL, 7th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WALLS AT PUBLIC HALL, 4th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE HARDWOOD FLOOR AT PUBLIC HALL, 4th STORY
Class CClosed
Mar 8, 2018
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT COLD WATER PIPE AT PUBLIC HALL, 4th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WALLS AT PUBLIC HALL, 3rd STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE HARDWOOD FLOOR AT PUBLIC HALL, 3rd STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE HARDWOOD FLOOR AT PUBLIC HALL, 2nd STORY
Class CClosed
Mar 8, 2018
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE UPPER AND LOWER WINDOW GLASS IN THE PUBLIC BATHROOM AT PUBLIC HALL, 3rd STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AND WALLS AT PUBLIC HALL, 7th STORY
Class CClosed
Mar 8, 2018
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT PUBLIC HALL, 2nd STORY
Class CClosed
Mar 8, 2018
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE DOOR LOCK AT BULKHEAD TO ROOF
Class CClosed
Mar 6, 2018Apt 5A8
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILIN AND WALLS IN THE ROOM LOCATED AT B-ROOM 5A8, 5th STORY, 1st B-ROOM FROM EAST AT SOUTH
Class CClosedRENT IMPAIRING
Oct 13, 2017
REPAIR FLUSHING APPARATUS OF WATER CLOSET · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET .. AT COMMUNITY BATHROOM, 1st STORY
Class CClosed
Oct 12, 2017
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
Class CClosed
Aug 31, 2017
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM ... AT PUBLIC HALL, 1st STORY
Class CClosed
Aug 21, 2017
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEMENT FLOOR AT PUBLIC HALL, 3rd STORY
Class CClosed
May 10, 2017
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXTERIOR SURFACE MOUNTED JUNCTION BOX AND EXPOSED ELECTRICAL WIRES AT EAST WALL AT PUBLIC HALL, 7th STORY, SECTION ''7B/ WEST''
Class CClosed
May 10, 2017
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT NORTH WALL AT 1st COMMUNITY BATHROOM FROM NORTH AT WEST, 7th STORY, SECTION ''7B/ WEST''
Class CClosed
May 10, 2017
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AND CERAMIC TILES AT NORTH WALL BEHIND WASH BASIN AT 1st COMMUNITY BATHROOM FROM NORTH AT WEST, 7th STORY, SECTION ''7B/ WEST''
Class CClosedRENT IMPAIRING
Apr 25, 2016Apt 7A1
INADEQUATE HOT WATER SUPPLY (VOLUME) · WATER SUPPLY
§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES (WASH BASIN) IN THE ROOM LOCATED AT B-ROOM 7A1, 7th STORY, 1st B-ROOM FROM WEST AT NORTH , SECTION AT EAST
Class CClosed
Apr 13, 2016Apt 3B6
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 3B6, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST
Class CClosed
Apr 13, 2016Apt 2B9
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING (UNKEYED) IN THE ROOM LOCATED AT B-ROOM 2B9, 2nd STORY, 1st B-ROOM FROM SOUTH AT WEST , SECTION ''A / B'', AT EAST
Class CClosed
Aug 24, 2015
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE FURNANCE CEMENT AROUND BREECHING AT CELLAR
Class CClosed
Aug 24, 2015
REPAIR · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE WINDOW BALANCE AT LOWER SASH AT SOUTH WALL AT PUBLIC HALL, 3rd STORY, SECTION AT NORTH
Class CClosed
Oct 22, 2014Apt 6S2
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PAINTED SPRINKLER HEAD IN THE ROOM LOCATED AT B-ROOM 6S2, 6th STORY, 1st B-ROOM FROM NORTH AT EAST , SECTION ''BLDG 350''
Class CClosed
Oct 21, 2014
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FLOWER POTS FREE STANDING AT 5TH & 6TH WINDOW SILLS FROM WEST TO EAST ,ON 4TH STORY BUILDING FRONT EXTERIOR WALL
Class CClosed
Aug 20, 2014
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE METAL TREADS 1ST, 2ND. 3RD, 4TH, 5TH, 6TH, 7TH, 8TH, 9TH STAIRS FROM BOTTOM AND PLATFORM FROM SAIRS CELLAR TO STREET LEVEL AT FRONT AREAWAY
Class CClosed
Aug 20, 2014
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE LOOSE BRICKS AND MORTIS JOINT AT VAULTED CEILING AT CELLAR ENTRANCE AT FRONT AREAWAY
Class CClosed
Aug 20, 2014
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE ERODED METAL SUPPORT BEAMS 1ST AND 2ND FROM EAST AT VAULTED CEILING AT CELLAR ENTRANCE AT FRONT AREAWAY
Class CClosed
Jul 31, 2014
RETIRED - REPLACE WITH NEW THE BROKEN AND DEFECTIVE · RETIRED
§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE ERODED METAL SUPPORT BEAMS 1ST AND 2ND FROM EAST AT VAULTED CEILING, AT CELLAR ENTRANCE, AT FRONT AREAWAY